Page 1
INSTALLATION, USE AND MAINTENANCE MANUAL GAS CONDENSING FREE-STANDING BOILER 100T MYDENS 115T 140T GAS CONDENSING 180T FREE-STANDING HOT WATER HEATER 210T AGUADENS 280T 62403578 - R03 14-07-2021_UK...
Installation and Modifications: Only a Competent Person must carry out the installation and calibration of the heater. Never modify the heater or its flue gas carrying components in any way. This heater must be properly vented. 60T - 280T COSMOGAS...
Page 3
Before performing any cleaning or maintenance, disconnect the appliance from the mains power supply. After any cleaning or maintenance, before reconnecting the power supply, make sure that all internal parts are properly dry. 60T - 280T COSMOGAS...
Installations in caravans and non-permanent dwellings. - BS 5482-3:2005 - Domestic butane and propane gas burning installations. Installations in boats, yachts and other vessels. - Building regulations issued by the Department of the Environment and Building Standards Regulations. 60T - 280T COSMOGAS...
2.1 - Presentation Congratulations! You have purchased one of the best products on the market. Each individual part is proudly designed, manufactured, tested and assembled within the COSMOGAS facilities, thus guaranteeing the best quality control. 2.2 - Overview of models...
Only in models 60T, 70T, 100T, 115T and 140T N° 2 FLANGE EN 1092-1-13 DN65 PN16 NPT Only in models 180T, 210T and 280T 2.4 - Manufacturer COSMOGAS srl Via L. da Vinci 16 47014 - Meldola (FC) Italy Tel. (+39) 0543 498383 Fax. (+39) 0543 498393 www.cosmogas.com...
When the boiler is connected to an external sensor, it always works at maximum efficiency (see section 17.9). Figure 4-5 - Modulation of model 280T boiler 60T - 280T COSMOGAS...
(see figures 10-1 and 10-2, detail “20”). Figure 4-6 - Example of diagram of efficiency / delivery and return temperature / outdoor temperature, for a home, in a very cold area and a system with radiators. 60T - 280T COSMOGAS...
- connection to outlet for condensate produced by the boiler; - electric connection of the room thermostat; - connection to safety valve outlet; - connection to the outdoor temperature sensor (where applicable); - room ventilation. 020010.01.011 020010.01.012 Figure 5-1 - Undoing transport pallet screws 60T - 280T COSMOGAS...
- Hydrochloric acid/muriatic acid; - Cements and glues; - Antistatic fabric softeners used in clothes dryers; - Chlorine-type bleaches, detergents and cleaning solvents found in household laundry rooms; - Adhesives used to fasten building products and other similar products; 60T - 280T COSMOGAS...
(detail “B” in figure 6-1) must be removed before the top Figure 6-1 - Lifting system cover is put on. B = Locking nut MIN 0 020010.01.013 MAX 0,39 " (10 mm) 020010_01_030 Figure 6-2 - Feet to make it level 60T - 280T COSMOGAS...
8-1, 8-2, 9-1 and 9-2. Figure 7-1 - Minimum distances to be observed for models 60T, 70T, 100T, 115T and 140T Figure 7-2 - Minimum distances to be observed for models 180T, 210T and 280T 60T - 280T COSMOGAS...
Figure 8-1 - Dimensions and centre space distances of attachments for models 60T, 70T, 100T, 115T and 140T (References in figure 8-3) Figure 8-2 - Dimensions and centre space distances of attachments for models 180T, 210T and 280T (References in figure 8-3) 60T - 280T COSMOGAS...
Page 29
28 mm * Connections and flanges are not factory fitted; ** Air intake in room, do not obstruct and do not add any connection; Figure 8-3 - Table of diameters of connections in figures 8-1 and 8-2 60T - 280T COSMOGAS...
Figure 9-1 - Dimensions and centre space distances of attachments for models 60T, 70T, 100T, 115T and 140T (References in figure 9-3) Figure 9-2 - Dimensions and centre space distances of attachments for models 180T, 210T and 280T (References in figure 9-3) 60T - 280T COSMOGAS...
Page 31
C = Cold water inlet; D = Connections supplied; E = Gas input connection; 020029.01.004 020013.01.013 Figure 9-4 - Assembly of flanges and reductions on threaded connections for hot water outlet, cold water inlet and gas 60T - 280T COSMOGAS...
“17” in figure 3-1 and pump “36” is 11 Expansion tank NOT the modulating type) 12 Microbubble separator 57 - Drain valve 13 External sensor 58 - Manifold sensor 14 Filter 15 Electric power supply 60T - 280T COSMOGAS...
WARNING! The safety drain valve must be oriented or conveyed in such a way as not to create danger situations to people or things in case of intervention. 020029.01.006 Figure 10-3 - Safety rellief valve 60T - 280T COSMOGAS...
