Start Up & Performance; Checking Airflow; Checking Refrigerant Charge; Charging By Liquid Pressure - Rheem 15 SEER Series Installation Instructions Manual

Table of Contents

Advertisement

10.0 ST RT UP ND PERFORM NCE
Even though the unit is factory charged with Refrigerant-410A, the charge must be
checked to the charge table attached to the service panel and adjusted, if required.
(See Table 1). Allow a minimum of 5 minutes running. Before analyzing charge, see
the instructions on the unit service panel rating plate for marking the total charge.
11.0 CHECKING IRFLOW
The air distribution system has the greatest effect on airflow. The duct system is
totally controlled by the contractor. For this reason, the contractor should use only
industry-recognized procedures.
Heat pump systems require a specified airflow. Each ton of cooling requires
between 350 and 450 cubic feet [165.2 and 212.4 L/s] of air per minute (CFM) [L/s],
or 400 CFM [188.8 L/s] nominally.
Duct design and construction should be carefully done. System performance can be
lowered dramatically through bad planning or workmanship.
Air supply diffusers must be selected and located carefully. They must be sized and
positioned to deliver treated air along the perimeter of the space. If they are too
small for their intended airflow, they become noisy. If they are not located properly,
they cause drafts. Return air grilles must be properly sized to carry air back to the
blower. If they are too small, they also cause noise.
The installers should balance the air distribution system to ensure proper quiet air-
flow to all rooms in the home. This ensures a comfortable living space.
An air velocity meter or airflow hood can give a reading of the system CFM [L/s].
12.0 CHECKING REFRIGER NT CH RGE
Charge for all systems should be checked against the Charging Chart inside the
access panel cover.
IMPORTANT: Do not operate the compressor without charge in system.
Addition of R-410A will raise pressures (vapor, liquid and discharge).
If adding R-410A raises both vapor pressure and temperature, the unit is over-
charged.
IMPORTANT: Use industry-approved charging methods to ensure proper system
charge.
12.1 CH RGING BY LIQUID PRESSURE
The liquid pressure method is used for charging systems in the cooling and heating
mode. The service port on the liquid (small valve) and suction (large valve) is used
for this purpose.
Verify that the outdoor unit is running and the indoor air mover is delivering the
maximum airflow for this system size. Read and record the outdoor ambient tem-
perature. Read and record the liquid and suction pressures at the ports on the liquid
and suction valves.
If refrigerant lines are sized using the nameplate charge, the correct liquid pressure
is found at the intersection of the suction pressure and the outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

15 seer 1815 seer 2415 seer 3015 seer 3615 seer 42

Table of Contents