Veris PX3 Series Installation Manual page 2

Bluetooth differential pressure/air velocity transducer

Advertisement

Installation Guide
Pressure Monitoring
Installation, Wiring
& Configuration
4.
For applications using conduit, remove the cable gland nut on the bottom of the
unit. Thread a standard 1/2-inch NPT female threaded coupler onto the body of the
(cont.)
cable gland. Connect the opposite end of the coupler to the conduit.
5.
Set DIP switches to desired settings.*
DIP Switch 1: Scale
DIP Switch 2: Mode
DIP Switch 3: Direction**
DIP Switch 4: Response
*DIP switches are all set to OFF by the factory.
**Velocity mode is unidirectional regardless of DIP switch setting.
DIP Switch Settings
Scale
ON Pascal/MPS Velocity
OFF in. WC/FPM Pressure
1
6. Set rotary switch to the desired setting. Align the arrow (not the slot) on the
rotary switch to the desired full-scale range. LCD models momentarily indicate
the selected range.
Z207504-0O
Page 5 of 8
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Installation, Wiring
Rotary Switch Settings (cont.)
& Configuration
Range 05 Model, Field Selectable (P) Pressure or (V) Velocity Mode,
Field Selectable (WC / ft/min or Pa / m/s)
(cont.)
(P) Pressure Mode
0
0 to 0.1 in. WC
1
0 to 0.25 in. WC
2
0 to 0.5 in. WC
3
0 to 1 in. WC
4
0 to 2.5 in. WC
5
0 to 5 in. WC
6
0 to 10 in. WC
7
0 to 10 in. WC
(P) Pressure Mode
0
0 to 25 Pa
1
0 to 50 Pa
2
0 to 100 Pa
3
0 to 250 Pa
4
0 to 500 Pa
5
0 to 1,000 Pa
6
0 to 2,500 Pa
7
0 to 2,500 Pa
8.
Connect the transmitter to the control system and power supply as indicated
below. Optional: Connect the ZERO terminals to the digital output (contact
closure) of the control system.
2-wire, 4-20 mA Current Loop Output
ZERO
1.000
RMT.
ZERO
Digital
Output
DIGITAL CONTROL
Return
V+
Z207504-0O
Page 7 of 8
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
1/2-inch NPT female threaded coupler
DIP Switch 5: Output
ON = Pascal (m/s)
ON = 4-20 mA
OFF = in. WC (ft/min)
OFF = Voltage
DIP Switch 6: Volt Scale
ON = Velocity
ON = 0-5 Vdc
OFF = Pressure
OFF = 0-10 Vdc
DIP Switch 7: Wireless
ON = Unidirectional
ON = Disabled
OFF = Bidirectional
OFF = Enabled
DIP Switch 8: Unused
ON = Slow
OFF = Fast
Mode
Direction Response Output Volt Scale
Uni
Slow
mA
5V
Bi
Fast
Volt
10V
2
3
4
5
6
(V) Velocity Mode
0
0 to 500 ft/min
1
0 to 1,000 ft/min
2
0 to 2,000 ft/min
3
0 to 3,000 ft/min
4
0 to 4,000 ft/min
5
0 to 5,000 ft/min
6
0 to 6,000 ft/min
7
0 to 7,000 ft/min
(V) Velocity Mode
0
0 to 2.5 m/s
1
0 to 5 m/s
2
0 to 10 m/s
3
0 to 15 m/s
4
0 to 20 m/s
5
0 to 25 m/s
6
0 to 30 m/s
7
0 to 35 m/s
3-wire, 0-5 V/0-10 V Voltage Output
ZERO
1.000
Digital
Output
DIGITAL CONTROL
RMT. ZERO
V IN
-
-
POWER SOURCE
24 VAC/DC
+
Installation Guide
Pressure Monitoring
Installation, Wiring
& Configuration
(cont.)
Wireless
Unused
Disabled
Unused
Enabled
Unused
7
8
0423
Z207504-0O
Page 6 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Installation Guide
Pressure Monitoring
Installation, Wiring
& Configuration
(cont.)
Operation
China RoHS Compliance
Information
0423
Z207504-0O
Page 8 of 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C.
in the USA and/or other countries. Other companies' trademarks are hereby acknowledged to belong to their respective owners.
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks is under license.
Rotary Switch Settings
Range 01 Model, Field Selectable (WC / ft/min or Pa / m/s)
(P) Pressure Mode
0
0 to 0.1 in. WC
0
1
0 to 0.25 in. WC
1
2
0 to 0.5 in. WC
2
3
0 to 1 in. WC
3
4
0 to 0.1 in. WC
4
5
0 to 0.25 in. WC