In old systems planned to work with radiators, characterised by pipework with a very large WARNING! COSMOGAS is not liable for any diameter, the water content of the system is significant and damage caused by incorrect use of additives in the fosters the formation of dirt and deposits.
DEPOSITS These are insoluble organic and inorganic substances: DIRT, RESIDUES FROM WORK. * In case of aluminum radiators, the pH must be between 7 and 8. 60T - 280T COSMOGAS...
A = MYDENS 60T and MYDENS 70T B = MYDENS 100T and MYDENS 115T C = MYDENS 140T D = MYDENS 180T and MYDENS 210T E = MYDENS 280T Water flow rate (m Figure 10-4 - Hydraulic resistances of MYDENS models “60T-280T” 60T - 280T COSMOGAS...
WARNING! The safety drain valve must be oriented or conveyed in such a way as not to create danger situations to people or things in case of intervention. 020029.01.006 Figure 11-2 - Safety rellief valve 60T - 280T COSMOGAS...
Refer to the expansion tank manufacturer’s instructions for further details about installation. Figure 11-3 Key A = AGUADENS 60T and 70T B = AGUADENS 100T and AGUADENS 115T C = AGUADENS 140T D = AGUADENS 180T and AGUADENS 210T E = AGUADENS 280T Figure 11-3 - Hydraulic resistances of AGUADENS models “60T-280T”...
3,6/4,5 7,8/9 12,8/13,5 14,8/18 4,0/4,5 8,6/9 13,1/13,5 16,4/18 Max 15 4,0/4,5 8,6/9 13,1/13,5 16,4/18 Figure 11-4 - Table of minimum/maximum flow values inside the water heater in function of the water hardness and the water temperature 60T - 280T COSMOGAS...
3 mm, as envisioned by the applicable standards in force. A = Electric cables sheath; B = Line; C = Neutral; D = Earth. Figure 13-1 – Electrical connections 60T - 280T COSMOGAS...
Proceed with the steps given in section 17.9.1 to set the correct adjustment values for the supply temperature, according to the outdoor temperature. Figure 13-2 – Correct positioning of the room thermostat/chronothermostat 60T - 280T COSMOGAS...
Where the possibility of scalding has been identified, appropriate measures such as thermostatic mixing valves should be considered. Maximum delivery temperature (Par.3017) Minimum delivery temperature (Par.3018) Voltage Hysteresis of ON/OFF Figure 13-3 – Operating rules for 0-10 VDC analogue input 60T - 280T COSMOGAS...
51°C may cause permanent injury/damage to persons, animals and objects. In particular, protect children, the elderly and people with disabilities against any possible risks of scalds, by inserting devices that limit the usage temperature of the DHW to users. 60T - 280T COSMOGAS...
Page 47
13 - INSTALLATION - Electrical connections Figure 13-4 - MYDENS boiler electrical connections (Example of system shown in figure 10-1) Figure 13-5 - MYDENS boiler electrical connections (Example of system shown in figure 10-2) 60T - 280T COSMOGAS...
Page 48
13 - INSTALLATION - Electrical connections Figure 13-6 – AGUADENS hot water heater electrical connections (Example of system shown in figure 11-1) 60T - 280T COSMOGAS...
Further details on ventilation requirements and allowances can be found in sections 5.1.1 and 5.1.2. Key Figure 14-1 A = Plant room; B = Ventilation openings; Figure 14-1 – Exhaust/intake systems 60T - 280T COSMOGAS...
14.- Attach, using screws “D”, the shelter for the electrical connections “L”, for the intake “M” and for the outlet “N” (or “P”) to the top cover (figures 15-25 and 15-26); remembering to insert gaskets “O” and “W” as shown in figure 15-25. 60T - 280T COSMOGAS...
12.- Put on the covers AF and AG as shown in figure 15- 57 and fasten them to the structure with screws “C” (figure 15-58). Then attach the anti-rain grill “R” to the cover AG using screws “B”, as shown in figure 15-58. 60T - 280T COSMOGAS...
5.- Check the pressure on the boiler display again (detail “M” in figure 17-1). If it has dropped, fill up to 1.5 bar again (or up to the value set). 020014.01.030 Figure 16-1 – Filling the condensate outlet siphon 60T - 280T COSMOGAS...
C - From another room, or from a neighbour’s property, immediately call a professionally qualified technician or the gas supply company. Call the Fire Service if the former are not available. 60T - 280T COSMOGAS...
C - From another room, or from a neighbour’s property, immediately call a professionally qualified technician or the gas supply company. Call the Fire Service if the former are not available. 020010.01.019 Figure 16-4 – Replacing the gas nozzle 60T - 280T COSMOGAS...
