10.3.3 Peak Demand Reset
To reset the recorded peak kW demand, complete the following steps:
1. Press the MENU button until "Reset kW/kWh Read" is indicated by the
arrow on the display.
Date & Time
Device ID
Reset KW/KWH Read
Exit
2. Press the SELECT button. The following screen will appear on the display.
Reset kW only? N
Reset all? N
3. Press the UP button to change the N to a Y after "Reset kW only?".
4. The peak demand will be reset to zero and the meter will return to its normal
scrolling display mode.