ECR International Utica Boilers MAH-125 Installation, Operation And Maintenance Manual page 24

Condensing wall mounted gas fired boiler
Table of Contents

Advertisement

12" (305 mm) Min. horizontal separation
between combustion air intake and vent of
same appliance.
 12" (305 mm) Min. 84" (2.2 m) Max. vertical
separation between combustion air intake and
vent of different appliances.
 15" (381 mm) Max. horizontal length of vent.
Roof
 Min. vent/intake between different appliances
Terminations
12" (305 mm).
 Max. allowable total vertical vent length with
outside exposure is 10 ft.(3.05 m).
 Abandoned unused masonry chimney may be
used as chase-way for combustion air and
vent. Both combustion air and vent pipe must
exit above top of chimney with clearances as
shown in Figure 5-14.
FIGURE 5-12 - Twin Pipe on Roof Combustion Air On
Sidewall
CAN BE USED ON ALL SIZES
Vent Terminal
Combustion Air
Ground
Level
FIGURE 5-13 - Twin Pipe Flue On Sidewall,
Combustion Air On Roof CAN BE USED ON ALL SIZES
Combustion Air
Vent - T Terminal
12" (305 mm)
Anticipated Snow Line
5 - COMBUSTION AIR AND VENT PIPING
FIGURE 5-14 - (2"/ 60 mm & 3" / 80 mm) Twin Pipe
Roof Vent CAN BE USED ON ALL SIZES
This Termination
12" (305 mm) Min.
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
Vent
12" (305 mm) US,
18" (458 mm) Canada Min.
Above
Anticipated Snow Line
FIGURE 5-15 - (3" / 80 mm ONLY) Single Wall
Exhaust Kit and Air Intake Minimum Distance Center
to Center
This Termination
can be used on:
3" / 80 mm
ALL SIZES
vent pipe only
See Grade,
Snow & Ice
FIGURE 5-16 - Horizontal Twin Pipe, Exhaust and
Intake
This Termination
can be used on:
2" / 60 mm ON
Minimum Separation
165/205
3" / 80 mm
ON ALL SIZES
vent only
See Grade,
Snow & Ice
22
15"
(381 mm)
Max.
Roof Line
Combustion
Air
43/4"
[120 mm]
12" (305 mm)
Manufacturer
Recommends
Greater Separation
240011941 REV G, [06/30/2019]