Veris PX3 Series Installation Manual

Bluetooth differential pressure/air velocity transducer

Advertisement

Quick Links

Installation Guide
Pressure Monitoring
Bluetooth® Differential Pressure / Air Velocity Transducer
Product Overview
PX3
The PX3 transducer can measure either air pressure or velocity with the flip of a switch.
Patent Pending
The PX3 is available in three installation configurations: duct, panel or universal. Duct and
50
panel models have two pressure and velocity ranges: 0-1 in. WC / 0-3,000 ft/min or
1-10 in. WC / 3,000-6,000 ft/min with four field-selectable sub-ranges. The universal
WARNING
model comes in one pressure/velocity range: 0-10 in. WC / 0-7,000 ft/min with seven
HAZARD OF ELECTRIC
field-selectable sub-ranges for pressure and eight for velocity. All variants are available
SHOCK, EXPLOSION
with and without display. The PX3 has an IP65/NEMA 4 environmental rating and a 5-year
OR ARC FLASH
limited warranty.
• Apply appropriate personal protective
equipment (PPE) and follow safe electrical
work practices. See NFPA 70E or CSA Z462.
The Veris Sensors App provides the ability to connect to a device and configure a variety
• This equipment must only be installed
of field-selectable parameters remotely from a smartphone via Bluetooth technology.
and serviced by quali ed electrical
The app allows users to create and store commonly used parameters that will reduce
personnel.
• Turn o all power supplying this
commissioning time and provide assurance that all parameters are properly configured
equipment before working on or inside
with no call backs. The app can also create a trend log while connected, providing
equipment.
important data for troubleshooting purposes. iOS® users can download the app through
• Always use a properly rated voltage
sensing device to con rm power is o .
the
iOS App Store
• Replace all devices, doors and covers
Google Play™
before turning on power to this
equipment.
Veris Sensors App User's Guide
Failure to follow these instructions can
Veris website.
result in death, serious injury or
equipment damage.
Product Identification
This product is intended for use in HVAC and
building environmental control applications.
It is not intended for direct medical monitoring
Enclosure
of patients.
PX3
Read and understand these instructions before
D = Duct
installing this product.
P = Panel
The installer is responsible for all applicable
codes.
*8-point calibration
If this product is used in a manner not speci ed
by the manufacturer, the protection provided
by the product may be impaired. No
responsibility is assumed by the manufacturer
for any consequences arising out of the use of
this material.
Local Display
PX3U
L = LCD Display
X = No Display
*16-point calibration
Z207504-0O
Page 1 of 8
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Specifications (cont.)
Zero Drift (1-year) 1 in. WC (250 Pa) models: 2.5% FS typ.; 10 in. WC (2,500 Pa) models: 0.25% FS typ.
Zero Adjust Pushbutton auto-zero and digital input (2-pos terminal block)
Operating Environment -20 to 60 °C (-4 to 140 °F)***
Altitude of Operation 0 to 3000 m
Pollution Degree 2
Humidity Range 100% RH, non-condensing
Mounting Location For indoor or outdoor use (display will not function below 0 °C (32 °F))
Fittings Brass barb; 0.24" (6.1 mm) o.d.
Suggested Cable Shielded:
Belden #9939 (22 AWG) 3-wire multi-conductor (or similar)
Belden #9940 (22 AWG) 4-wire multi-conductor (or similar)
Belden #9939 (22 AWG) 5-wire multi-conductor (or similar)
Unshielded:
Belden #8443 (22 AWG) 3-wire multi-conductor (or similar)
Belden #8444 (22 AWG) 4-wire multi-conductor (or similar)
Belden #8445 (22 AWG) 5-wire multi-conductor (or similar)
Bluetooth Frequency
2.402 to 2.480 GHz (Bluetooth version 4.2), enabled by DIP switch, enabled by DIP switch
Range
Maximum Output Power 0 dBm
Limited Warranty 5 years
Environmental Rating IP65, NEMA 4
Flammability Rating UL 94 5VA fire retardant ABS, plenum rated
EMC Conformance: EN 61000-6-3 and A1, Class B, EN 61000-6-1, EN61326-1 and EN61326-2-3.
* Class 2/II power source.
** For measured values between 200 and 7000 ft/min (1 and 35 m/s).
*** Display will not function below 0 °C (32 °F).
Installation, Wiring
1. Plan the installation. Panel or duct mount?
& Configuration
Static Pressure
Panel Installations
Duct Installations
Velocity with VFXP Probe
For velocity applications, use the VFXP Series air velocity/measurement probe or AA18,
AA19 or AA20 velocity pitot tubes. For use with the PX3P (panel) and PX3U (universal)
models in Velocity mode only. Sold separately.
Z207504-0O
