Instruction CF-RU Repeater Unit
3 . Placing and Mounting
The Repeater Unit has been assigned
When the Repeater Unit has been assigned to the Master Controller, discon-
nect it from the temporary 20V power supply outlet
•..
Place it somewhere between the Master Controller and the room therm
stat (with the unsatisfactory link test) – see fig. – and connect it to a 20V
power supply outlet
•..
Verify the transmission to the Master Controller by making a link test from
the Repeater Unit – see
•..
Perform another link test from the room thermostat with 1) the
unsatisfactory link test or 2) where system enlargement is required
Note: Extending the transmission range of the CF2 system
•..
Up to three Repeater Units can be installed in a chain – see fig.
•..
Several chains of Repeater Units can be added to one Master Controller
– see fig.
8
VI .UH .N1 .52
Produced by Danfoss Floor Heating Hydronics 08.2008