indoor unit installation

3 INDOOr uNIT INsTALLATION
D A N G E r
• Check to ensure that the accessories are packed with the
indoor unit.
• Do not install the indoor units outdoors. If installed out-
doors, an electric hazard or electric leakage will occur.
• Consider the air distribution from each indoor unit to the
space of the room, and select a suitable location so that
uniform air temperature in the room can be obtained. It is
recommended that the indoor units be installed 2.3 to 3
meters from the floor level. If the unit is installed higher
than 3 meters, it is also recommended that a fan be utili-
sed to obtain uniform air temperature in the room.
• Avoid obstacles which may hamper the air intake or the
air discharge flow.
• Pay attention to the following points when the indoor
units are installed in a hospital or other places where the-
re are electronic waves from medical equipment, etc.
• Do not install the indoor units where electromagnetic wave
is directly radiated to the electrical box, remote control cable
or remote control switch.
• Prepare a steel box and install the remote control switch
in it. Prepare a steel conduit tube and wire the remote
control cable in it. Then connect the ground wire with the
box and tube.
• Install a noise filter when the power supply emits harmful
noises.
3.1 uNIT INsTALLATION
3.1.1 Factory-Supplied Accessories
Accessory
Pattern Board
(Carton Board)
Checking Scale
Cross Recessed
Head Screws
(m6)
Washer with in-
sulation material
(m10)
Washer (m10)
Drain Hose
Hose Clamp
6
Qty.
Purpose
for adjusting space
1
of false ceiling
opening and
position of the unit
1
For fitting paper
4
pattern
4
for unit installation
4
1
for Drain Hose
Connection
1
PmmL0223A rev.0 - 05/2012 - P5415035
• This unit is exclusive non electrical heater type indoor
unit. It is prohibited to install a electrical heater in the
field.
• Do not put any foreign material into the indoor unit and
check to ensure that none exist in the indoor unit before
the installation and test running. Otherwise a fire or failu-
re, etc., may occur.
C A u T I O N
Do not install the indoor units in a flammable environment to
avoid a fire or an explosion.
Check to ensure that the ceiling slab is strong enough. If not
strong enough, the indoor unit may fall down on you.
Do not install the indoor units in a machinery shop or kitchen
where vapor from oil or mist flows to the indoor units. The oil
will deposit on the heat exchanger, thereby reducing the indo-
or unit performance, and may deform. In the worst case, the
oil damages the plastic parts of the indoor unit.
To avoid any corrosive action to the heat exchangers, do not
install the indoor units in an acid or alkaline environment.
When lifting or moving the indoor unit, use appropriate slings
to avoid damage and be careful not to damage the insulation
material on units surface.
Accessory
Pipe insulation
Pipe insulation
Cord clamp
Cord clamp
insulation
(5Tx50x200)
insulation
(5Tx100x200)
insulation
(5Tx25x500)
Qty.
Purpose
1
for refrigerant
piping connection
1
For fixing remote
2
control switch
wiring, louver
sensor and
6
insulation of piping
for covering wiring
1
connection
1
for covering drain
connection
1

Advertisement

Chapters

loading

This manual is also suitable for: