6.5 International color code table ................... 24 7. Local menu system structure .................... 25 7.1 WTT-3000 (WISE) ......................25 7.1.1 How to change menu settings value ................25 7.1.2 Menu settings structure ....................26 7.1.3 Menu settings value table ....................27 8.
1. General items 1.1 Introduction The SMT3000 is a product to measure the temperature of liquids, gases or vapors and it is specially designed for use throughout industrial processes. The HART® communication is possible for this product and parameters can be set using a PC or HART® communicator. Substances of which the temperature can be measured are gases or liquids suitable for the sensing unit materials of the product.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 2. Warning Guide on handling for safe use For the safe and correct use of the product, make sure to read the handling guide carefully before use. Handling errors can cause device malfunctions, and it can lead to injury, accidents, etc.. Warining For the safety, only a worker with professional skills in electronics and electrical construction is allowed to install the product.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 3. Main specs 3.1 Explosion-proof Model: SMT3000 Explosion-proofing grade: Ex db IIC T6 Explosion-proofing technology: IEC 60079-0, IEC 60079-1 3.2 Protection grade IP66 / IP67 3.3 Temperature sensor types Thermocouple (TC): K, E, J, T, N, B, R, S type ...
Page 7
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com Thermocouple (TC): Class 1,2,3(IEC/EN 60584-2) or Standard / Special(ASTM E230, ANSI MC 96.1) Type Class Temperature range Maximum deviation -200 ~ 0 ℃ The greater of ±2.2 ℃ or ±2% Standard 0 ~ 1260 ℃ The greater of ±2.2 ℃...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4. Design 4.1 Structure 4.1.1 Basic type Products generally come in two types: explosion proof and general. Explosion proof products are resistance against pressure and explosion. The enclosure is designed to withstand the pressure of explosive gases or vapors exploding inside, and to prevent combustion due to explosive gases or vapors outside the enclosure through joints and lead-ins.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.2 Head General / Explosion proof Warning: Certified explosion proof cable glands must be used when installing in hazardous areas. See the <Table: Head information> below for the types of cables that may be connected. Table : Head information Head thread Conduit adaptor...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.3 Detector unit and process connection unit material Metal Usage max. temperature temperature Material characteristics (℃) (℃) Less carbon content than 316. 316L SS 1050 Better acid and alkaline resistance than 316SS. Weak sulfur and reducing heat resistance. Outstanding 321SS 1000 corrosion and heat resistance.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.4 Process connection unit 4.4.1 Sheathed cable (MI cable) type Nipple Union & Nipple Fixed flange lag C-QIM-2731-T31_EN_Rev.1...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.4.2 Remote type None Compression fitting Fixed thread *Note. Please inquire with the manufacturer if you need a different process connection unit. C-QIM-2731-T31_EN_Rev.1...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.5 Relationship between process connection unit length and head temperature increase T: Operating temperature Process Extension length: Distance between thermowell or process line to head / Lead wire connection length): Length of extension cable or extension & compensating wire * The process connection unit length of units installed in explosion proof areas must be sufficient to keep the temperature increase at less than 20°C.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.6 Transmitter failure (NAMUR NE43) NAMUR NE43 means failure indication when signals of 3.6 mA or less or 21 mA or more which are not within the normal instrument output range of 4-20 mA are detected. The 3.8~20.5mA signal section is used as the normal measurement signal, and the signal ≥21mA or ≤3.6mA can be checked with failure alarm.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.7 HART® Communication A process configured with product and the HART® communication device can be used. We recommend the use of a communicator officially licensed by HART® for the configuration of the communication process. Electrical Connection Diagram (Using the HART® Protocol) 2-Wire(Current) HART®...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5. Installation guide 5.1 Pre-installation checks and precautions 1) If there is a risk of lightning strike or damage can be caused by overvoltage, use stronger lightning protection device. 2) Be careful to prevent dust from excessively accumulating on the product (more than 5 mm) or completely covering the product.
Page 17
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 8) Check whether the fluid in the pipe and materials of the O-ring, sensor, and thermowell supplied are suitable for use. 9) The explosion-proof rating of the cable entry device should be equivalent to or higher than that the product (Ex d IIC).
