10
Start-up
-
DHW SETPT
• Th is is the desired set point temperature of
Domestic Hot Water (DHW) generated by the
unit. Note that the required anti-scald mixing
valve will likely require a setting greater than the
desired DHW temperature.
• Range: 60°F – MAX DHW SETPT
• Default: 120°F
-
DOMESTIC HOT WATER BOILER WATER TEMP
(BOILER ONLY)
Th is is the desired temperature of the boiler water
going to the indirect tank.
Range: 68°F – 190°F
Default: 180°F
-
SPACE HEAT RATE LIMITING (COMBI ONLY)
Th is feature is used when the maximum space
heating load is less than the maximum input
rating of the unit. Th is setting will limit the
maximum input rate of the unit for a space
heating demand only (DHW demands will not
be limited).
Range: 10% – 100%
Default: 100%
-
COMBI PRE-HEAT (COMBI ONLY)
Th e Combi Pre-Heat function can be used to
improve DHW performance and comfort by
maintaining boiler water at an elevated
temperature to be able to immediately serve a
DHW demand. In certain applications, the Pre-
Heat function can also reduce water usage
compared to not using Pre-Heat.
Pre-Heat, however, can increase fuel usage as the
unit will periodically fi re to maintain heated
water.
Settings: ENABLED/DISABLED
Default: ENABLED
Service mode
Entering
WARNING
immediately cause the boiler to
fire. Failure to ensure that the unit
is fully assembled and installed and
in safe working condition; including
having properly installed venting, all
air purged from the heat exchanger,
and with proper water supply and
flow, can result in serious injury,
death, significant property damage, or
destruction of the heater.
66
Enabling
Service
Mode
will
Installation & Service Manual
F I R E T U B E
Th e Noble Fire Tube includes a Service Mode feature
that can be used to force the unit to run at a particular
fi ring rate. Th is feature can be used by qualifi ed service
technicians for adjusting combustion or troubleshooting
the unit.
Service Mode can be accessed by holding ► and ▼
buttons simultaneously for 5 seconds.
Combi Models Only: In Service Mode, the unit will
operate with the diverter valve in the space heating
position; therefore, zone(s) in the heating system must be
actively running in order to reject the heat generated.
Figure 10-6 Service Menu
Button functions in Service Mode
▲/▼ -
Change the target fan speed in increments of 100 rpm.
-
Toggle between operating at high fi re and low fi re.
-
Exit Service Mode and return to the Home Screen.
Check flame and combustion
1. Turn the main power off to the boiler.
2. Remove the flue plug from the vent pipe adapter.
Note: Combustion measurements will be made at this
point.
Figure 10-7 Flue Plug Removal
REMOVE THE FLUE PLUG
FROM THE VENT PIPE
ADAPTER
DIR #2000534695 00