Mitsubishi Electric MCFH-GA35VB-E1 Service Manual

Floor and ceiling type air conditioners, wireless type

Advertisement

Quick Links

FLOOR AND CEILING TYPE AIR CONDITIONERS
SERVICE MANUAL
Wireless type
Models
MCFH-GA35VB-
MCFH-GA50VB-
MCFH-GA60VB-
NOTE:
• This manual describes technical data of indoor units
• As for outdoor units MUCFH-GA35VB/GA50VB/GA60VB-
• As for outdoor units MXZ-A14/A18/A26/A32WV-
EDITION-A.
(WH)
E1
(WH)
E1
(WH)
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. SPECIFICATION·················································4
Indication of
4. NOISE CRITERIA CURVES ·······························5
model name
5. OUTLINES AND DIMENSIONS ·························6
MCFH-GA35VB-
E1
E1
6. WIRING DIAGRAM ············································7
E1
7. REFRIGERANT SYSTEM DIAGRAM ················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING······································11
10. DISASSEMBLY INSTRUCTIONS·····················19
11. PARTS LIST······················································21
12. OPTIONAL PARTS···········································23
, refer to the service manual OB381.
E1
, refer to the service manual OB319 REVISED
E1
No. OB380

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric MCFH-GA35VB-E1

  • Page 1: Table Of Contents

    FLOOR AND CEILING TYPE AIR CONDITIONERS No. OB380 SERVICE MANUAL Wireless type Models MCFH-GA35VB- (WH) MCFH-GA50VB- (WH) MCFH-GA60VB- (WH) CONTENTS (When installed on the floor) 1. TECHNICAL CHANGES ····································2 2. PART NAMES AND FUNCTIONS······················2 3. SPECIFICATION·················································4 Indication of 4. NOISE CRITERIA CURVES ·······························5 model name 5.
  • Page 2: (When Installed On The Floor)

    TECHNICAL CHANGES MCFH-A12WV- MCFH-GA35VB- 1. Model name has been changed. MCFH-A18WV- MCFH-GA50VB- 1. Model name has been changed. MCFH-A24WV- MCFH-GA60VB- 1. Model name has been changed. PART NAMES AND FUNCTIONS MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - INDOOR UNIT ACCESSORIES (When installed on the floor) Item Q'ty Installation plate...
  • Page 3 MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - REMOTE CONTROLLER Signal transmitting section Operation display section OPERATE /STOP (ON /OFF)button ON/OFF WARM COOL TEMPERATURE buttons Open the front lid. Indication of remote controller model is on back. CLOCK ON/OFF WARM COOL FAN SPEED CONTROL button VANE CONTROL button STOP OFF-TIMER button...
  • Page 4: Specification

    SPECIFICATION MCFH-GA35VB- MCFH-GA50VB- MCFH-GA60VB- Indoor model Cooling Heating Cooling Heating Cooling Heating Function Single phase Power supply 230V, 50Hz Capacity Air flow(High/Med.W/LowW) 780/636W/492W 840/696W/570W 840/744W/642W K /h Power outlet Running current 0.30 0.36 0.36 Power input Auxiliary heater — — —...
  • Page 5: Noise Criteria Curves

    NOISE CRITERIA CURVES MCFH-GA35VB - MCFH-GA50VB - SPL(dB LINE SPL(dB LINE FAN SPEED FUNCTION FAN SPEED FUNCTION COOLING COOLING High High HEATING HEATING Test conditions, Test conditions, Cooling : DB 27: WB 19:\ Cooling : DB 27: WB 19:\ Heating : DB 20: WB 15: Heating : DB 20: WB 15: NC-70 NC-70...
  • Page 6: Outlines And Dimensions

    OUTLINES AND DIMENSIONS MCFH-GA35VB - Unit: mm MCFH-GA50VB - MCFH-GA60VB - INDOOR UNIT 80.8 112.8 (When installed on the floor) 50cm or more 50cm or more (When installed on the ceiling) 50cm or more 1100 Gas line 12.7 (MCFH-GA35/GA50VB) Liquid line 15.88 (MCFH-GA60VB) 6.35 Wireless remote controller...
  • Page 7: Wiring Diagram

    WIRING DIAGRAM MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - INDOOR UNIT MODELS WIRING DIAGRAM GRN/YLW POWER SUPPLY RT12 ~/N 230V HIC1 50Hz LDCOM CN201 TAB12 LDC11 CIRCUIT BREAKER LDC12 LDFH X144 LDFM SR143 TO OUTDOOR LDFL SR142 UNIT LDFVL CN CN SR141 CONNECTING ELECTRONIC CONTROL P.C BOARD...
  • Page 8: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM Unit : mm MCFH-GA35VB- MCFH-GA50VB- INDOOR UNIT INDOOR UNIT Refrigerant pipe [12.7 Refrigerant pipe [12.7 (with heat insulator) (with heat insulator) Indoor Indoor heat heat Distributor Distributor Flared connection exchanger Flared connection exchanger Indoor coil Indoor coil thermistor thermistor RT12...
  • Page 9: Service Functions