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.2 Installation requirement After removing the lock screw, open the back cover by turning it by hand. After fastening the certified cable entry device, check the terminal configuration diagram. (6.4 See the terminal configuration diagram) Complete the electrical wiring of the sensor and power by referring to the terminal configuration diagram.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.3 Changing orientation of display 5.3.1 WTT-3000 After removing the lock screw, open the front cover by turning it by hand. Rotate the display to the desired orientation. (The display can rotate up to 270 degrees.) Before closing the front cover again, check the O-rings and threads of the cover and replace the O-rings if necessary.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.4 Power connection requirement *Note. When using a device with connector terminals, observe the separation distance standard and connect correctly to avoid disconnection of the connecting wires. Connect the product according to the electrical specifications provided in the connection table and wiring diagram as following.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6. Wiring 6.1 Extension & compensation wire This type of cable used for temperature measurement. A wire of the same material (extension) as the thermocouple (TC) or a material having thermoelectric power characteristics as the thermocouple (TC) is extended to the terminal of the instrument.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com If there are outdoor wiring sections, do not use glass sheathing. Humidity may reduce insulation resistance and cause measuring errors. Cables shall be protected from damage such as breakage or cutting by the surrounding environment. Exercise caution to prevent folding or knitting of cable.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6.3 Earthing 6.4 As shown in the terminal configuration diagram, the product can be grounded internally and externally. The recommended grounding wire is AWG 24 or more, and when using an extension cable, a size thicker than the standard grounding wire should be used. When working with terminals, washers are used to prevent loosening, plated terminals and lugs should be used to prevent corrosion, and the grounding point should be connected to building rebar, floor ground or bus bar.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6.5 International color code table See the table below when connecting the product. (Different colors may be used according to customer requirements.) Thermocouple (TC) EN (IEC 60584-3) ANSI(ISA MC96.1) JIS C 1610 (KS C 1609) Type Brown White...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 7. Local menu system structure 7.1 WTT-3000 (WISE) "Z" button: moves the cursor to another location. "M" button: Changes the next menu, or saves the changed settings value. "S" button: Change the displayed value. "S"+"Z" button: Press both buttons for about 2~5 seconds to enter to Menu 2.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 7.1.3 Menu settings value table Menu 1. Change the way 2. PV(°C, °F)(St’d) 1. Current(mA) 3. PV(%) LCD screens are represented 1. °C (St’d) Menu 2. Unit change 2. °F 3. °R 4. K 5. mV 6.
Name plate 경고. 폭발성가스분위기가 존재할 우려가 있는 경우 열지 마십시오! 2022 Deogyeong-daero,Giheung-gu, Yongin-si,Gyeonggi-do,Korea WISE CONTROL INC. KCs Ex db Certified explosion proof products have passed confirmation testing, and have the same specs as submitted to the certification lab.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 9. Repair and maintenance Only skilled personnel may carry out maintenance and repair activities when necessary, and Wise Co., Ltd. may provide support for maintenance and repair. Repairs Repairs may be carried out only by Wise Co., Ltd. or a component manufacturer.
Incorrect installation can eventually lead to an inaccurate reading of temperature. Wise Co., Ltd. can support users’ selection but will not be responsible for them in any sort of way. 12. Product return If the product gets returned for recalibration or repair work, make sure to use the original packaging or safe packaging method, and also make sure to return the related documents.
Page 32
The product spec or exterior can be changed without a pre-notice for the quality improvement purposes, thus Wise Co., Ltd. has the rights to change them. Figures used in the user manual are for just illustration purposes, and they can differ from the actual shapes.
Page 33
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com SMART TEMPERATURE TRANSMITTER SMT3000 C-QIM-2731-T31_KR_Rev.2...
Page 34
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 목차 1. 일반사항 ........................3 1.1 소개 ............................ 3 1.2 적용 ............................ 3 1.3 보증 ............................ 3 2. 경고 ........................... 4 3. 주요사양 ........................5 3.1 방폭 ............................ 5 3.2 보호 등급 ..........................5 3.3 온도 센서 타입 ........................5 3.4 정확도...
Page 35
6.4 터미널 배선 ........................21 6.5 국제 색상 비교표 ......................22 7. 로컬 메뉴 시스템 구조....................23 7.1 WTT-3000 (WISE) ......................23 7.1.1 메뉴 설정 값 변경 방법....................23 7.1.2 메뉴 설정 구조 ......................24 7.1.3 메뉴 설정 값 테이블 ...................... 25 8.
1. 일반사항 1.1 소개 SMT3000은 산업 공정의 전반에 사용하기 위해 특별히 설계되었으며, 액체, 가스 또는 증기 등의 온도 를 측정하는데 사용하는 제품입니다. 이 제품은 HART® 통신이 가능하며, PC나 HART® 커뮤니케이터 를 이용하여 파라미터 등의 설정이 가능합니다. 온도 측정이 가능한 물질은 제품 감지부의 재질에 적합...
Page 37
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 2. 경고 안전한 사용을 위한 취급설명서 이 제품을 바르고 안전하게 사용하기 위하여 사용 전에 이 취급설명서를 잘 읽어주시기 바랍니다. 취급시의 오류는 기기고장의 원인이 되며, 상해나 사고 등의 재해가 발생할 수 있습니다. 경 고 1) 안전을 위해 설치는 계장, 전기공사 등의 전문기술을 보유한 작업자가 실시하여야 합니다. 2) 사양서에...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 3. 주요사양 3.1 방폭 모델명: SMT3000 방폭 등급: Ex db IIC T6 방폭 기술 기준: IEC 60079-0, IEC 60079-1 3.2 보호 등급 IP66 / IP67 3.3 온도 센서 타입 열전대(TC): K, E, J, T, N, B, R, S type ...
Page 39
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 1) 열전대(TC): Class 1,2,3(IEC/EN 60584-2) or Standard / Special(ASTM E230, ANSI MC 96.1) Type Class Temperature range Maximum deviation -200 ~ 0 ℃ The greater of ±2.2 ℃ or ±2% Standard 0 ~ 1260 ℃ The greater of ±2.2 ℃...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4. 설계 4.1 구조 4.1.1 기본 타입 본 제품에는 일반적으로 비방폭 구조와 방폭 구조 두 가지 유형이 있습니다. 방폭 구조는 내압 방폭으 로 용기 내부에서 폭발성가스 또는 증기가 폭발하였을 때 용기가 그 압력에 견디도록 설계되어 있으며 접합면, 인입부...
Page 41
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.2 헤드 General / Explosion proof Warning: 방폭 지역에 설치하는 제품의 케이블 그랜드는 방폭 인증된 제품을 사용해야 합니다. 연결 가능한 케이블은 아래 <Table: Head information >을 확인합니다. Table : Head information Head thread Conduit adaptor Head Head material Conduit adaptor...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.4 프로세스 연결부 4.4.1 시스 케이블(MI cable) 타입 Nipple Union & Nipple Fixed flange lag C-QIM-2731-T31_KR_Rev.2...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.4.2 리모트 타입 None Compression fitting Fixed thread *Note. 이외에 프로세스 연결부를 적용해야 할 경우 당사에 문의 바랍니다. C-QIM-2731-T31_KR_Rev.2...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.5 프로세스 연결부 길이와 헤드부 상승 온도 관계 1) T: 사용온도 (Operating temperature) 2) 프로세스 연결부 길이 (Extension length): 써모웰 또는 프로세스 라인과 헤드까지 거리 / 리드와이어 연결부 길이 (Lead wrie length): 연장 케이블 또는 보상 도선 길이 * 방폭...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.6 트랜스미터 오류 신호 (NAMUR NE43) NAMUR NE43이란 정상적인 계기 출력 범위인 4~20mA 보다 낮은 구간 3.6mA 이하 또는 21mA 이상 신호 감지 시 장애 표시를 뜻하며 신호를 통해 장애 경보를 확인할 수 있고, 3.8~20.5mA 신호 구간은...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 4.7 HART® 통신 HART® 통신장비를 사용하여 프로세스를 구성하고 제품을 사용할 수 있습니다. 당사는 통신 프로세스 의 구성을 위해 HART® 의 정식 라이선스가 있는 커뮤니케이터의 사용을 추천합니다. 1) Electrical Connection Diagram (Using the HART® Protocol) 2) 2-Wire(Current) HART® system ...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5. 설치 지침 5.1 제품 설치 전 확인 및 주의 사항 1) 번개가 칠 위험이 있거나, 과전압으로 인해 손상이 있을 수 있는 경우에는 더 강한 낙뢰 보호장치 를 사용하십시오. 2) 과도한 먼지 축적 (5mm 이상) 또는 먼지로 완전히 덮이지 않게 주의하십시오. 3) 본...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.2 설치 요구사항 1) Lock Screw 제거 후 후면 커버(Back cover)를 손으로 돌려 열어줍니다. 2) 인증 받은 케이블 인입 장치 체결 후 터미널 구성도를 확인합니다. (6.4 터미널 구성도 참조) 3) 터미널 구성도를 참조하여 센서와 전원의 전기 배선을 완료합니다. 