5.17.6 - “80/125PP coaxial” system: accessories available ................. 33 5.17.7 - “80/125PP coaxial” system: installation examples .................. 34 5.18 - Installing and uninstalling the MYDENS 60 external cover kit (on request) ............35 6 - START-UP ..............................38 6.1 - Start-up .................................. 38 6.1.1 - Instructions to the user ..........................
Page 3
8.13 - Replacing the pump motor ........................... 76 8.14 - Removing the central heating circuit pressure sensor ..................76 8.15 - Emptying the boiler .............................. 77 8.16 - Minimum and maximum power ........................... 77 8.17 - Checking the ionisation current ..........................78 COSMOGAS MYDENS 60...
Page 4
8.19 - Water temperature measurement sensors ......................78 8.20 - Outdoor temperature sensor ..........................79 8.21 - Wiring diagram ..............................80 9 - TECHNICAL DATA ............................82 10 - COMMAND MENU DIAGRAM ........................84 11 - EU DECLARATION OF COMPLIANCE ......................85 12 - PRODUCT FICHE ............................86 COSMOGAS MYDENS 60...
4. - From another room, immediately call a professionally Any options or kits added later must be original Cosmogas qualified technician or the gas supply company. Call the products. Fire Service if the former are not available.
2.1 - Presentation Congratulations! You have purchased one of the best products on the market. Each individual part is proudly designed, manufactured, tested and assembled within the COSMOGAS facilities, thus guaranteeing the best quality control. 2.2 - Overview of models MYDENS XXY “60C”...
- to achieve a high level of operating safety; charge or retailers. - to maintain a high level of environmental combustion compatibility; Offer your customer a scheduled maintenance contract. COSMOGAS MYDENS 60...
23 = Central heating system 24 = Air vent valve 25 = Safety valve 26 = Water flow rate gauge 50 = Primary heat exchanger temperature fuse * Only on model C Figure 4-1 – Hydraulic layout MYDENS 60A MYDENS 60C COSMOGAS MYDENS 60...
4.1.3 - Production of domestic hot water For the production of domestic hot water a storage tank must be connected following the diagram in figure 4-6. The temperature of the domestic hot water is adjusted following the procedure in section 7.7. COSMOGAS MYDENS 60...
4-2. The modulation range (detail “x”) can be checked using the graph in figure 4-2. Figure 4-2 KEY X = Modulation range Figure 4-2 – Residual head for MYDENS 60C with modulating pump (as standard) COSMOGAS MYDENS 60...
For this purpose the hydraulic resistances of the boiler are shown in figure 4-3 in the form of a graph. Figure 4-3 - Hydraulic resistances of MYDENS “A” boiler COSMOGAS MYDENS 60...
4.- hang the boiler on the plugs “C”; 5.- make the hydraulic connections. 5.5 - Delivery and return WARNING! COSMOGAS is not liable for any damage caused by incorrect use of additives in the central heating system. WARNING! The system after the appliance must be made with materials that resist temperatures up to 97°C and pressure of 3 bar.
The presence of air is caused by the fact that the system might not be perfectly sealed. A slow drop in system pressure due to a leak is often difficult COSMOGAS MYDENS 60...
20°C (see section 7.15). With this setting, the boiler will adjust the supply to a temperature between 20°C and 45°C. No adjustment from the command panel (also via climate control) can supply water at a temperature over 45°C. COSMOGAS MYDENS 60...
A = central heating delivery Ø 35 G = central heating return Ø 35 Figure 5-6 – Siphon funnel (on request) C = delivery fitting 1” 1/2 D = return fitting 1” 1/2 E = Gasket 1”1/2 COSMOGAS MYDENS 60...
7.- Connect the yellow/green cable to the earth terminal (see symbol); 8.- Connect the brown cable (Phase) to terminal L1; 9.- Connect the blue cable (Neutral) to terminal N. Figure 5-8 – Correct positioning of the room thermostat/programmable thermostat COSMOGAS MYDENS 60...
Once the CR04 remote control has been connected, all the room temperature adjustments and domestic hot water temperature operations must be carried out directly on the remote control. Remember to follow the instructions in the CR04 remote control manual carefully. COSMOGAS MYDENS 60...
