FIGURE 5-4 Roof Mount Coaxial Venting
CAN BE USED ON ALL SIZES
FIGURE 5-5 - Coaxial Vertical Exhaust -
CAN BE USED ON ALL SIZES
12" (305 mm)
Minimum Separation
5 - COMBUSTION AIR AND VENT PIPING
Maintain 12"(305 mm)
US (18"(457 mm)
Canada) clearance
above highest
anticipated snow level
Anticipated
Snow Line
24" (610 mm) above
roof or ground
Multiple
Appliances
Manufacturer
Recommends
Greater Separation
FIGURE 5-6 Side Wall Coaxial Venting
CAN BE USED ON ALL SIZES
FIGURE 5-7 - Coaxial Horizontal Exhaust -
CAN BE USED ON ALL SIZES
19
18" Vertical
Clearance to
ventilated soffit
Min. 8" (181 mm)
Max. 14" (356 mm)
Maintain 12"(305 mm)
US (18"(457 mm)
Canada) clearance
above highest
anticipated snow level
24" (610 mm) above
roof or ground
Anticipated
Snow Line
Ground
Multiple
Appliances
24" (610 mm)
Min. Separation
Manufacturer
Recommends
Greater Separation
recommends gr