TKB Series — Battery Powered
In-Line Paddle Wheel Flow Meter
Programming
Press
and hold for 3 seconds, then press
STEPS
Home Screen
1
+
F
Set Pasword — Enter #
2
Changing K Factor — K= #
3
Display Mode — dSP.non
4
Light On — t-5
5
Flow Alarm Delay — dt-10
5
Reset Totalizer — rESEt.0
5
23-0107
© Icon Process Controls Ltd.
Select/Save/Continue
or
to select
DISPLAY
��
5 Sec .
Move selection left
F
Flow Rate Units
GPM
LPM
CMH
Home Screen
r = Flow Rate | Default Setting
Factory Default: Lock = 8
Enter ANY Number from 0 - 9 to Set
Flow Coefficient = Input pulses x 1/k *
Only required if changing displays from one size to another
i.e. 1" to 2" pipe size
1. dSP-non | Press any key to turn on the LED back light | Default
is set to 6 seconds
2. dSP-Eco | Backlight LED function is not active
In dSP-non mode Backlight default is t-0006 | Set Duration Time
(sec) of Backlight to remain On.
Press any key to turn on the display to turn on LED light
(> Time = < Reduced Battery Life)
Delay Time ensures Alarm Setting only becomes active after the
flow remains constant for xx seconds
Programming the High | Low Alarm
Press
+
3 Sec to Display High Alarm Setting
Press
or
to Enter Alarm Value.
Press
to Display Low Alarm Setting.
Press
or
to Enter Alarm Value. The Press
1. To Prevent Totalizer reset - Enter Password Number 0-9
(excluding # 5 ) Flow Totalizer Reset Protection Active
2. rESEt.= 5 Default = Flow Totalizer Reset Enabled
Change digit value
STR
Flow Total | Totalizer Units
GPM
LPM
OPERATION
to Confirm
CMH
6