Page 3 of 8
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
PX3 Series
on their smart device. Android users can download the app through the
store. For instructions on downloading and operating the app, see the
and
Veris Sensors App Quick Start Guide
Local Display
NIST Certificate*
Range
L = LCD Display
N = NIST
01 = Pressure:
X = No Display
X = None
0 to 1 in. WC /
0 to 250 Pa
Velocity:
0 to 3,000 ft/min /
0 to 15 m/s
02 = Pressure:
1 to 10 in. WC/
250 to 2,500 Pa
Velocity:
3,000 to 6,000 ft/min /
15 to 30 m/s
NIST Certificate*
Range
Wireless Technology
N = NIST*
05 = Pressure:
Blank
X = None
0 to 10 in. WC /
0 to 2500 Pa
Velocity:
0 to 7000 ft/min /
0 to 35 m/s
Differential Pressure
FILTER
Velocity with AA18/AA19/AA20 Pitot Tube
Installation Guide
Pressure Monitoring
Dimensions
in. (mm)
3.5
(88)
Specifications
Media Compatibility Dry air or inert gas
Output Power Field-selectable: 2-wire, loop-powered 4-20 mA
01 Pressure
Range
available on the
02 Pressure
Range
Wireless Technology
Blank
=
Wireless
technology
enabled mode
05 Pressure
Range
Response Time Standard: T95 in 20 sec, Fast: T95 in 2 sec, DIP switch selectable
Display (Option) Pressure mode: Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
Proof Pressure 3 psid (20, 600 Pa)
Burst Pressure 5 psid (34, 500 Pa)
=
Wireless
Pressure Mode Accuracy ±1% FS (combined linearity and hysteresis)
technology
enabled mode
Velocity Mode Accuracy ±90 ft/min (±0.45 m/s) plus 5% of measured value**
Temperature Effect 1 in. WC (250 Pa) models: 0.05%/°C; 10 in. WC (2,500 Pa) models: 0.01%/°C
0423
Z207504-0O
Page 2 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Installation, Wiring
& Configuration
(cont.)
0423
Z207504-0O
Page 4 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
1.6
1.6
(42)
(42)
3.5
(88)
3.1
(78)
4.4
(112)
7.4
(188)
Input Power Three-wire Volt mode: 24 Vac or 12-30 Vdc*
Two-wire mA mode: 12-30 Vdc*
Minimum input voltage for 4 to 20 mA operation: 250 Ω loop = 12 Vdc; 500 Ω loop = 19 Vdc
(DC only, clipped and capped), 24 Vac/dc or 3-wire 0-5V/0-10V
Minimum load resistance for Volt operation: 5 kΩ
Pressure
Unidirectional: 0.1/0.25/0.5/1.0 in. WC, switch selectable
Mode
Bidirectional: ±0.1/±0.25/±0.5/±1.0 in. WC, switch selectable
Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, switch selectable
Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, switch selectable
Velocity
500/1,000/2,000/3,000 ft/min
Mode
2.5/5/10/15 m/s
Pressure
Unidirectional: 1.0/2.5/5/10 in. WC, switch selectable
Mode
Bidirectional: ±1.0/±2.5/±5/±10 in. WC, switch selectable
Unidirectional: 250/500/1,000/2,500 Pa, switch selectable
Bidirectional: ±250/±500/±1,000/±2,500 Pa, switch selectable
Velocity
3,000/4,000/5,000/6,000 ft/min
Mode
15/20/25/30/35 m/s
Pressure
Unidirectional: 0.1/0.25/0.5/1/2.5/5/10 in. WC, switch selectable
Mode
Bidirectional: ±0.1/±0.25/±0.5/±1/±2.5/±5/±10 in. WC, switch selectable
Unidirectional: 25/50/100/250/500/1,000/2,500 Pa, switch selectable
Bidirectional: ±25/±50/±100/±250/±500/±1,000/±2,500 Pa, switch selectable
Velocity
500/1000/2000/3000/4000/5000/6000/7000 ft/min
Mode
2.5/5/10/15/20/25/30/35 m/s
Mode Unidirectional or bidirectional, DIP switch selectable
Velocity mode: Signed 4-1/2 digit LCD, indicates velocity, overrange indicator
(Relative to 25 °C) 0 to 50 °C (32 to 122 °F)
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
2. For duct mount applications, thread the probe into the back of the device housing,
as shown in the dimensional drawing. Configure the internal tubing for the selected
installation method as described below.
3. Duct mount tubing configuration:
a. Connect sensor port A to the rear brass barb marked as "-" on the underside of the
device housing.
b. Connect sensor port B to the probe in the back of the device housing.
Panel mount tubing configuration:
a. Connect sensor port A to the rear brass barb marked as "-" on the underside of the
device housing.
b. Connect sensor port B to the front brass barb marked as "+" on the underside of the
device housing.
Tubing for Duct Mount
Tubing for Duct Mount
3. Mount the transducer (see the screw hole diagram below).
in. (mm)
3.3
(83)
CTR-CTR
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
0.3
(7)
0423
Tubing for Panel Mount
Tubing for Panel Mount
2.3
(59)
CTR-CTR
2.5
(62)
To Pickup
Tube
3.2
(81)
0.5
(13)
1.4
(35)
To Pickup Tube
0423

Advertisement

loading

Summary of Contents for Veris PX3 Series

  • Page 1 0423 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C.
  • Page 2 0423 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C.