    SERVICE FUNCTIONS MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - 8-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-6.) 3-minutes time delay : 3-minutes 3-seconds Set time : 1 minute...
  • Page 10 8-3. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.Then, the unit will restart automatically.
  • Page 11: Troubleshooting

    TROUBLESHOOTING MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - 9-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: (1) Check the power supply voltage. (2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during service. (1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after confirming the horizontal vane has completely closed, turn off the breaker.
  • Page 12 9-2. Instruction of troubleshooting Start Indoor unit Indoor unit Indoor unit operates. OPERATION INDICATOR operates. doesn't receive Outdoor unit lamp on the indoor unit is Outdoor unit the signal from doesn't operate flashing on and off. doesn't remote controller. normally. operate.
  • Page 13 9-3. Troubleshooting check table OPERATION INDICATOR lamp Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table Abnormal Indication Symptom Detect method Check point point 0.5-second ON Check wiring (visual check and conductiv- Mis-wiring ity check). or Serial Outdoor unit When serial signal stops for 4...
  • Page 14 9-4. Trouble criterion of main parts MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - Part name Check method and criterion Figure Room Measure the resistance with a tester. temperature (Part temperature 10°C ~ 30°C) thermistor (RT11) Normal Abnormal Indoor coil 8kΩ ~ 20kΩ Open or short-circuit thermistor (RT12) Measure the resistance between the terminals with a tester.
  • Page 15 9-5. Troubleshooting flow Indoor fan does not operate. Check of indoor fan motor Turn OFF power supply. Check connector (Fan motor) visually. Is soldered point of the connector Are lead wires connected? correctly soldered? Reconnect the lead wires. Resolder it. Disconnect lead wires from connector (Indoor fan motor).
  • Page 16 The unit does not operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch. Check of indoor electronic control P.C. board Replace the fuse. Is fuse(F11)blown? Check both “parts side”and “pattern Trouble of the indoor electronic side”...
  • Page 17 When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit does not operate. How to check mis-wiring and serial signal error (when outdoor unit does not work) Start Is this mis-wiring, poor contact, Make them sure. or disconnection of wire? 1.
  • Page 18 9-6. Test point diagram and voltage MCFH-GA35VB - MCFH-GA50VB - MCFH-GA60VB - Indoor electronic control P.C. board Fan motor power supply 230V AC Very Med. High Fuse (F11) 250V AC 3.15A Varistor (NR11) Power supply input 230V AC R132 about 20V DC (Refer to 9-5.E.) 5V DC –...
  • Page 19: Disassembly Instructions

    DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
  • Page 20 OPERATING PROCEDURE PHOTOS Photo 4 2. Removing the indoor fan motor (1) Remove the grille. (Refer to 1(1) (2).) (2) Remove the fan casing.(upper) Motor band Fan casing (3) Disconnect the connector of the indoor fan motor. (upper) (4) Disconnect the ground wire of the fan motor. (5) Remove the screws of the motor band and remove the catch.
  • Page 21: Parts List

    PARTS LIST MCFH-GA35VB - (WH) MCFH-GA50VB - (WH) MCFH-GA60VB - (WH) 11-1. INDOOR UNIT STRUCTURAL PARTS Part number that is circled is not shown in the illustration. Q'ty/unit Symbol MCFH-GA35VB MCFH-GA50VB MCFH-GA60VB in Wiring Part No. Part name Remarks Diagram (WH) (WH) (WH)
  • Page 22 MCFH-GA35VB - (WH) MCFH-GA50VB - (WH) MCFH-GA60VB - (WH) 11-2. INDOOR UNIT 11-3. ACCESSORY AND ELECTRICAL PARTS REMOTE CONTROLLER 11-2. INDOOR UNIT ELECTRICAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol MCFH-GA35VB MCFH-GA50VB MCFH-GA60VB in Wiring Part No.
  • Page 23: Optional Parts

    OPTIONAL PARTS 12-1. AIR CLEANING FILTER If the air cleaning filter is clogged, it may lower the unit’s capacity or cause condensation at the air outlet . The air cleaning filter is disposable . The standard usable term is about 4 months . However , if the color of the filter turns to dark brown , replace soon .
  • Page 24 HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN C C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Jan. 2005 Specifications subject to change without notice. Distributed in Jan. 2005. No.OB380 6 Made in Japan...