Configuration

9.2 Configuration wizard

Installer reference guide
122
6 Press the left dial to confirm the new setting.
7 Press the center button to go back to the home screen.
INFORMATION
When you change the overview settings and you go back to the home screen, the
user interface will show a popup screen and request to restart the system.
When confirmed, the system will restart and recent changes will be applied.
After first power ON of the system, the user interface will guide you using the
configuration wizard. This way you can set the most important initial settings. This
way the unit will be able to run properly. Afterwards, more detailed settings can be
done via the menu structure if required.
You can find a short overview of the settings in the configuration here. All the
settings can also be adjusted in the settings menu (use the breadcrumbs).
For the setting...
Language [7.1]
Time/date [7.2]
Hours
Minutes
Year
Month
Day
System
Indoor unit type (read only)
Backup heater type [9.3.1]
Domestic hot water [9.2.1]
Emergency [9.5]
Number of zones [4.4]
Glycol Filled system (overview
field setting [E‑0D])
Booster heater capacity [9.4.1]
(if applicable)
Backup heater
Voltage [9.3.2]
Configuration [9.3.3]
Capacity step 1 [9.3.4]
Additional capacity step 2
[9.3.5] (if applicable)
Main zone
Refer to...
"9.5.9 Installer
settings" [
"9.5.5 Space heating/
cooling" [
4
 158]
"9.5.9 Installer
settings" [
4
"Backup
heater" [
 181]
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
4
 178]
4
 178]