Sanyo CLM1972 Technical & Service Manual page 14

Dc inverter multi-system air conditioner
Hide thumbs Also See for CLM1972:
Table of Contents

Advertisement

CLM3172
Outdoor Unit
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Run Capacitor
Crankcase Heater
Fan
Type
Q'ty ... Dia.
Fan Motor
Type
Model ... Q'ty
No. of Poles
Rough Measure RPM (Cool)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type
Over-Current Protection
Over-Heat Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows
Fins per inch
Face Area
External Finish
Pints (cc)
Ohm
Model
Operation Temp.
Micro F
VAC
inch (mm)
W
Ohm
Micro F
VAC
ft
(m
)
2
2
14
CB-CLM3172
Microprocessor
250V 25A
DC Twin Rotary (Hermetic)
5JD420XAB22 / 3,000W
FV50S ... 2.55 (1,200)
U - V :
V - W :
W - U :
Yes
Yes
Yes
CS-7LN115
Open : 239 °F (115 °C), Close : 212 °F (100 °C)
-
-
230V 30W
Propeller
1 ... D18-1/8 (D460)
DC Motor
SIC-71FW-D490-1 ... 1
8
800
90
-
Internal Controller
Yes
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
18.1
7.75 (0.72)
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
0.435
0.441
0.452

Hide quick links: