Opening And Closing The Unit; To Open The Indoor Unit - Daikin Altherma ELSH12P30E Series Installation Manual

Hide thumbs Also See for Altherma ELSH12P30E Series:
Table of Contents

Advertisement

PATTERN 4
PATTERN 4 is only allowed for installations in technical rooms (i.e.
room that is NEVER occupied by persons). For this pattern there are
no requirements to the minimum floor area if you provide 2 openings
(one at the bottom, one at the top) between the room and the
outside to ensure natural ventilation. The room must be protected
from frost.
A
a2
Min. 50% of A
nv-min
a1
A nv (≥A
)
nv-min
A
Unoccupied room where the indoor unit is installed.
Must be protected from frost.
a1
A
: Bottom opening for natural ventilation between the
nv
unoccupied room and the outside.
▪ Must be a permanent opening that cannot be closed.
▪ Must be above ground level.
▪ Must be completely located between 0 and 300 mm from
the floor of the unoccupied room.
▪ Must be ≥A
(minimum bottom opening area as
nv-min
specified in the table below).
▪ ≥50% of the required opening area A
≤200 mm from the floor of the unoccupied room.
▪ The bottom of the opening must be ≤100  mm from the
floor of the unoccupied room.
▪ If the opening starts from the floor, the height of the
opening must be ≥20 mm.
a2
Top opening for natural ventilation between room A and
the outside.
▪ Must be a permanent opening that cannot be closed.
▪ Must be ≥50% of A
nv-min
as specified in the table below).
▪ Must be ≥1.5 m from the floor of the unoccupied room.
A
(minimum bottom opening area for natural ventilation)
nv-min
The minimum bottom opening area for natural ventilation between
the unoccupied room and the outside depends on the total
refrigerant in the system. For intermediate refrigerant charges, use
the row with the higher value. Example: If the refrigerant charge is
3.5 kg, use the row of 3.55 kg.
Total refrigerant charge (kg)
3.25 kg
3.35 kg
3.45 kg
3.55 kg
3.65 kg
3.75 kg
3.85 kg
3.95 kg
4.05 kg
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH₂O
4P708484-1 – 2023.03
must be
nv-min
(minimum bottom opening area
A
(dm²)
nv-min
9.1 dm²
9.2 dm²
9.4 dm²
9.5 dm²
9.7 dm²
9.8 dm²
9.9 dm²
10.0 dm²
10.2 dm²
4.2

Opening and closing the unit

4.2.1

To open the indoor unit

NOTICE
The top cover can only be removed if the switch box is
lowered.
Overview
b
a
a
User interface panel
b
Switch box cover
Open
1 Remove the user interface panel. Open the hinges at the top
and slide the interface panel downwards.
2 Remove the switch box cover.
NOTICE
Do NOT damage or remove the foam sealing of the switch
box.
3 Disconnect the ground connection from the top cover of the
switch box.
4 Unit installation
1
2
Installation manual
13

Advertisement

Table of Contents
loading

Table of Contents