4) 후면...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.3 디스플레이 방향 변경 5.3.1 WTT-3000 1) Lock Screw 제거 후 전면 커버(Front Cover)를 손으로 돌려 열어줍니다. 2) 디스플레이를 원하는 방향으로 회전하십시오. (디스플레이는 최대 270˚까지 회전 가능합니다.) 3) 전면 커버(Front cover)를 닫기 전에 커버의 오링과 나사산을 점검하고 필요한 경우 오링을 교체하 십시오.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 5.4 전원 연결 요구사항 *Note. 커넥터 단자가 있는 장치를 사용하는 경우 분리 거리 표준을 준수하고 연결선이 분리되지 않도록 올바 르게 연결하십시오. 아래와 같이 연결 테이블 및 결선도에 제공된 전기적 사양에 따라 제품을 연결하십시오 Electrical Connections Connection Terminals Supply + (Ub+) PWR +...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6. 배선 6.1 연장 및 보상 도선 온도 측정에 사용하는 케이블로 열전대(TC)와 동일한 재질(연장선) 또는 열전대(TC)와 유사한 열기전력 특성을 가진 재질(보상)로 된 도선을 계측기 단자까지 연장하여 사용하는 전선입니다. 보상 도선은 열전 대(TC)를 연장한 것과 같은 동일 효과로 온도를 보상할 수 있고, 사용 환경 조건에 따라 저온용, 고온용, 내습용, 내유용, 내굴곡용...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6.2 배선 주의사항 1) 방폭 등급 제품은 반드시 전원을 차단한 후 배선하십시오. 2) 열전대(TC)는 극성(+/-)을 확인한 후 연결하고, 측온저항체(RTD)의 경우에는 A/B/B(3선식) 단자를 분리한 후 배선하십시오. 3) 보상 도선 및 케이블의 끝은 압착 단자를 사용하여 단자대에 부착하고 나사는 단단히 조입니다. 4) 트랜스미터에...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 6.5 국제 색상 비교표 제품을 연결하기 위해 아래 테이블을 참조하십시오. (색상은 고객의 요구 사항에 따라 다르게 적용될 수 있습니다.) 열전대(TC) EN (IEC 60584-3) ANSI(ISA MC96.1) JIS C 1610 (KS C 1609) Type Brown White Blue White Violet(Purple)
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 7. 로컬 메뉴 시스템 구조 7.1 WTT-3000 (WISE) "Z" 버튼: 커서를 다른 위치로 변경합니다. "M" 버튼: 다음 메뉴 항목으로 변경하거나, 변경된 설정 값을 저장합니다. "S" 버튼: 표시된 값을 변경합니다. "S"+"Z" 버튼: 두 버튼을 동시에 2~5초간 눌러 메뉴 2 항목으로 진입합니다.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 7.1.3 메뉴 설정 값 테이블 메뉴 1. LCD 화면 표현 방식 선택 1. 전류(mA) 2. PV(°C, °F)(St’d) 3. PV(%) 메뉴 2. 단위 변경 1. °C (St’d) 2. °F 3. °R 4. K 5. mV 6. Ohm 메뉴...
방폭 type 일반 type Name plate 경고. 폭발성가스분위기가 존재할 우려가 있는 경우 열지 마십시오! 2022 Deogyeong-daero,Giheung-gu, Yongin-si,Gyeonggi-do,Korea WISE CONTROL INC. KCs Ex db 방폭 인증 제품은 확인 시험에 합격하고 인증기관에 제출된 사양과 동일함. 명판을 장치에서 분리하지 마십시오.
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 9. 유지 보수 유지 보수 활동을 수행해야 하는 경우 숙련된 인력만 유지 보수를 수행할 수 있으며 ㈜와이즈는 유지 보수를 지원할 수 있습니다. 수리 수리는 ㈜와이즈 또는 부품 제조업체에서만 수행해야 합니다. 재 교정 장치의 설정 값 또는 정확도는 사용 기간이나 환경에 따라 미세하게 변할 수 있습니다. 이는 설정된 측 정...
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 11. 사용자 의무 온도 센서는 고온 및 부식성 환경에서 사용되는 제품으로 예상되는 각종 안전사항을 고려하여 제품을 선정 하여야 하며, 모든 온도 센서 디자인에서는 올바른 설치가 가장 중요합니다. 잘못된 설치는 궁극적으로 부정확한 온도 판독으로 이어질 수 있습니다. ㈜와이즈는...
Page 62
Tel +82-2-300-2300 Fax +82-2-300-2400 webmaster@wisecontrol.com 본 설명서의 내용은 심혈을 기울여 제작되었지만, 오탈자 또는 수정해야 할 내용이 있을 수 있으니 이점 양해하여 주시기 바랍니다. 본 제품의 규격 및 외관은 품질 향상을 위해 사전 통보 없이 변경될 수 있으며, ㈜와이즈는 이에 대한 변경 권리를...
Need help?
Do you have a question about the SMT3000 and is the answer not in the manual?
Questions and answers