Configuration Wizard; Configuration Wizard: Language; Configuration Wizard: Time And Date; Configuration Wizard: System - Daikin ETSH12P30EF Installation Manual

Hide thumbs Also See for ETSH12P30EF:
Table of Contents

Advertisement

7 Configuration
Advanced user
1234
User pin code
The User pin code is 0000.
User
0000
To access the installer settings
1 Set the user permission level to Installer.
2 Go to [9]: Installer settings.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
Most settings can be configured via the menu structure. If for any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:
1 Set the user permission level to Installer. See
change the user permission
2 Go to [9.I]: Installer settings > Overview
field settings.
3 Turn the left dial to select the first part of the setting
and confirm by pressing the dial.
00
05
0A
01
06
0B
0
1
02
07
0C
2
03
08
0D
3
04
09
0E
4 Turn the left dial to select the second part of the
setting
00
05
0A
01 15
06
0B
1
02
07
0C
03
08
0D
04
09
0E
5 Turn the right dial to modify the value from 15 to 20.
00
05
0A
01 20
06
0B
1
02
07
0C
03
08
0D
04
09
0E
6 Press the left dial to confirm the new setting.
7 Press the center button to go back to the home
screen.
INFORMATION
When you change the overview settings and you go back
to the home screen, the user interface will show a popup
screen and request to restart the system.
When confirmed, the system will restart and recent
changes will be applied.
Installation manual
28
"To
level" [ 4  27].
7.2

Configuration wizard

After first power ON of the system, the user interface starts a
configuration wizard. Use this wizard to set the most important initial
settings for the unit to run properly. If required, you can afterwards
configure more settings. You can change all these settings via the
menu structure.
7.2.1

Configuration wizard: Language

#
Code
[7.1]
N/A
Language
7.2.2

Configuration wizard: Time and date

#
Code
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. If you want to change these
settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
7.2.3

Configuration wizard: System

Indoor unit type
The indoor unit type is displayed, but cannot be adjusted.
Backup heater type
#
Code
[9.3.1]
[E‑03]
▪ 0: None
▪ 2: 3V
▪ 3: 6V
▪ 4: 9W
Domestic hot water
The system includes an energy storage tank and can prepare
domestic hot water. This setting is read only.
#
Code
▪ Integrated
[9.2.1]
[E‑05]
[E‑06]
The backup heater will also be used
for domestic hot water heating.
[E‑07]
Emergency
When the heat pump fails to operate, the backup heater or boiler can
serve as an emergency heater. It then takes over the heat load
either automatically or by manual interaction.
▪ When Emergency is set to Automatic and a heat pump failure
occurs, the backup heater or boiler automatically takes over the
domestic hot water production and space heating.
▪ When Emergency is set to Manual and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning main menu screen and confirm whether the
backup heater can take over the heat load or not.
Description
Description
Description
Description
ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663479-1A – 2022.07