Nortek BENSON VRA-4 12 Installation, Commissioning, Servicing And User Instructions

Gas-fired, balanced flue or power vented unit heater

Advertisement

Gas‐fired, balanced flue or  
power‐vented unit heater 
VRA‐4 
12, 20, 30, 35, 45, 50, 
60, 75, 100, 120, 145 
INSTALLATION – COMMISSIONING – SERVICING ‐ USER 
Please  read  this  document  carefully  before  commencing  installation  commissioning  and/or  servicing. 
Leave it with the user or attached to the appliance or gas service meter after installation. 
 
ATTENTION 
Improper  installation,  adjustment,  alteration,  service  or  maintenance  can  cause  property  damage, 
injury or death. All work must be carried out by appropriately qualified persons. The manufacturer does 
not take any responsibility in the event of non‐observance of the regulation concerning the connection 
of  the  apparatus  causing  a  harmful  operation  possibly  resulting  in  damage  to  the  apparatus  and/or 
environment in which the unit is installed. 
This appliance meets the following EC Directives 
DIR 2009/142/EC : GAD 
DIR 2004/108/EC : EMC 
DIR 2006/95/EC : LVD 
DIR 2006/42/EC : MD 
INSTRUCTIONS 
1610VRA4‐AMEN, p. 1/24 

Advertisement

Table of Contents
loading

Summary of Contents for Nortek BENSON VRA-4 12

  • Page 1 Gas‐fired, balanced flue or   power‐vented unit heater  VRA‐4  12, 20, 30, 35, 45, 50,  60, 75, 100, 120, 145  This appliance meets the following EC Directives  DIR 2009/142/EC : GAD  DIR 2004/108/EC : EMC  DIR 2006/95/EC : LVD  DIR 2006/42/EC : MD  INSTALLATION – COMMISSIONING – SERVICING ‐ USER  INSTRUCTIONS  Please  read  this  document  carefully  before  commencing  installation  commissioning  and/or  servicing.  Leave it with the user or attached to the appliance or gas service meter after installation.    ATTENTION  Improper  installation,  adjustment,  alteration,  service  or  maintenance  can  cause  property  damage,  injury or death. All work must be carried out by appropriately qualified persons. The manufacturer does  not take any responsibility in the event of non‐observance of the regulation concerning the connection  of  the  apparatus  causing  a  harmful  operation  possibly  resulting  in  damage  to  the  apparatus  and/or  environment in which the unit is installed. ...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS      1.0 INTRODUCTION             p 3    6.2   Gas Connection    1.1   Basic Information    6.3   Suspension and Support    1.2   Warranty    6.4   Lighting the Heater       6.5   Heater pipe work    2.0 TECHNICAL DATA             p 4    6.6   Adjustments    2.1   Specifications    6.7   Air Distribution System    ...
  • Page 3: Introduction

      WARNINGS     For your safety, if you smell gas :   Do not try to light any appliance   Do not touch any electrical switch, do not use any phone in your building     Evacuate all personnel & contact your gas supplier immediately  WARNINGS    Do not store or use petrol or other flammable vapours and liquids in the vicinity of the  appliance.    Improper  installation,  adjustment,  alteration,  service  or  maintenance  can  cause  property damage, injury or death. Read the installation, operation and maintenance  instructions thoroughly before installing or servicing this equipment.    Do not use this appliance if any part has been immersed in water.  Immediately call a    qualified service technician to inspect the appliance and replace any gas control that    has been immersed in water.    This  appliance  is  not  intended  for  use  by  persons  (including  children)  with  reduced  sensory ...
  • Page 4: Warranty

      When the external control calls for heat, an electronic control begins the ignition sequence to provide for a safe  start. About 30 seconds after the call for heat, the fan will begin circulating warm air. The electronic control will  supervise  the  flame  during  the  entire  heating  cycle  to  ensure  safe  operation.  When  the  required  room  temperature  is  reached,  the  main  burner  will  shut  down  leaving  the  fan  running  to  cool  down  the  heat  exchanger.  After approximately 45 seconds, the fan delay relay will turn off the fan.     1.2 Warranty  Warranty is void if: ...
  • Page 5: Dimensions

    Table 2A:  Injector size and burner pressure G20 natural gas (Inlet pressure = 20.0 mbar )  VRA-4 Quantity Injector size marking 7,25 Burner pressure (mbar) (1) Table 2B:  Injector size and burner pressure G30/G31 butane/propane (Inlet pressures  G30 = 28mbar ‐  G31 = 37mbar)  VRA-4 Quantity 1,15 1,15 1,15 1,15 1,45 1,45 1,95 Injector size marking butane N.A. 28,1 28,1 28,4 28,14 27,9 27,75 26,96 Burner pressure (mbar) (1) propane 35,80 35,80 36,20...
  • Page 6: General Requirements

