Optional Gas Heat; Gas Piping; Electric Heat Application Data; Gas Heat Application Data - York SUNLINE MagnaDRY WR300 Installation Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MagnaDRY WR300:
Table of Contents

Advertisement

TABLE 3: ELECTRIC HEAT APPLICATION DATA
NOMINAL
VOLTAGE
HEATER
3-PHASE,
SIZE (KW)
60 HZ
18
208/230,460,575
36
208/230,460,575
208/230
54
460,575
208/230
72
460,575
TABLE 4: GAS HEAT APPLICATION DATA
0 To
2,000 To
2,000 Feet
4,500 Feet
Above
Sea Level
Sea Level
Max.
Min.
Max.
300
150
270
400
200
360
1.
On VAV units, individual VAV boxes must be full open in heating mode to insure airflow falls within
temperature rise range.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet
per hour of gas flow required, specific gravity of the gas
and the length of run. "National Fuel Gas Code" Z223.1
(in U.S.A.) or the current Gas Installation Codes CSA-
B149.1 (in Canada) should be followed in all cases
unless superseded by local codes or gas utility require-
ments. Refer to the Pipe Sizing Table 5.
The heating value of the gas may differ with locality.
The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement
specifying a minimum diameter for gas piping.
All units require a one-inch pipe connection at
the entrance fitting.
Johnson Controls Unitary Products
MINIMUM CFM UNIT SIZE
15 TON
20 TON
25 TON
4500
4500
5000
6000
7500
4500
5000
4500
Output Capacity (Mbh)
0 To
2,000 Feet
Above
Above
Sea Level
Min.
Max.
135
240
180
320

OPTIONAL GAS HEAT

These gas-fired heaters have aluminized-steel or
optional stainless steel, tubular heat exchangers with
spark ignition with proven pilot.
All gas heaters are shipped from the factory equipped
for natural gas use, but can be field converted to L.P./
Propane with Kit Model # 1NP0418. See Gas Heat
Application Data Table.
2,000 To
4,500 Feet
Available
Above
on Models
Sea Level
Max.
213
15, 20 & 25 Ton
281
15, 20 & 25 Ton
TABLE 5: PIPE SIZING
Length in Feet
10
20
30
40
50
60
70
80
90
100
Maximum capacity of pipe in cubic feet of gas per hour. (Based upon
a pressure drop of 0.3 inch water column and 0.6 specific gravity
gas).
284813-YIM-C-1008
Temp.
Natural
Rise ºF
Gas
At
Rate
1
Full Input
(Ft./Hr.)
Min.
Max.
279
20
50
372
30
60
Nominal Iron Pipe Size
1 in.
1-1/4 in.
520
1,050
350
730
285
590
245
500
215
440
195
400
180
370
170
350
160
320
150
305
13