Troubleshooting - Aprilaire E130C Installation And Operating Manual

Table of Contents

Advertisement

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 a�m� to 5:00 p�m� CST, at (800) 334-6011� Use the guides on the following pages to identify
and correct system faults� Contact Technical Support before replacing the unit or any components and for additional troubleshooting�
DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE REQUIRED
will be displayed on the control screen�
TABLE 1 – DIAGNOSTIC CODES
Diagnostic
Code
Failure Mode
Internal Humidity or
E1
Temperature Sensor
Open or Shorted
High Refrigeration
E2
Pressure
Model 76
E3
Remote Control
Communication Loss
E4
Insufficient Capacity
High Temperature
E5
Thermistor Failure
Low Temperature
E6
Thermistor Failure
Action
1. Cycle power to clear error code�
2. If error code reoccurs replace User Interface, Part No� 5445�
1. Verify that the fan works, and that there is nothing restricting air flow�
2. If the fault persists, call Technical Support�
1. Check connections between Model 76 and dehumidifier control board� Terminals should be fully
inserted and secured in the control board and Model 76 control terminals�
2. If connections are correct and secure, turn off the dehumidifier and remove the Model 76� Use a short
section of 4-wire cable to reconnect the Model 76 to the control board� Turn the dehumidifier back on
and increase the dryness level setting on the Model 76� If the dehumidifier turns on, the problem is
with the wiring between the dehumidifier and control�
3. If the dehumidifier does not turn on, call Technical Support�
1. Check the frost sensor connection at the power board� Terminal should be fully seated on the power
board pins�
2. Remove the side access panel and verify that the sensor is secured to the suction line�
3. If the sensor is connected and secured to the refrigeration line proceed to the next step�
4. Reset the fault by cycling power to the dehumidifier�
5. Turn the humidity setting down (below room/home humidity level) to make a dehumidification call�
6. Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test
mode by simultaneously pressing the
the temperature measured by the internal sensor while also displaying AIR SAMPLING and ON, the
humidity measured by the internal sensor while also displaying %RH and ON, and the frost sensor
temperature while also displaying ON� Scroll through these values and by using the
buttons�
7. Record values and call Technical Support�
1. Check the high temperature sensor connection at the power board� Terminal should be fully seated
on the power board pins�
2. Remove the side access panel and verify the sensor is not damaged and connected to the
refrigeration line coming from the compressor�
3. If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part
No� 5456 — contact Technical Support to confirm�
1. Check the low temperature sensor connection at the power board�
2. Remove the side access panel and verify the sensor is not damaged and connected to the suction
line�
3. If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part
No� 5455 — contact Technical Support to confirm�
and MODE buttons for 3 seconds� The LCD will display
90-1854
Reset
Cycle Power
Cycle Power
Self-Correcting
Cycle Power
and
Cycle Power
Cycle Power
9