    GENERAL REQUIREMENTS                     3.1 Related documents    It  is  important  that  all  gas  appliances  are  installed  Air  heaters  should  not  be  installed  in  in  accordance  with  the  rules  in  force  and  by  corrosive atmospheres, i.e. near plating or  appropriately  qualified  persons.  Failure  to  install  degreasing ...
  • Page 7   3.3.1 Flues for power vented installations (Type B appliances)  If  the  air  heater is to be installed as a type B appliance, air for combustion will be taken from within the  space where the heater is installed. Ensure that an adequate air supply for combustion and ventilation is  provided within the building in accordance with the regulations & rules in force.    Table  5  shows  flue  pipe  sizes  and  maximum  Table 5 : Flue pipe diameters & maximum lengths pipe  lengths.  The  minimum  flue  length  is  0.5  20, 30 VRA-4 35->145 metres.  Single  wall  flue  pipes  are  required.  Heater socket & All ...
  • Page 8: Air Supply

      3.4 Air supply    It  is  important  to  ensure  that  there  is  an  adequate  WARNING:  This  model  air  heater  is  air  supply  at  all  times  for  both  combustion  and  installed  as  a  type  B  application  and  is  heating requirements.   designed  to  take  air  for  combustion  from   ...
  • Page 9: Installation

    INSTALLATION                          4.1 Unpacking and preparation    Prior  to  dispatch,  the  air  heater  was  operated  and  tested  at  the  factory.  If  the  heater  has  incurred  any  damage in shipment, file a report claim within 2 working days from receipt.  Check  the  shipping  label  and  data  plate  to  ensure  the  specification  of  gas  and  electrical  supplies  are  compatible. ...
  • Page 10: Gas Connection

      Figure 4   Figure 5       4.4 Gas connection    Do  not  use  the  appliance  gas  supply  to                Figure 6 balance  or  support  any  part  of  the  appliance.        Connection  to  a  gas  network  may  only  be  carried  out  by  appropriately ...
  • Page 11: Air Distribution

    4.6 Room thermostat location    Do  not  attempt  to  control  more  than  1  air  heater  from  a  room  thermostat  or  control  panel  unless  a  properly wired relay is fitted. Follow instructions supplied with such panels.  The  location  of  the  room  thermostat  is  important.  It  should  not  be  fitted  on  an  outside  wall.  Avoid  location in draughty areas or where it may be influenced by heat sources e.g. the sun, process plant, etc. ...
  • Page 12: Suspension And Support

    6.3 Suspension and support    Check  to  ensure  that  the  air  heater  is  adequately  suspended  or  supported  and  that  no  other  parts  have  been fitted that are not independently supported and secured. For safe and correct operation, check the  heater is level in both planes.      6.4 Lighting the air heater    VRA‐4  air  heaters  are  all  fitted  with  automatic  spark  ignition  systems.  When  adequate  airflow  for  combustion ...
  • Page 13: Air Distribution System

        Figure 7 : Honeywell gas valve             1 Gas valve HONEYWELL VR4601AB  2 Inlet pressure gas test point  3 Burner pressure gas test point  4 Burner pressure regulator cover  5 Burner pressure regulator    6 Electrical connection 230V     6.7 Air distribution system    Adjust the air outlet discharge louvers to provide a  If  louver adjustment  is  carried  out  whilst  satisfactory  spread  of  the  warm  air.  Direct  the  air  the  appliance  is  hot  wear  gloves  to  avoid  towards ...
  • Page 14: Servicing Instructions

    SERVICING INSTRUCTIONS                                 IMPORTANT: Only appropriately qualified persons may carry out servicing and fault finding on this gas fired equipment.  Before commencing service ensure that both the gas and the electricity are turned and switched "OFF" and that the air  heater  has  cooled  down.    Inadvertent  substitution  or  replacement  of  components  similar  to  those  specified  or  replacement in a manner contrary to the method herein described could constitute a hazard and lead to prosecution.  VRA‐4  air  heaters  will  operate  with  a  minimum  of  maintenance.  To  ensure  long  life  and  satisfactory  and  safe ...
  • Page 15: Main Burner Removal

    Removal & replacement of parts                       VRA‐4  air  heaters  must  only  be  fitted  with  authorized  replacement  parts.    These  heaters  must  use  certificated spare parts to comply with legislation.    Remember!  After any service work has been carried out, the air heater must be fully commissioned.         See section 6 of this document    Figure 8   (for clarity, heater  8.1 Main burner removal  cabinet & other parts are not  illustrated    Instructions for burner removal (see figure 8):  1.  Turn OFF the gas supply to the air heater.  2.  Switch OFF the electricity supply to the air heater.  3. ...
  • Page 16: Ignition System

