Sanyo CLM1972 Technical & Service Manual page 57

Dc inverter multi-system air conditioner
Hide thumbs Also See for CLM1972:
Table of Contents

Advertisement

(7) Branch tubing temperature sensor
Check that the sensor is securely contained in the thermostat holder.
(8) Breaker
Check whether or not the breaker has been tripped.
Check that the breakers and fuses used are of the specified capacity.
Check that the breaker and its line are exclusive for A/C use.
(9) Refrigerant gas pressure
Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values
with the performance charts.
If the values are higher than the performance charts:
Check for refrigerant shortage or blockage of the refrigerant circuit.
< Assessment of refrigerant shortage >
1. The pressure in the low-pressure section is 5 MPa or more below the value in the performance charts.
2. There is little condensation on the indoor heart exchanger, which overall appears dry.
< Distinguishing between refrigerant shortage and refrigerant circuit blockage >
If the pressure in the low-pressure section does not change when the circuit is charged 2 to 3 times with
refrigerant gas (0.44 lbs each time), or if the change is small, then the problem may not be
refrigerant shortage.
The problem may be a blockage of the refrigerant circuit.
1. Check that there is no internal leakage inside the 4-way valve:
At the low-pressure side tubing, check that there is no temperature difference between the intake and
discharge of the 4-way valve.
2. Check that the electric expansion valve is not blocked. Check as described on the preceding page.
57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Clm3172Clm2472Cm1972Cm3172Cm2472

Table of Contents