3.- Connect the bipolar cable to the ends of the outdoor which is supplied whenever the boiler exhibits an error. temperature sensor. Maximum delivery temperature (Par.2024) Minimum delivery temperature (Par.2023) ON/OFF hysteresis Figure 5-9 – Operating rules for 0-10 VDC analogue input COSMOGAS MYDENS 60...
4184 = 1 * = Number of 2001 = 0 4147 = * appliances present The S4 Sensor switch is cascade A-LINK located here To the next appliance Figure 5-11 – Wiring diagram for appliances in a cascade COSMOGAS MYDENS 60...
If the boiler is connected to a storage tank for the to storage tank with coil preparation of domestic hot water, a disinfection cycle MYDENS 60 model boilers can be connected to a is used against legionella bacteria. This cycle involves storage tank with coil.
- C83, separated with wall intake or another point independent from the intakes of other appliances, and outlet in exhaust flue. - C93, separated with outlet on roof and intake in pre- existing channel. Figure 5-12 – Outlet/intake systems COSMOGAS MYDENS 60...
1 metre from each other. The rods must be fastened to rigid walls that can take the weight of the duct itself. Figure 5-15 – Fixing the outlet and intake pipes COSMOGAS MYDENS 60...
The condensate produced in the vertical pipe must all be conveyed into the boiler. The intake must slope towards the outside to prevent rain water entering. Figure 5-17 – Example of “80/80 PP system” installation COSMOGAS MYDENS 60...
9. Every 45° bend has a loss equivalent to the value in section 9. Figure 5-19 - Measurements and centre space distances for coaxial outlet preinstallation hole Figure 5-20 - Positioning the coaxial pipe COSMOGAS MYDENS 60...
When setting up a coaxial outlet (see figure 5-21), whether vertical and horizontal, the outlet pipe must slope upwards so that the condensate flows into the boiler. Figure 5-21 – Examples of coaxial pipe installation COSMOGAS MYDENS 60...
5 - INSTALLATION 5.18 - Installing and uninstalling the MYDENS 60 external cover kit (on request) To fit the external cover, follow the instructions below: 1 - Position upper fixing bracket “A” and the centring template “B” on the wall, as shown in figures 5-22 and 5-23;...
2.- insert a rubber tube into hole “S” and at the other end of the tube position a funnel; 3.- Use the funnel to slowly pour in about 200 cm³ of water (= a glass); 4.- reassemble everything in reverse order. 020005.01.006 Figure 6-1 – Filling the condensate drain siphon COSMOGAS MYDENS 60...
20 mbar. 3P-G31-37mbar LPG This means that the boiler is set to operate with G31 gas (propane, also known as LPG) of group P of the third family, at a supply pressure of 37 mbar. COSMOGAS MYDENS 60...
Call the Fire Service if the former are not available. 16.- Check the supply gas pressure, following the procedure in section 6.6; 020002.01.042 17.- Open the CO2 adjustment screw completely (see figure 6-7, detail “A”); Figure 6-4 – Replacing the gas nozzle COSMOGAS MYDENS 60...
6.- If the icon flashes but the radiators still do not heat up, bleed the air from the radiators again. 020002.01.023 A - Gas inlet tapping point. Figure 6-7 – Gas valve COSMOGAS MYDENS 60...
13.- Close the tapping point “A” again as in figure 6-7; 14.- Check for any gas leaks at the pressure point using suitable tools. WARNING! Test the gas seal using a soap and water solution only. The use of naked flames is prohibited. COSMOGAS MYDENS 60...
020002.01.045 by the system, the boiler switches off continuously to reach the maximum temperature allowed (93°C). A - CO2 adjustment screw at maximum power; B - CO2 adjustment screw at minimum power; Figure 6-9 – Gas valve COSMOGAS MYDENS 60...
1.- Access the “installer” profile as detailed in section 7.15; 2014 2.- Set parameter as shown in the table in figure 6-10; Figure 6-10 – Corresponding values to enter under parameter to obtain the desired power 2014 necessary in central heating line COSMOGAS MYDENS 60...
S - Key for reducing the temperature of the domestic hot water (below the minimum, the domestic hot water is set to OFF) or for scrolling through and changing the value of the parameters T - On/off switch U - Appliance in anti-freeze mode COSMOGAS MYDENS 60...
WARNING! If shutdown due to lockout occurs frequently, contact a qualified technician to restore normal operating conditions. Once the boiler has been ignited correctly, it will continue to operate for the service requested. COSMOGAS MYDENS 60...
