TriangleTube EXRKIT131 Conversion Kit Instructions

Advertisement

Quick Links

Propane to Natural Gas Conversion
Kit Part Number
EXRKIT131
EXRKIT132
EXRKIT133
Kit Includes
Propane Gas Venturi
Venturi/blower O RIng
Venturi Gasket
Venturi/Blower Screws
Gas Pipe Gaskets
Aucoustic Dampening Foam (EXRKIT131 & EX-
RKIT132 Only)
Rating Label
Conversion Label
WARNING
!
Indicates a potentially hazardous situation which,
if ignored, can result in serious injury or substan-
tial property damage.
WARNING
!
For your safety, turn off electrical power supply
at service panel and allow unit to cool before pro-
ceeding to avoid possible electrical shock and
scald hazard. Failure to do so can cause severe
personal injury or death.
NOTICE
Upon completion of the conversion from Natural to Pro-
pane, affix the new rating label included in the kit to the
unit adjacent to the existing rating label. DO NOT affix
the new label over the existing rating label. Add propane
conversion labeling to the gas valve.
Revision Date: 9/12/2022
Exalt
Description
NG to LP Conversion
NG to LP Conversion
NG to LP Conversion
Recommended Tools
Adjustable Wrench / 10 mm Socket & Ratchet
Phillips Head Screwdriver
Flat Head Screwdriver
Calibrated Combustion Analyzer
NOTICE
Indicates special instructions on installation, operation
or maintenance, which are important to equipment
but not related to personal injury hazards.
WARNING
!
Failure to follow instructions below can result in
severe personal injury or damage if ignored.
Instructions are for a qualified installer/ ser-
vice technician only.
Read all instructions before proceeding.
Follow instructions in proper order.
NOTICE
These instructions cover NG to LP conversion for Exalt
boilers only. Each kit is supplied with one venturi suitable
for use with that particular boiler model.
Model
Exalt 110 Solo
Exalt 155 Solo & Combi
Exalt 199 Solo & Combi
2019-30 Exalt NG to LP Conversion

Advertisement

loading
Need help?

Need help?

Do you have a question about the EXRKIT131 and is the answer not in the manual?

Questions and answers

Summary of Contents for TriangleTube EXRKIT131

  • Page 1 • Flat Head Screwdriver • Venturi/Blower Screws • Calibrated Combustion Analyzer • Gas Pipe Gaskets • Aucoustic Dampening Foam (EXRKIT131 & EX- RKIT132 Only) • Rating Label • Conversion Label NOTICE WARNING Indicates special instructions on installation, operation Indicates a potentially hazardous situation which,...
  • Page 2: Preliminary Instructions

    EXALT NATURAL TO PROPANE CONVERSION INSTRUCTIONS 1. Preliminary Instructions: 1. Verify that the venturi replacement kit is correct for the model of boiler. See page 1. 2. Turn off electrical power supply to the boiler. 3. Close the manual gas shut off valve to the unit. 4.
  • Page 3 EXALT NATURAL TO PROPANE CONVERSION INSTRUCTIONS substantial property damage, serious injury, or death. NOTICE 2. Install the new venturi/blower gasket into the The Exalt boiler has a length of acoustic foam already in- blower. stalled in the air inlet adaptor. DO NOT remove this 3.
  • Page 4 EXALT NATURAL TO PROPANE CONVERSION INSTRUCTIONS over the applicable part of the existing rating label 5. Combustion Test and Adjustments NOTICE The installer MUST perform a complete combustion check to ensure the following combustion levels are met at high and low input firing rates and the burner is operating at op- timum conditions.
  • Page 5 EXALT NATURAL TO PROPANE CONVERSION INSTRUCTIONS Clockwise adjustment of the THROTTLE SCREW at High Fire (100% firing rate): NOTICE increases and CO decreases An adequate CH load must be present to dissipate the heat generated during the combustion test. If an adequate CH 7.
  • Page 6 EXALT NATURAL TO PROPANE CONVERSION INSTRUCTIONS Fig. 9: Throttle Screw Location...

This manual is also suitable for:

Exrkit132Exrkit133