5
6
0 to 0.5 in. WC
6
7
0 to 1 in. WC
7
(P) Pressure Mode
0
0 to 25 Pa
0
1
0 to 50 Pa
1
2
0 to 100 Pa
2
3
0 to 250 Pa
3
4
0 to 25 Pa
4
5
0 to 50 Pa
5
6
0 to 100 Pa
6
7
0 to 250 Pa
7
Range 02 Model, Field Selectable (WC / ft/min or Pa / m/s)
(P) Pressure Mode
0
0 to 1 in. WC
0
1
0 to 2.5 in. WC
1
2
0 to 5 in. WC
2
3
0 to 10 in. WC
3
4
0 to 1 in. WC
4
5
0 to 2.5 in. WC
5
6
0 to 5 in. WC
6
7
0 to 10 in. WC
7
(P) Pressure Mode
0
0 to 250 Pa
0
1
0 to 500 Pa
1
2
0 to 1,000 Pa
2
3
0 to 2,500 Pa
3
4
0 to 250 Pa
4
5
0 to 500 Pa
5
6
0 to 1,000 Pa
6
7
0 to 2,500 Pa
7
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
9. Wait five seconds, then press and hold the ZERO pushbutton for two seconds or
provide contact closure on the AUX ZERO terminal. This will reset the output and
display to zero pressure. For best accuracy, press the ZERO button while both ports
are open to atmospheric pressure. To protect the unit from accidental zero, this
feature is enabled only when the detected pressure is within about 0.5 in. WC
(125 Pa) of factory calibration.
10. Connect desired external tubing to the PX3.
PX3 Series devices employ high performance sensors and sophisticated temperature
compensation circuitry. The sensor achieves its best accuracy after an initial warm-up
period. During the first few minutes of operation, readings at zero pressure and the
lowest pressure ranges may appear erroneous. Following this initial warm-up period, the
PX3 device maintains its specified accuracy and stability.
The LCD momentarily indicates range 'SET' when a selection is made. Pressure is normally
indicated on the display. Units are in inches water column (in. WC), Pascals (Pa) or
kilopascals (kPa) as indicated on the display. The display shows 'OVR' when the pressure
is over range.
Environment-Friendly Use Period (EFUP) Table
部件名称
有害物质 -
Part Name
(Pb)
(Hg)
(Cd)
电子件
X
O
O
Electronic
本表格依据SJ/T11364的规定编制。
O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
X: 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572规定的限量要求。
(企业可在此处,根据实际情况对上表中打
This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the homogeneous materials
for this part is below the limit as stipulated in GB/T 26572.
X: indicates that concentration of hazardous substance in at least one of the homogeneous
materials used for this part is above the limit as stipulated in GB/T 26572
Z000057-0B
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's
authority to operate the equipment.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation of the device.
Cet appareil est conforme aux normes d' e xemption de licence RSS d'Industry Canada. Son fonctionnement
est soumis aux deux conditions suivantes : (1) cet appareil ne doit pas causer d'interférence et (2) cet appareil
doit accepter toute interférence, notamment les interférences qui peuvent affecter son fonctionnement.
©2023 Veris Industries 12345 SW Leveton Drive, Tualatin, OR 97062 USA / 800.354.8556 or +1.503.598.4564 / support@veris.com
(V) Velocity Mode
0 to 500 ft/min
0 to 1,000 ft/min
0 to 2,000 ft/min
0 to 3,000 ft/min
0 to 500 ft/min
0 to 1,000 ft/min
0 to 2,000 ft/min
0 to 3,000 ft/min
(V) Velocity Mode
0 to 2.5 m/s
0 to 5 m/s
0 to 10 m/s
0 to 15 m/s
0 to 2.5 m/s
0 to 5 m/s
0 to 10 m/s
0 to 15 m/s
(V) Velocity Mode
0 to 3,000 ft/min
0 to 4,000 ft/min
0 to 5,000 ft/min
0 to 6,000 ft/min
0 to 3,000 ft/min
0 to 4,000 ft/min
0 to 5,000 ft/min
0 to 6,000 ft/min
(V) Velocity Mode
0 to 15 m/s
0 to 20 m/s
0 to 25 m/s
0 to 30 m/s
0 to 15 m/s
0 to 20 m/s
0 to 25 m/s
0 to 30 m/s
0423