Page 64
Burner 4 A - Connector from burner 1 (MASTER) B - Connector from display C - Connector from burner 2 D - Connector from burner 3 E - Connector from burner 4 Figure 16-5 - Burners position 60T - 280T COSMOGAS...
G31; apply label “A” if the boiler has been converted to G20. D - Gas inlet tapping point. E - CO2 regulation screw. F - Factory regulation screw (do not touch). Figure 16-6 – Gas valve 60T - 280T COSMOGAS...
Page 66
CO2 LPG gas (G31) at minimum power from 9.7 to 9.9 O2 LPG gas (G31) at maximum power from 5.2 to 5.6 O2 LPG gas (G31) at minimum power from 5.9 to 6.1 Figure 16-8 - Operating settings for the different gases 60T - 280T COSMOGAS...
Do not force the screws to close the tapping points in order to avoid damaging the gas valve. WARNING! Test the gas seal using a leak detection fluid. The use of naked flames is prohibited. 60T - 280T COSMOGAS...
020010.01.022 D - Gas inlet tapping point. E - CO2 regulation screw. F - Factory regulation screw (do not touch). Figure 16-10 – Gas valve 60T - 280T COSMOGAS...
“F” as shown in the manufacturer’s instructions for the outlet pipe. WARNING! Once stopper “F” is in position with the boiler at maximum power, check there are no leaks of exhaust gases that could cause damage. 60T - 280T COSMOGAS...
R - Key for reducing the temperature of the domestic hot water with puffer and for scrolling through and changing the value of the parameters T - On/off switch 60T - 280T COSMOGAS...
To adjust the temperature use keys (see figure 17-1). When the keys are pressed the display, detail “N” in figure 17-1, shows the temperature requested. The temperature of instant domestic hot water can be set to between 20°C and 80°C. 60T - 280T COSMOGAS...
2020 of the next season via parameter . When the outside temperature rises above the value set under this parameter, the central heating switches off automatically. When the 60T - 280T COSMOGAS...
Page 73
2023 Par. = Outdoor spring temperature 2024 Par. = delivery temperature corresponding to projected outdoor spring temperature 3016 Par. = Minimum delivery temperature 3015 Par. = Maximum delivery temperature Figure 17-2 - Graph of climate control 60T - 280T COSMOGAS...
E.g. If it shows 1:29, it means 29 minutes; no lockout or error. E.g. If it shows 2:12, it means 12 hours; E.g. If it shows 3:15, it means 15 days; E.g. If it shows 4:26, it means 26 weeks. 60T - 280T COSMOGAS...
°C From 0 to 80 project outdoor temperature (winter) 2023 Climate control: spring project outdoor temperature °C From 0 to 30 2024 Climate control: delivery temperature corresponding to °C From 0 to 40 spring outdoor temperature 60T - 280T COSMOGAS...
Description of parameter Display on screen “N” in Figure 17-1 Anti-frost function on Boiler temperature (°C) AFro DHW with puffer operation status Temperature of DHW (°C) Operation status of central heating or instant DHW Output temperature (°C) 60T - 280T COSMOGAS...
Software error inside Replace the command and control board. control board Loc 18 Software error inside Replace the command and control board. control board Loc 19 Software error inside Replace the command and control board. control board 60T - 280T COSMOGAS...
Page 78
- If the temperature does not increase, replace the burner ignites 1006) increases in temperature when the burner exhaust gas temperature sensor or the command and ignites. control board. (*) = This error locks out all the burners 60T - 280T COSMOGAS...
B - Check the earthing and that neutral is at 0 volt the control board. B - If the neutral isn’t at zero, the correct electric power supply must be restored. If the neutral is at 0 Volt, try to replace the control board. 60T - 280T COSMOGAS...
Page 80
C - If the display is not connected to the MASTER MASTER the words “NO-CONN” appear D - If none of the above cases apply, replace the control board and/or the display. (*) = This error locks out all the burners 60T - 280T COSMOGAS...
- Cleaning the burner and the primary heat exchanger, flue gas side and checking good order of heat insulation devices (Follow section 18.4) - Clean air intake filter (Follow section 18.6) - Clean condensate outlet system (Follow section 18.7). - Check the appliance efficiency (See section 18.13); 60T - 280T COSMOGAS...
“H” in Figure 18-4. WARNING! Test the gas seal using a leak detection fluid. The use of naked flames is prohibited. 020009.01.008 Figure 18-1 - Dismantling of casing and opening of control panel 60T - 280T COSMOGAS...
“T” in the burner (see figure 18-5). 020009.01.012 020010.01.020 Figure 18-2 - Dismantling sparks generator 020022.01.008 020010.01.021 020009.01.014 Figure 18-3 – Removing the air manifold Figure 18-4 – Removing the gas valve 60T - 280T COSMOGAS...
