Wiring
Power Supply
1
Factory-installed jumper,
2
remove only when installing on 2-transformer system.
Use either O or B terminals for changeover valve.
3
Use a small piece of wire (not included) to connect W and Y terminals.
4
A 24 VAC 500mA common connection is required with this thermostat.
5
Typical 1H/1C system: 1 transformer
5
Typical 1H/1C heat pump system
2
1
4
5
3
Typical heat only system
2
5
Technician Setup Menu
To enter tech setup:
1. Press and hold the + and - buttons for 3 seconds.
2. Press and hold TECH button.
3. Configure the installer options as desired using the table below. Use the + or - buttons to
change settings and the PREV and NEXT buttons to move from one step to another.
4. To exit tech setup: press and hold the + and - buttons for 3 seconds, or wait 20 seconds.
Tech Setup Steps
This feature allows the installer to
Room
change the calibration of the room
Temperature
temperature display. For example, if the
thermostat reads 70 degrees and you
Calibration
would like it to read 72 then select +2.
The compressor short cycle delay
Compressor
protects the compressor from "short
Short Cycle
cycling". This feature will not allow
the compressor to be turned on for 5
Display
minutes after it was last turned off.
The swing setting often called "cycle
rate", "differential", or "anticipation" is
Cooling
adjustable. A smaller swing setting will
Swing
cause more frequent cycles and a larger
swing setting will cause fewer cycles.
The swing setting often called "cycle
rate", "differential", or "anticipation" is
Heating
adjustable. A smaller swing setting will
cause more frequent cycles and a larger
Swing
swing setting will cause fewer cycles.
This feature allows you to set a
Heating
maximum heat setpoint value. The
Setpoint
setpoint temperature cannot be raised
above this value.
Limit
This feature allows you to set a
maximum cool setpoint value. The
Cooling
setpoint temperature cannot be raised
Setpoint
above this value.
Limit
Swing Setting Tip
Temperature swing, sometimes called differential or cycle rate, can be
customized for this individual application. For most applications choose a swing
setting that is as wide as possible without making the occupants uncomfortable.
Typical 1H/1C system: 2 transformers
5
Typical heat only systems w/o fan
5
Typical cool-only sytem
2
1
5
LCD Will Show
Adjustment Options
You can adjust the room
0
temperature display to read
4˚above or below the factory
calibrated reading.
COMP DELAY
Selecting "On" will not allow the
compressor to be turned on
0F
PREV
NEXT
The cooling swing setting is
COOL SWING
adjustable from 0.2˚ to 2˚. A
swing setting of 0.5˚will begin
0.5
cooling at approximately 0.5˚
above the setpoint and stop
approximately 0.5˚ below the
setpoint.
PREV
NEXT
The heating swing setting is
HEAT SWING
adjustable from 0.2˚ to 2˚. A
swing setting of 0.5˚will begin
0.4
heating at approximately 0.5˚
below the setpoint and begin
approximately 0.5˚ above the
setpoint.
PREV
NEXT
Use the + and - buttons to select
HE L
the maximum heat setpoint.
90
PREV
NEXT
Use the + and - buttons to select
CO L
the maximum cool setpoint.
44
PREV
NEXT
Tech settings continued on next page ...
Wiring
Replacement Thermostat Wiring
1.
If you are replacing a thermostat, make
note of the terminal connections on the
thermostat that is being replaced. In some
cases the wiring connections will not be
color coded. For example, the green wire
may not be connected to the G terminal.
2.
Loosen the terminal block screws. Insert
wires then retighten terminal block screws.
3.
Place nonflammable insulation into wall
opening to prevent drafts.
4.
This thermostat requires a 24V common
wire to the C terminal.
Installation Tip
Do not overtighten terminal block screws, as this can damage the terminal block.
A damaged terminal block can keep the thermostat from fitting on the subbase
correctly or cause system operation issues.
Wiring Chart
For all systems, the following terminals are wired according to whether you have a
single or dual transformer system as shown:
SINGLE
TRANSFORMER
SYSTEM
DUAL
TRANSFORMER
SYSTEM
*FAILURE TO REMOVE PROVIDED JUMPER ON DUAL TRANSFORMER INSTALLATIONS COULD CAUSE SEVERE DAMAGE TO HVAC SYSTEMS
O Terminal
B Terminal
1
Note: Devices such as a float switch that mechanically break circuits should be installed
so that they break the control wire (Y) not the power (R). Interrupting the power circuit
will shut off power to the thermostat completely and not allow it to operate.
If using in Heat Pump without Auxiliary or Emergency heat application,
please see wiring diagram on previous page.
Technician Setup Menu
Tech Setup continued:
Tech Setup Steps
This feature allows you to display
temperature in either Fahrenheit or
˚F or ˚C
Celsius.
Default
You can select either 12 or 24 hour
clock setting.
12 or 24
Hour Clock
O
The display light can be configured to
Display
operate 3 different ways. To come on
only when the Light Key is pressed,
Light
when Any Key is pressed, or stay on ALL
ON
of the time.
You can configure this thermostat to
accept a programmed schedule from
the mobile App, if WIFI
Programmable
communication is set up through your
home network.
0.5 ˚F
(Only displayed if
the thermostat is
connected to the
internet)
You can configure the system for your
0.4 ˚F
particular application.
HEAT-OFF-COOL
System
HEAT-OFF
Set
COOL-OFF
Select GAS for systems that control the
90
fan during a call for heat. Select ELEC
to have the thermostat control the fan
during a call for heat.
Fan
Operation
44
Caution:
Electrical Hazard
Failure to disconnect the power
before beginning to install this
product can cause electrical shock or
equipment damage.
Warning:
All components of the control system
and the thermostat installation must
conform to Class II circuits per the
NEC Code.
Max Torque = 6in-lbs.
RH
RC
24 VAC HOT
JUMPER SHOULD REMAIN
24 VAC Common
INSTALLED
24 VAC Common
24 VAC-Heat
24 VAC-Cool
*REMOVE PROVIDED
*REMOVE PROVIDED
*FROM COOL
JUMPER
JUMPER
TRANSFORMER
Heat pump changeover valve-- Energized during cooling
Heat pump changeover valve-- Energized during heating
LCD Will Show
Adjustment Options
F OR C
˚F for Fahrenheit
F
PREV
NEXT
12/24H
Use the + and - key to
12
select 12 or 24 hour clock.
PREV
NEXT
DISP LIGHT
AUTO "AU" - Any key ON
AU
ON "On" - Always ON
OFF "OF" - Only light key ON
PREV
NEXT
PROGRAMABLE
Select "OF" to configure the
thermostat for NON-Program-
mable. (Time of day will NOT
appear on display).
OF
Select "ON" to configure the
thermostat for programmable
operation, from the app.
PREV
NEXT
Use the + and - key until the
SYS MODE
desired application is flashing.
HC
HC - Heat - OFF - Cool
H - Heat Only
C - Cool Only
PREV
NEXT
GAS - "GS"
FAN OPER
ELEC - "EL'
G5
PREV
NEXT
C
G
Blower / Fan
500mA
500mA
Blower / Fan
Default
˚F
12
AUTO
OFF
Heat
Off
Cool
GAS