Honeywell RAEGuard 3 User Manual page 64

Fixed gas detector
Table of Contents

Advertisement

Selectable
Default
Gas
Full Scale
Range
Range
O
30.0%vol
25.0-30.0%vol
2
H
S
100ppm
20.0-200.0ppm
2
CO
500ppm
50-1000ppm
*LEL
100%LEL
100%LEL
*CH
4
100%LEL
100%LEL
-IR
Note: The performance characteristics of the above products are typical results tested in an environment with a temperature of +20 ° C and a humidity of 50% RH. When calibrating, use the
calibration cap and the recommended flow for detection. If the sunshade/deluge protection is used instead or the detection is carried out at low temperature, its response speed will be
slowed down.
LEL model is FGM-6100/6100S. NDIR model is FGM-6200/6200S. Toxic and Oxygen models are: FGM-6300/6300S. No suffix that means aluminum alloy housing material, and "S" that
means a stainless steel housing material.
* For availability, please contact Honeywell Analytics.
1ppm is equivalent to 1μmol/mol.
Lower
Default
Resoluti
Detecta
Cal.
on
ble Limit
Point
0.1%vol
-
20.9%vol
0.1ppm
0.5ppm
50ppm
1ppm
3ppm
250ppm
1%LEL
-
50%LEL
1%LEL
-
50%LEL
RAEGuard 3 User Manual
Selectable
Response
Cal. Gas
Time T90/T10
Range
20.9%vol
<20s
<30s
(Fixed)
<25s
<25s
30 to 70%
<25s
<25s
of Full
<25s
<30s
Scale
Range
<30s
<35s
64
Default
Accuracy
Alarm 2
<±0.7%vol
23.5%vol▲
<±5ppm
20ppm▲
<±5ppm
50ppm▲
<±5%LEL
50%LEL▲
<±5%LEL
50%LEL▲
Default
Alarm 1
19.5%vol▼
10ppm▲
25ppm▲
25%LEL▲
25%LEL▲