      8.3 Ignition system  To access the ignition system, follow steps 1 to 3 in § 8.1.  Due  to  high  voltage  on  the  spark  wire  Ignitor‐  refer  to  figure  9  and  locate  the  ignitor  (on  the  side  of  and  electrode,  do  not  touch  when  the burner rack). Disconnect the wire, remove the screw and the  energized. See hazard levels. ignitor. Clean with an emery cloth.  Note: Spark gap must be maintained to 3.0 mm (see figure 10a). Re‐fit the ignitor as per figure 10b.  Flame  sensor  ‐  Refer  to  figure  9  and  locate  the  flame  sensor.  Disconnect  the  wire,  remove  the  screw  and  the  flame  sensor. Clean with an emery cloth. ...
  • Page 17: Fault Finding

      FAULT FINDING         Fault finding may only be carried out by appropriately qualified persons      9.1  Main fault finding chart ‐ Lock‐out indicator light is "OFF", but air heater will not operate    Is the thermostat above room temperature and if used is the time Set thermostat above room clock"ON" temperature & if used make certain the time clock is ON Is power venting operating? Is there continuity between terminals 9 &10 Reset limit control...
  • Page 18 9.2 Ignition Controller Lockout indicator Light Repeatedly Comes "ON"      Is polarity of mains correct? Correct polarity Does the inlet gas pressure agree with the correct the gas supply data badge pressure Wait 15" and press reset button Check spark gap and ceramic & check During 5" trial for ignition is spark wire &...
  • Page 19 9.3  Limit Control Fault Finding Chart (limit control trips)    Note VRA‐4 air heaters are equipped with 2 limits (a recycling limit and a manual reset limit). During normal operation,  neither limit should trip even if the main electric supply is interrupted during operation. In the event of motor failure, the  recycling limit will trip opening the gas valve.      Adjust thermostat Replace temp. setting above the motor ambient to energize fan & gas solenoid valve Is there 220-240V at terminals N and 4? Does the fan motor operate? Has any non-factory authorized air distribution device been placed on the heater? Is there excessive Consult fan static pressure in the ductwork? Did the motor overload...
  • Page 20: Parts List

    PARTS LISTING                       Settings VRA-4 Part number Delta P switch S3: 12 30 60617 238 238Pa out 250Pa in Delta P switch S3: 20/30 30 60617 175 175Pa out 203Pa in Delta P switch S3: 35/45 30 60621 155 1627Pa out 1767Pa in...
  • Page 21: Users Instructions

    USER INSTRUCTIONS     Operating  How the air heater works Gas is burned by an atmospheric burner which fires into a heat exchanger. The gas burner  is  controlled  by  a  double  gas  valve  via  an  electronic  burner  control,  which  is  actuated  automatically  via  external  controls i.e. a room thermostat and/or a time switch. The burner is ignited by a spark igniter. When the burner fires  and  warms  the  heat  exchanger,  the  heat  is  sensed  by  a  thermally  actuated  fan  control  which  switches  on  the  fan  when ...
  • Page 22: Health & Safety Statement

    HEALTH & SAFETY STATEMENT                          General  Under  the  Consumer  Protection  Act  1987  and  Section  6  of  the  Health  and  Safety  at  Work  Act  1974  we  hereby provide the following information on substances hazardous to health.  Product range reference VRA‐4 air heaters.    Cautionary note  During  first  firing  some  smoking  may  occur,  this  is  due  to  the  burning  off  of  protective/lubricating  oils  used ...
  • Page 23             CERTIFICATE        EC DECLARATION OF CONFORMITY OF MACHINERY   (Annex II 1 A of EC Machinery Directive 2006/42/EC)      The manufacturer  Nortek Global HVAC Belgium nv  J&M Sabbestraat 130/A000  B‐8930 Menen, Belgium       Hereby declares that the following gas‐fired unit heaters:  VRA‐4   Types 12‐4,20‐4, 30‐4, 35‐4, 45‐4, 50‐4, 60‐4, 75‐4, 100‐4, 120‐4, 145‐4    Complies with the requirements of the above mentioned machinery directive    Complies with the requirements of further directives, namely  GAD 2009/142/EC ‐ EMC 2004/108/EC – LVD 2006/95/EC    the following harmonized standards have been applied:  EN  1020:  Non‐domestic  gas‐fired  forced  convection  air  heaters  for  space  heating  not  exceeding  a ...
  • Page 24                                                 NORTEK GLOBAL HVAC (UK) LTD  Fens Pool Avenue  Brierley Hill  West Midlands DY5 1QA  United Kingdom      Tel. 01384 489 250    www.ambirad.co.uk  Registered in England N° 1390934. Registered office: 10 Norwich Street, London, EC4A 18D    Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited. Because of continuous product innovation. Nortek Global HVAC reserves the right to    change product specification without due notice 1610VRA4‐AMEN,p 24/24 ...