13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of "Unit Status" (...continuation)
Screen Parameter
P04
NUM_WO_DIG_3
P04
NUM_WO_DIG_4
P04
NUM_WO_DIG_5
P04
NUM_WO_DIG_6
P04
NUM_WO_DIG_7
P04
NUM_WO_DIG_8
Parameters of "Unit On/Off "
Screen Parameter
Description of the parameter
PM01
SYS_ON
Selection of the unit ON/OFF by keyboard or remote: 0: Switch-off (Off ) # 1: Switch-on (On)
PM01z SYS_ON_T11 Selection of the zone 1 ON/OFF by keyboard or remote: 0: Switch-off (Off ) # 1: Switch-on (On)
PM01z SYS_ON_T12 Selection of the zone 2 ON/OFF by keyboard or remote: 0: Switch-off (Off ) # 1: Switch-on (On)
PM01z SYS_ON_T13 Selection of the zone 3 ON/OFF by keyboard or remote: 0: Switch-off (Off ) # 1: Switch-on (On)
PM01z SYS_ON_T14 Selection of the zone 4 ON/OFF by keyboard or remote: 0: Switch-off (Off ) # 1: Switch-on (On)
Parameters of "Setpoint"
Screen Parameter
S01zn SET_POINT_TEMP_FRIO_T11
S01zn SET_POINT_TEMP_CALOR_T11
S02zn SET_POINT_TEMP_FRIO_T12
S02zn SET_POINT_TEMP_CALOR_T12
S03zn SET_POINT_TEMP_FRIO_T13
S03zn SET_POINT_TEMP_CALOR_T13
S04zn SET_POINT_TEMP_FRIO_T14
S04zn SET_POINT_TEMP_CALOR_T14
S01
SET_POINT_TEMP_FRIO
S01
SET_POINT_TEMP_CALOR
S02
SET_POINT_HUM
HAB_SONDA_HUM_INT_
S02
VIRTUAL
S03
SET_COMPRESOR_EN_FRIO
S03
SET_COMPRESOR_EN_CALOR Calculation of setpoints: Setpoint In HEATING mode (winter) + Dead Zone / 2 0.0
S03
SET_TEMP_COMPRESOR
S03
SET_RES_EN_FRIO
S03
SET_RES_EN_CALOR
S03
SET_TEMP_RES
S03
SET_VLV_CALOR_EN_FRIO
S03
SET_VLV_CALOR_EN_CALOR
S03
SET_VLV_CALOR
S03
SET_FCOOL_VER
S03
SET_FCOOL_INV
S03
SET_FHEAT
S04
SET_IMPULSION_FRIO_CAL
S04
SET_IMPULSION_CALOR_CAL
32
Description of the parameter
Work order number of the unit (digit 3)
Work order number of the unit (digit 4)
Work order number of the unit (digit 5)
Work order number of the unit (digit 6)
Work order number of the unit (digit 7)
Work order number of the unit (digit 8)
Description of the parameter
Temperature setpoint in COOLING mode (summer) in the terminal of zone
1 (zoning of the air fl ow)
Temperature setpoint in HEATING mode (winter) in the terminal of zone 1
(zoning of the air fl ow)
Temperature setpoint in COOLING mode (summer) in the terminal of zone
2 (zoning of the air fl ow)
Temperature setpoint in HEATING mode (winter) in the terminal of zone 2
(zoning of the air fl ow)
Temperature setpoint in COOLING mode (summer) in the terminal of zone
3 (zoning of the air fl ow)
Temperature setpoint in HEATING mode (winter) in the terminal of zone 3
(zoning of the air fl ow)
Temperature setpoint in COOLING mode (summer) in the terminal of zone
4 (zoning of the air fl ow)
Temperature setpoint in HEATING mode (winter) in the terminal of zone 4
(zoning of the air fl ow)
Temperature setpoint in COOLING mode (summer)
Temperature setpoint in HEATING mode (winter)
Indoor humidity setpoint
Enabling the indoor humidity probe in the SHRD shared network
Calculation of setpoints: Setpoint in COOLING mode (summer) + Dead
Zone / 2
Current selection of the setpoint
Calculation of setpoints: Setpoint of the electrical heaters in COOLING mode 0.0
Calculation of setpoints: Setpoint of the electrical heaters in HEATING mode 0.0
Current selection of setpoint for electrical heaters
Calculation of setpoints: Setpoint of the hot water coil in COOLING mode 0.0
Calculation of setpoints: Setpoint of the hot water coil in HEATING mode
Current selection of setpoint for the hot water coil
Calculation of setpoints: free-cooling in summer
Calculation of setpoints: free-cooling in winter
Calculation of setpoints: free-heating
Supply setpoint calculated in COOLING mode
Supply setpoint calculated in HEATING mode
F
MODES
A
GENUIT
C
SETPOINT
Value Min.
Max. UOM Type
0
0
9
---
Analog. R
0
0
9
---
Analog. R
0
0
9
---
Analog. R
Analog. R
0
0
9
---
Analog. R
0
0
9
---
Analog. R
0
0
9
---
Value Min. Max. UOM Type R/W
0
0
1
---
Digital R/W 65
0
0
1
---
Digital
0
0
1
---
Digital
0
0
1
---
Digital
0
0
1
---
Digital
Value Min. Max. UOM Type
26.0
0.0
50.0 °C
Analog. R/W 283
21.0
0.0
50.0 °C
Analog. R/W 284
26.0
0.0
50.0 °C
Analog. R/W 285
21.0
0.0
50.0 °C
Analog. R/W 286
26.0
0.0
50.0 °C
Analog. R/W 287
21.0
0.0
50.0 °C
Analog. R/W 288
26.0
0.0
50.0 °C
Analog. R/W 289
21.0
0.0
50.0 °C
Analog. R/W 290
26.0
0.0
50.0 °C
Analog. R/W 15
21.0
0.0
50.0 °C
Analog. R/W 16
50.0
0.0
100.0 %rH Analog. R/W 18
1:
0
0: no
---
Digital R
yes
0.0
0.0
99.9 °C
Analog. R
0.0
99.9 °C
Analog. R
0.0
0.0
99.9 °C
Analog. R
0.0
99.9 °C
Analog. R
0.0
99.9 °C
Analog. R
0.0
0.0
99.9 °C
Analog. R
0.0
99.9 °C
Analog. R/W
0.0
0.0
99.9 °C
Analog. R/W
0.0
0.0
99.9 °C
Analog. R/W
00.0
-99.9 99.9 ---
Integer R
00.0
-99.9 99.9 ---
Integer R
00.0
-99.9 99.9 ---
Integer R
7.0
0.0
30.0 °C
Analog. R
45.0
0.0
55.0 °C
Analog. R
Add.
R/W
BMS
187
188
189
190
191
192
Add.
BMS
R/W
364
R/W
365
R/W
366
R/W
367
Add.
R/W
BMS
122
121