10. Compressor
10-1. Compressor Trouble Diagnosis and Check Methods
Generally, compressor failures can be classified into the following categories.
(1) Mechanical trouble
(2) Electrical trouble
Trouble diagnosis is based on the following remote controller displays: [H03] (Compressor 1: INV compressor,
center), [H11] [H12] [H13] (Compressor 2: constant-speed compressor 1, left side when viewed from front), [H21]
[H22] [H23] (Compressor 3: constant-speed compressor 2, right side when viewed from front (not present in type
90). A judgment is made based on factors that include the following: coil resistance (varies depending on the
compressor), insulation resistance, current, leakage breaker operation, oil and refrigerant fouling, odor, pressure,
and noise.
Reference: Insulation resistance (Use a DC 500 V insulation resistance meter and measure the insulation
resistance between the electrified and non-electrified parts.)
(a) Motor
(b) Compressor → Min. 100 MΩ (servicing part)
(c) Unit
* Minimum insulation resistance as required by generally accepted requirements is 1 MΩ.
JUDGMENT START
Is there
Is there burning of the failed
compressor motor?
YES
YES
Follow the instructions in
"3. Discharging Compressor Oil" and
drain the oil from all compressors in the
same system. Then inspect.
Are there 2 or more outdoor units where
the compressor oil color phase is 4.0 or
higher or where a sharp odor is present?
YES
YES
Go to "10-2-3. Replacing all
compressors in a system."
Follow the instructions in "10-2-4. Dry
core cleaning" and perform dry core
cleaning of all outdoor units.
Reference: Symptoms of motor burning
1.
Ground fault results in breaker operation.
2.
Short circuit results in different coil resistance at different phases.
3.
Open circuit
(A) Locking (intrusion of foreign objects, galling, etc.)
(B) Pressure rise failure (damaged valve, seal, bearing, or other component)
(C) Noise (damaged stator rotor, valve, or other component)
(A) Coil burning
(B) Open circuit
(C) Insulation failure
(D) Short circuit
→ Min. 300 MΩ
→ Min. 10 MΩ (This is due to the presence of refrigerant, which decreases the
insulation resistance.)
Follow the instructions in
"3. Discharging Compressor Oil"
NO
NO
and drain the oil from the failed
compressor. Then inspect.
NO
NO
Go to "10-2-2. Replacing all
compressors in a failed unit."
Follow the instructions in
"10-2-4. Dry core cleaning" and
perform dry core cleaning of the
failed outdoor unit.
2 - 23
3-WAY ECO-i SYSTEM
Outdoor Unit Repair Procedures
Is the color phase 4.0 or above, or is a
sharp odor present?
YES
YES
NO
NO
Go to "10-2-1. Replacing only the
failed compressor."