Page 84
UNIT WARNING! The gasket ensures the combustion chamber is sealed. If the gasket is damaged DO NOT reuse it, it must be replaced along with the burner unit. Consult the manufacturer for information on replacing it. 60T - 280T COSMOGAS...
For accurate location of the electrodes it is good to use sliding callipers to respect the tolerances given in Figure 18-7. A = Left-hand ignition electrode B = Right-hand ignition electrode C = Detection electrode Figure 18-7 - Position of electrodes on the burner 60T - 280T COSMOGAS...
WARNING! Carefully follow figure 18-9 to replace the box “A” in the correct position. After the maintenance described above, restore the level of liquid in the siphon as shown in section 16.1.2. Figure 18-9 - Dismantling and opening condensate neutraliser box 60T - 280T COSMOGAS...
C = Connector for dialogue Burner 2 D = Connector for dialogue Burner 3 (Only in models 180T, 210T and 280T) E = Connector for dialogue Burner 4 (Only in model 280T) Figure 18-10 Connection of display in other burners 60T - 280T COSMOGAS...
6. Follow points 3 to 5 to remove the control board from the burner located lowest down; 7. Fit the board in place of that of Burner 1 (Master); SELECTOR SWITCH S4 020009.01.010_a Figure 18-11 - Command board 60T - 280T COSMOGAS...
High to force the burner, or all the burners, at maximum power; 2010 2200 4.- To end forcing, return parameter multi-burner models) to the value and press the RESET button. 60T - 280T COSMOGAS...
Maximum central heating temperature °C Minimum central heating temperature °C Maximum central heating pressure “PMS” Minimum central heating pressure Rated power supply voltage Rated power supply frequency Absorbed electrical power Electrical protection rating IP21 IP21 IP21 60T - 280T COSMOGAS...
20 - 60 20 - 60 20 - 60 Maximum temperature for safety intervention °C Maximum pressure “PMS” Minimum pressure Rated power supply voltage Rated power supply frequency Absorbed electrical power Electrical protection rating IP21 IP21 IP21 60T - 280T COSMOGAS...
1 or 2 3100 Material selection ABS; CPVC; PVC; SST; PP. 3101 Nation selection US, CA “ S 4 ” “S4” Switch Position (see fig 18-11 and On or Off switch 18-12) N/A = Not Applicable 60T - 280T COSMOGAS...
Page 107
100 and 115 = 40 100 and 115 = 40 60 = 40 140, 180, 210 140, 180, 210 70 = 45 and 280 = 45 and 280 = 45 100, 115 and 140 210 = 2 280 = 3 60T - 280T COSMOGAS...
Hold down RESET button for 2 seconds Hold down RESET button for 5 seconds At the same time, hold down, for the number of seconds shown by the number, the two buttons RESET and Press and release button Press and release button 60T - 280T COSMOGAS...
Page 109
Installer menu shown parameters on display (see in normal section 17.15) operating conditions (see section 17.16) User menu parameters (see section 17.14) Return to normal operation Return to normal operation Figure 21-1 - Command menu diagram 60T - 280T COSMOGAS...
22 - MYDENS PRODUCT FICHE Name or brand of the supplier COSMOGAS MYDENS Supplier’s model number Condensing boiler Low-temperature boiler B1 boiler Cogeneration space heater Combination heater Equipped with supplementary heater Energy efficiency class Item Symbol Unit Rated heat output Seasonal space heating energy efficiency ηs...
23 - AGUADENS PRODUCT FICHE (a) Name or brand of supplier COSMOGAS AGUADENS (b) Supplier’s identifying model number (c) Declared load profile XXL (1) XXL (1) (d) Class of energy efficiency (e) Domestic hot water production efficiency ηwh 85.3 85.6...
24 - BOILER EU DECLARATION OF COMPLIANCE The undersigned CEO of the company COSMOGAS S.r.L., with registered office in Via L. Da Vinci no. 16 - 47014 Meldola (FC) ITALY, DECLARES under its own responsibility that the central heating boiler: SERIAL No.
25 - WATER HEATER EU DECLARATION OF COMPLIANCE The undersigned CEO of the company COSMOGAS S.r.L., with registered office in Via L. Da Vinci no. 16 - 47014 Meldola (FC) ITALY, DECLARES under its own responsibility that the instantaneous water heater: SERIAL No.
Page 116
COSMOGAS s.r.l. Via L. da Vinci 16 - 47014 MELDOLA (FC) ITALY info@cosmogas.com www.cosmogas.com...
Need help?
Do you have a question about the AGUADENS 60T and is the answer not in the manual?
Questions and answers