4. Air Purging

Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they
must be purged completely.
G
pressure in the system rises
G
operating current rises
G
cooling efficiency drops
G
moisture in the air may freeze and block capillary tubing
G
water may lead to corrosion of parts in the refrigerant
system
I
Air Purging with a Vacuum Pump
(for Test Run)
G
In order to protect the earth's environment, be sure to use
a vacuum pump to perform the air purge.
(Never perform an air purge by using the refrigerant gas
cylinder or other external gas, or by using the gas inside
the outdoor unit.)
CAUTION
Perform the air purge for tubes A, B, C, and D. Use the
same procedures for all tubes.
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been
properly connected and all wiring for the test run has
been completed. Note that both narrow and wide tube
service valves on the outdoor unit are kept closed at
this stage.
(2) Using an adjustable wrench or box wrench, remove
the valve caps from the service valve on both narrow
and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube
service valve. (Fig. 20).
CAUTION
CAUTION
2:56 PM
Page 16
In order to prevent charging errors with
A/C that uses R410A, the screw diameter
at the service valve charging port has
been changed. When recharging or per-
forming other servicing, use the special
charging hose and manifold gauge.
Before using the vacuum pump
adapter, read the vacuum pump
adapter manual, and use the
adapter correctly.
Be sure to use a manifold valve for
air purging. If it is not available,
use a stop valve for this purpose.
The "Hi" knob of the manifold
valve must always be kept closed.
Service
valve on
D
narrow
C
Service
B
valve on
wide tube
A
side
Hex wrench
With push-pin
Stopper
Spindle
Screw diameter: 1/2
UNF 20 threads
Valve core
Cap nut tightening torque:
60 – 95 lbs·in
(70 – 110 kgf·cm)
(Tighten by hand, then use a
wrench to turn approximately 30 .)
<Structure of service valve on wide tube side>
When using a hex wrench to open the spindle, an
G
extremely small amount of refrigerant may leak.
This does not indicate a problem.
Use a hex wrench of a type to which force can be
G
easily applied.
16
Manifold gauge
(special for R410A)
High-pressure valve
Low-pressure
valve
Vacuum pump
adapter
(for preventing
Leave the
Lo
Hi
reverse flow)
valve open.
(special for
Open
R410A)
Vacuum
pump
Charging hose
(special for R410A)
Fig. 20
Cap tightening torque:
170 – 215 lbs·in
(200 – 250 kgf·cm)
(Tighten by hand, then
use a wrench to turn.)
Fig. 21