Sola ups 520 User Manual

750 va, 1050 va, 1425 va, and 2250 va

Advertisement

Quick Links

USER GUIDE
ups 520
750 VA, 1050 VA, 1425 VA, and 2250 VA
Company
A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ups 520 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sola ups 520

  • Page 1 USER GUIDE ups 520 750 VA, 1050 VA, 1425 VA, and 2250 VA Company...
  • Page 2 Important Notice The UPS ground (earth) conductor carries leakage current from the loads in addition to any leakage current generated by the UPS. This UPS generates no more than 0.5 mA of current (U model), or 1 mA of current (A & E model). To limit the total leakage current to 3.5 mA, the load leakage must be limited to 3 mA on the U model and 2.5 mA on the A &...
  • Page 3 ® u p s 5 2 0 750 VA, 1050 VA, 1425 VA and 2250 VA User Guide STM-0408A © Copyright 1998, Best Power. All rights reserved.
  • Page 4 SOLA’s service technicians have in-depth knowledge of the UPS and power problems. SOLA may tell you the UPS must be returned. If this happens, we will give you a Return Authorization (RA) number. When you return a SOLA 520 to the factory for any reason, please use the original packing material in which your unit was shipped to you.
  • Page 5: Table Of Contents

    SOLA Australia Offices ........
  • Page 6: Safety Instructions

    For assistance, call SOLA Service or your local SOLA office. If the SOLA 520 unit has been damaged during shipment, call your vendor immediately. If the SOLA 520 unit is stored, the batteries should be recharged every 6 months. If stored above 25 Celsius, recharge the batteries more often.
  • Page 7: Ups Features

    520 UPS Features The SOLA 520 provides protection against power problems, including power outages, brownouts, and sudden increases in power. It also provides spike suppression and line noise filtering to protect your equipment. Front panel LEDs and an audible alarm keep you aware of the unit’s status.
  • Page 8: Quick Startup

    520 Quick Startup If your SOLA 520 UPS has a removable power cord, connect the power cord to the back of the unit. Plug the UPS into a wall outlet. Even if the UPS is turned off, the battery charger will operate when input power is applied to the UPS.
  • Page 9: Installing Checkups Ii Software

    BestDock Installation and Operation of the SNMP Card Option The SOLA 520’s BestDock communication slot accepts optional communication cards, like the internal BestLink SNMP/WEB adapter. The insertion of a card into the BestDock communication slot replaces the normal communication channel from the SOLA 520’s DB-9 Communication Port.
  • Page 10: Symbols, Leds And Audible Beeps

    See Table 3 for information on beep coding. In the figure below, bucking means that SOLA 520 is reducing high input voltage, and boosting means SOLA 520 is increasing low input voltage.
  • Page 11 See Tables 3 and 4. If your SOLA 520 runs on batteries frequently because the input utility line varies often, you may want to adjust your SOLA 520 to accept wider voltage variations before switching to batteries. Appendix A describes how to adjust the SOLA 520 from the front panel in response to specific utility power problems.
  • Page 12: Troubleshooting

    SOLA Service or your local SOLA office. Please have the model number and serial number (located on the rear of the unit) available. If the unit must be returned, SOLA will give you a Return Authorization (RA) number. Please phone SOLA for an RA number before returning the unit for any reason.
  • Page 13: Replacing The Batteries

    520 Replacing the Batteries SOLA 520’s batteries are user-replaceable and can be replaced while the SOLA 520 has AC input applied and powers the loads. This means that, if necessary, you can replace the batteries while the UPS is running. Before you replace the batteries, make sure that you read the safety information below.
  • Page 14: Replacement Instructions

    520 Replacement Instructions Phone Best Power’s Worldwide Service to order a replacement battery pack. It must be the same type and rating of the original batteries. See Battery information in Specifications. If it is necessary, the batteries may be replaced while the Fortress is running with the protected equipment attached.
  • Page 15: Communication Port

    Windows 3.X, 95 and NT Novell NetWare SOLA offers interface kits that allow you to connect many other computer systems to the SOLA 520’s communication port. For the following computer systems, or specific information on SOLA interface kits, call SOLA Service or your local SOLA dealer.
  • Page 16: Specifications

    520 Specifications SOLA reserves the right to change specifications without prior notice. Line Transient Protection: Passes ANSI/IEEE C62.41 Category A testing. Safety Compliance: TUV/GS Listed, AS3260 EMC Compliance: CISPR 22 Class B, Vfg 243-91/46-92 B, EN55022, CE Mark Self-certified to: CE Marking Directive 93/68/EEC, Low Voltage Directive 73/23/EEC, C-Tick, AS3548.
  • Page 17: Warranty

    Storage Temperature: -15° to +50° C. Battery life is reduced above 25 ° C. If the SOLA 520 unit is stored, the batteries should be recharged every 6 months. If stored above 25° Cel- sius, recharge the batteries more often.
  • Page 18 4. For units up to 3kVA that are installed as a portable device, the Warranty covers repair or replacement of defective parts at the factory, or other service locations as nominated by Sola Australia, provided the unit has been returned by the user packed adequately to prevent shipping damage, and approval has been obtained from SOLA Australia Ltd before shipment.
  • Page 21: Appendix A: Adjusting Voltage Settings

    • Nominal Voltage — The normal voltage the UPS is programmed to expect, and the nominal UPS output voltage under line loss conditions. • Buck — The input voltage at which the SOLA 520 decreases voltage before providing output because the input voltage is too high.
  • Page 22 Press this button 4. Once the correct LEDs are lit, continue to hold the button for 10 for ten seconds to save your changes. If the SOLA 520 is SECONDS to running on AC input power, the display will change back save your to the percent of full load.
  • Page 23: Sola Australia Offices

    520 SOLA Australia Offices Head Office - Melbourne Sola Australia Ltd. 13 Healey Road Dandenong VIC 3175 Phone: 61-3-9706-5022 Fax: 61-3-9794-9150 National Service and Repair Centre Free Call: 1800 034 401 (except Melbourne) 9768 3105 (Melbourne only) Customer Service Offices...
  • Page 24 2 year warranty against defects in material and workmanship. This product is backed by over 60 years of pride and integrity. We are sure you will agree, there is no substitute for a SOLA. SOLA is one of the Best group of companies Did you know that SOLA also makes: •...

Table of Contents