If the system needs to be running under power consumption
limitation conditions when an external signal is sent to the unit, this
setting defines the level power consumption limitation that will be
applied for step 2. The level is according to the table.
[2‑31]
Power consumption limitation
1 (default)
2
3
[2‑32]
Forced, all time, power consumption limitation operation (no external
control adaptor is required to perform power consumption limitation).
If the system always needs to be running under power consumption
limitation conditions, this setting activates and defines the level
power consumption limitation that will be applied continuously. The
level is according to the table.
[2‑32]
0 (default)
Function not active.
1
Follows [2‑30] setting.
2
Follows [2‑31] setting.
[2‑35]
Height difference setting.
[2‑35]
0
In case the outdoor unit is installed in the
lowest position (indoor units are installed on a
higher position than outdoor units) and the
height difference between the highest indoor
unit and the outdoor unit exceeds 40 m, the
setting [2‑35] should be changed to 0.
1 (default)
Other changes/limitations to the circuit apply, for more information
see
"5.3.5 Piping length: VRV DX only" on
[2‑49]
Height difference setting.
[2‑49]
0 (default)
1
In case the outdoor unit is installed in the
highest position (indoor units are installed on a
lower position than outdoor units) and the
height difference between the lowest indoor
unit and the outdoor unit exceeds 50 m, the
setting [2‑49] has to be changed to 1.
Other changes/limitations to the circuit apply, for more information
see
"5.3.5 Piping length: VRV DX only" on
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
[2‑81]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings,
see
"7.3 Energy saving and optimum operation" on
[2‑82]
Heating comfort setting.
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1 – 2018.07
(approximately)
40%
50%
55%
Restriction reference
Description
page 15.
Description
page 15.
Cooling comfort setting
page 39.
This setting is used in conjunction with setting [2‑9].
[2‑82]
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings,
see
"7.3 Energy saving and optimum operation" on
[2‑83]
Master user interface allocation in case VRV  DX indoor units and
RA DX indoor units are used at the same time.
By changing setting [2‑83], you can allow the VRV DX indoor unit to
be the operation mode selector (system power OFF/ON is required
after applying this setting).
[2‑83]
0
VRV DX indoor unit has mode selection right.
1 (default)
RA DX indoor unit has mode selection right
setting.
7.2.9
To connect the PC configurator to the
outdoor unit
2
3
4
5
a
PC
b
Cable (EKPCCAB)
c
Outdoor unit main PCB
7.3
Energy saving and optimum
operation
This heat pump system is equipped with advanced energy saving
functionality. Depending on the priority, emphasises can be put on
energy saving or comfort level. Several parameters can be selected,
resulting in the optimal balance between energy consumption and
comfort for the particular application.
Several patterns are available and explained below. Modify the
parameters to the needs of your building and to realize the best
balance between energy consumption and comfort.
No matter which control is selected, variations on the behaviour of
the system are still possible due to protection controls to keep the
unit operating under reliable conditions. The intentional target,
however, is fixed and will be used to obtain the best balance
between energy consumption and comfort, depending on the
application type.
Care should be taken about selection procedures and system
setups, especially when using Hydrobox units. The requested
leaving water temperature from the Hydrobox has priority over this
energy saving control, as it is related to the required water
temperature.
7 Configuration
Heating comfort setting
page 39.
Description
a
c
b
X27A
A1P
Installer and user reference guide
39