Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G
install in a sturdy manner to avoid increased operating
noise.
Table 3
Allowable
Model
Tubing Length
CMH1972
CMH2472
CMH3172
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary.
2:56 PM
Page 5
Max.
Max. Allowable Total
Tubing Length
at shipment
per unit
(L1+L2+L3) or
(ft.)
(L1+L2+L3+L4)
(ft.)
82
150 (L1+L2+L3)
82
150 (L1+L2+L3+L4)
100
150 (L1+L2+L3+L4)
Limit of
Limit of Elevation
Total Tubing Length
Difference
(L1+L2+L3) or
(H1, H2, H3, H4)
(L1+L2+L3+L4)
(ft.)
(ft.)
150 (L1+L2+L3)
50
200 (L1+L2+L3+L4)
50
230 (L1+L2+L3+L4)
50
5
Required Amount
of Additional
Refrigerant
*
(oz./ft.)
0.22
0.22