; “Control from input 0-10 VDC with room thermostat”: The heating delivery temperature is adjusted by means of the 0-10 VDC signal as shown in figure 5-9. The opening or closing of the room thermostat has priority over the 0-10 VDC signal adjustment. COSMOGAS MYDENS 60...
- large systems, with radiant panels (low temperature), where each area is controlled by its own room thermostat and the boiler pump is stopped only when all area thermostats are satisfied (appropriate electrical system set-up required). COSMOGAS MYDENS 60...
The recommended start value is 22°C. - It is also possible to set the minimum and maximum central heating temperatures using the respective parameters 2023 2024 in section 7.15. COSMOGAS MYDENS 60...
Page 51
= Minimum heating temperature setting 2024 Par. = Maximum heating temperature setting 2025 Par. = Heating stop spring temperature 2109 Par. = Adjusting the line parallelism Figure 7-2 – Climate control graph for “high temperature” systems (with radiators) COSMOGAS MYDENS 60...
During the summer, the pump switches on once every 24 hours for 15 seconds in order to prevent any build-up from blocking it. The diverter valve and the storage tank pump (if present) are activated at the same time for the same reason. COSMOGAS MYDENS 60...
Delivery temperature (according to sensor) User °C 1006 Flue gas temperature User °C 1007 Return temperature User °C 1008 Ionisation current (see section 8.17) User μA 1012 Temperature required by climatic curve or by input 0-10 V User °C COSMOGAS MYDENS 60...
Page 54
User volt 1090 Days until maintenance (negative when the deadline has expired) User days 1098 Command board version User Hexadecimal 1099 Appliance software version User Hexadecimal 1995 Display software version User Hexadecimal * N/A = Not applicable; COSMOGAS MYDENS 60...
0-1275 2018 Heating PID factor D Factory 0-1275 2019 Climate - Winter heating temperature Installer °C 20-90 2020 Climate - Outside winter temperature Installer °C -25 to 25 2021 Climate - Spring heating temperature Installer °C 20-90 COSMOGAS MYDENS 60...
Page 56
Flow rate at which the setpoint can be reached at Factory l/min minimum power (N/A) 2062 Flow rate at which the setpoint can be reached at Factory l/min maximum power (N/A) 2063 DHW modulation timing ON/OFF Factory Secs COSMOGAS MYDENS 60...
DO NOT ATTEMPT TO RESET THEM. Please contact the manufacturer. Loc 4 Boiler in error mode for Check the last error displayed on the board. Respond according to the last error displayed. more than 20 hours COSMOGAS MYDENS 60...
Page 61
Replace the command board. command board Loc 20 Flame present 10 Replace the gas valve or the command board. seconds after gas valve is closed Loc 21 Flame present before Replace the gas valve or the command board. ignition COSMOGAS MYDENS 60...
Page 62
Loc 36 Software error on the Replace the command board. command board Loc 37 Software error on the Replace the command board. command board Loc 38 Software error on the Replace the command board. command board COSMOGAS MYDENS 60...
8.19. Check the elec- the electric circuit is damaged, repair it. Where neither tric cables for connection between the sensor and of the two previous cases apply, replace the com- the command board. mand board. COSMOGAS MYDENS 60...
Page 64
Err 136 Software error on the Replace the command board. command board Err 137 Software error on the Replace the command board. command board Err 138 Software error on the Replace the command board. command board COSMOGAS MYDENS 60...
Page 65
Replace the command board. command board Err 165 Supply current too low Power supply current too low for more than 60 seconds Err 166 Supply current too high Power supply current too high for more than 60 seconds COSMOGAS MYDENS 60...
Check that it has been connected correctly. of the two previous cases apply, replace the com- circuited) mand and control board. AttE 206 Cascade probe error Replace the command and control board (contact open or short- circuited) COSMOGAS MYDENS 60...
WARNING! Before any maintenance work, disconnect the appliance from the electrical power supply, using the relevant switch nearby. WARNING! Before any maintenance operation turn off the gas cock COSMOGAS MYDENS 60...
2. - In the event of obstructions in the drain pipe proceed with cleaning the pipe; in the event of other damage indicated above proceed with replacing the valve. COSMOGAS MYDENS 60...
