Configuration Wizard: System - Daikin ETVH16S18DA6V(G) Installation Manual

Hide thumbs Also See for ETVH16S18DA6V(G):
Table of Contents

Advertisement

INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. If you want to change these
settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
6.2.3

Configuration wizard: System

Indoor unit type
The indoor unit type is displayed, but cannot be adjusted.
Backup heater type
The backup heater is adapted to be connected to most common
European electricity grids. The type of backup heater can be viewed
but not changed.
#
Code
▪ 3: 6V
[9.3.1]
[E‑03]
▪ 4: 9W
Domestic hot water
The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. This setting is read only.
#
Code
(a)
[9.2.1]
[E‑05]
▪ Integrated
(a)
[E‑06]
The backup heater will also be used
for domestic hot water heating.
(a)
[E‑07]
(a)
Use the menu structure instead of the overview settings. Menu
structure setting [9.2.1] replaces the following 3 overview settings:
• [E-05]: Can the system prepare domestic hot water?
• [E-06]: Is a domestic hot water tank installed in the system?
• [E-07]: What kind of domestic hot water tank is installed?
Emergency
When the heat pump fails to operate, the backup heater can serve
as an emergency heater. It then takes over the heat load either
automatically or by manual interaction.
▪ When Emergency is set to Automatic and a heat pump failure
occurs, the backup heater automatically takes over the domestic
hot water production and space heating.
▪ When Emergency is set to Manual and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning main menu screen and confirm whether the
backup heater can take over the heat load or not.
▪ Alternatively, when Emergency is set to:
▪ auto
SH
reduced/DHW
domestic hot water is still available.
▪ auto SH reduced/DHW off, space heating is reduced and
domestic hot water is NOT available.
▪ auto
SH
normal/DHW
normally but domestic hot water is NOT available.
Similarly as in Manual mode, the unit can take the full load with
the
backup
heater
if
the
Malfunctioning main menu screen.
To keep energy consumption low, we recommend to set Emergency
to auto SH reduced/DHW off if the house is unattended for longer
periods.
ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P586454-1C – 2020.12
Description
Description
on, space heating is reduced but
off, space heating operates as
user
activates
this
via
#
Code
[9.5.1]
[4-06]
INFORMATION
The auto emergency setting can be set in the menu
structure of the user interface only.
INFORMATION
If a heat pump failure occurs and Emergency is set to
Manual, the room frost protection function, the underfloor
heating screed dryout function, and the water pipe
antifreeze function will remain active even if the user does
NOT confirm emergency operation.
Number of zones
The system can supply leaving water to up to 2 water temperature
zones. During configuration, the number of water zones must be set.
INFORMATION
Mixing station. If your system layout contains 2 LWT
zones, you need to install a mixing station in front of the
main LWT zone.
#
Code
[4.4]
[7‑02]
[4.4]
[7‑02]
the
6 Configuration
Description
▪ 0: Manual
▪ 1: Automatic
▪ 2: auto SH reduced/DHW on
▪ 3: auto SH reduced/DHW off
▪ 4: auto SH normal/DHW off
Description
▪ 0: Single zone
Only one leaving water temperature
zone:
a Main LWT zone
▪ 1: Dual zone
Two leaving water temperature zones.
The main leaving water temperature
zone consists of the higher load heat
emitters and a mixing station to
achieve the desired leaving water
temperature. In heating:
c
a Additional LWT zone: Highest
temperature
b Main LWT zone: Lowest temperature
c Mixing station
Installation manual
a
a
b
19