5 Piping installation
NOTICE
If glycol was added to the water circuit, and the
temperature of the water circuit is low, the flow rate will
NOT be displayed on the user interface. In this case, the
minimum flow rate can be checked by way of the pump
test (check that the user interface does NOT display error
7H).
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).
See the installer reference guide for more information.
See the recommended procedure as described in
commissioning" [ 4  37].
during
5.2

Connecting water piping

5.2.1

To connect the water piping

NOTICE
Do NOT use excessive force when connecting the field
piping and make sure the piping is aligned properly.
Deformation of the piping can cause malfunctioning of the
unit.
1 Connect the outdoor unit field piping to the water connection
pipes of the indoor unit.
Do NOT exceed the maximum tightening torque (Thread size 1",
25-30  N•m). To avoid damage, apply the necessary countertorque
with a suitable tool.
3
≤Ø7 mm
1
2 Remove the thermal insulation of the hydraulic block. Open the
vent valve on the pump by one turn. Afterwards put the thermal
insulation back on the hydraulic block.
Installation manual
10
"8.2  Checklist
2
NOTICE
The thermal insulation can easily be damaged if NOT
handled correctly.
▪ ONLY remove parts in the order and direction as
indicated here,
▪ do NOT use force,
▪ do NOT use tools,
▪ re-install the thermal insulation in reverse order.
3 Connect the shut-off valves using the flat gaskets (accessory
bag) to the space heating/cooling water pipes of the indoor unit.
4 Connect the space heating/cooling field piping to the shut-off
valves using a sealing.
Do NOT exceed the maximum tightening torque (Thread size 1",
25-30  N•m). To avoid damage, apply the necessary countertorque
with a suitable tool.
2
3
1
≤Ø7 mm
5 Connect the domestic hot water in and out pipes to the indoor
unit.
Do NOT exceed the maximum tightening torque (Thread size 1",
25-30  N•m). To avoid damage, apply the necessary countertorque
with a suitable tool.