1. - Check that after attempts to start the appliance, with the gas shut-off valve closed, the appliance goes into lockout mode and the “Loc 1” message appears on the display. 2. - If the lockout message does not appear, replace the command and control board. COSMOGAS MYDENS 60...
To access the electrical connections board: 1.- Turn the control panel “D” towards the front; 2.- Slide cover “E” out using the closing flaps “F”; 020005.01.007 Figure 8-1 – Removing the casing and opening the control panel COSMOGAS MYDENS 60...
If the gasket is damaged DO NOT reuse it, it must be . Consult the replaced along with the burner unit manufacturer for information on replacing it. 020005.01.008 Figure 8-2 – Removing the burner-fan unit COSMOGAS MYDENS 60...
11.- Check for any gas leaks using the relevant tools; WARNING! Test the gas seal using a soap and water solution only. The use of naked flames is prohibited. Figure 8-3 – Positioning the electrodes on the burner 020025.01.004 Figure 8-4 – Removing the electrodes COSMOGAS MYDENS 60...
13.- Check for any gas leaks using the relevant tools; WARNING! Test the gas seal using a soap and water solution only. The use of naked flames is prohibited. 020005.01.015 020025.01.040 Figure 8-5 – Removing the gas valve COSMOGAS MYDENS 60...
5.- Loosen the fitting that attaches the safety valve to the pipe; 6.- Remove safety valve “A” by taking it upwards and replace it, returning its outlet pipe to its former position. 020005.01.009 Figure 8-10 – Removing the safety valve COSMOGAS MYDENS 60...
5.- Slide out and remove pressure sensor “A” from fitting “C”, as shown in the figure. 6.- Proceed with replacing the sensor, restoring the connections to as they were before. Figure 8-13 – Removing the central heating circuit pressure sensor COSMOGAS MYDENS 60...
The electrical resistance between the two sensor contacts must correspond to figure 8-14. 1001 1002 1005 The temperature sensors are: 1006 1007 , and . Check their positioning in figures 3-1 and 3-2. Figure 8-14 - Water sensors curve COSMOGAS MYDENS 60...
On request, the external temperature sensor can be 1004 connected to the boiler (see section 5.14.5). The electrical resistance between the two sensor contacts must correspond to that shown in figure 8-15. Figure 8-15 - Outdoor temperature sensor curve COSMOGAS MYDENS 60...
Page 81
19 - System fill solenoid valve example above). This is to identify 20 - Slave appliance BUS the correct follow-on of the cables on the next page. 21 - Cascade sensor (1015) 22 - Master appliance BUS COSMOGAS MYDENS 60...
Primary heat exchanger water content Minimum operating flow rate 2500 2500 DHW adjustment range with storage tank °C 40 - 70 40 - 70 Design temperature °C Maximum central heating temperature °C Minimum central heating temperature °C COSMOGAS MYDENS 60...
Page 83
Maximum CO2 content in the combustion agent air Maximum fumes temperature for overheating °C Max. negative pressure allowed in the flue gas outlet/air intake system Condensate maximum flow rate Condensate average acidity Operating room temperature °C 0.5; + 50 0.5; + 50 Boiler weight COSMOGAS MYDENS 60...
(see section 7.16) Example of Menu 0.000 menu parameters (see section 7.15) Return to normal operation Example of Return to normal operation 0.200 menu parameters (see section 7.15) Figure 10-1 - Command menu diagram COSMOGAS MYDENS 60...
11 - EU DECLARATION OF COMPLIANCE The undersigned company COSMOGAS S.r.L., with registered office in Via L. Da Vinci no. 16 - 47014 Meldola (FC) ITALY, DECLARES under its own responsibility that the product: SERIAL No. MODEL PRODUCTION that is the subject of this declaration, complies with the model described in EU Type Test Certificate, issued by the notified body Kiwa Cermet Italia S.p.A., whose...
According to Regulations (EU) no. 811/2013 and no. 813/2013. N/A = Not applicable. (*) High-temperature regime means 60°C return temperature and 80°C delivery temperature. (**) Low-temperature regime for condensing boilers means 30°C, for low-temperature boilers, 37°C, and for other appliances, 50°C return temperature COSMOGAS MYDENS 60...
Page 88
COSMOGAS s.r.l. Via L. da Vinci 16 - 47014 MELDOLA (FC) ITALY info@cosmogas.com www.cosmogas.com...