Liquid Level Alarm

4. OPERATION and TROUBLESHOOTING

4.1 State Table and Troubleshooting - Indoor Alarm Display

LED
AUDIO
OFF
OFF
GREEN
OFF
STEADY
RED
PULSING
FLASHING
RED
MUTED
FLASHING
RED
OFF
STEADY
YELLOW
PULSING
FLASHING
YELLOW
CONTINUOUS
STEADY
GREEN /
YELLOW
CONTINUOUS
FLASHING
RED
CONTINUOUS
STEADY
RED /
YELLOW
CONTINUOUS
FLASHING
As it was
CHIRP
Page 12
HIGH LEVEL
LOW LEVEL
(i.e. Septic tank)
(i.e. Cistern)
No Power
PROBE
PROBE DRY
WET
ALARM
ALARM -
- PROBE
PROBE WET
DRY
ALARM
ALARM -
- PROBE
PROBE WET
DRY
DISPLAY GOING INTO
PROGRAMMING MODE
MANUAL TEST
NO WIRELESS SIGNAL
PROBE ERROR
PROBE SHORT
PROBE DISCONNECTED
LOW BATTERY
CORRECTIVE ACTION
Check breaker
Check Transformer
Check plug into display
OK
OK
OK
See 4.3.1
OK
Replace batteries (See 5.1)
Check for radio interference
Change radio frequency Transmitter
out of range
Replace probe
Check polarity of probe conductors
Check the probe wire for damage
Check outdoor transmitter interior for
moisture
Replace probe
Check battery polarity
Connect probe wires (See 4.2)
Check probe wire for damage; make a
waterproof repair
Replace batteries (See 5.1)