Important Safety Instructions - ABB CC1600-SC55 Quick Start Manual

Small cell -48v power source
Table of Contents

Advertisement

Important Safety Instructions

1.
SAVE THESE INSTRUCTIONS – This document contains important safety and operating instructions for the Small Cell 48V
Power Source.
2.
Before using the Small Cell 48V Power Source, read all instructions and cautionary markings on the AC Panel Feeding the
unit, the radio, and all other connected equipment.
3.
Rules and Regulations - Follow all national and local rules and regulations when making field connections.
4.
Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
a.
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
b.
Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker
rating.
c.
Size DC field-wired conductors with 90°C ampacity (NEC) equal to or greater than 30A .
5.
AC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
6.
Compression Connectors
a.
U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified field-wire
conductors.
b.
All installations - apply the appropriate connector to the correct size conductor as specified by the connector
manufacturer, using only the connector manufacturer's recommended or approved tooling for that connector.
7.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
8.
Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors. Always provide a drip loop to
shed water off cables before they enter the strain reliefs.
9.
Alarm Signals - Provide external current limiting protection. Rating–60V (125V for 125V charger), 0.5A unless otherwise
noted.
10. Grounding - Connect the equipment chassis directly to ground.
11. This equipment is to be mounted directly and permanently above non-combustible surface, such as concrete or metal.
12. WARNING: Equipment is not designed to charge an external battery source.
13. WARNING: A battery can present a risk of electrical shock, burn from high short circuit current, fire or explosion from vented
gases. Observe proper precautions.
Page 3