ELECTRICAL CONNECTION

Pin
1
2
3
4
connector M12
(male)
2
1
4
3
TEACHING FUNCTION ANALOG OUTPUT
Teaching the measurement range:
The measuring range is defined by two teach points. The output signal is scaled to the taught
measuring range.
Procedure:
1. Place the target on the position of the 1st teach point (i.e. where 0 V or 4 mA should be output).
2. Connect the teaching line (Pin 4) with +V (Pin 1) for 0.1...2 s. LED flashes slowly (1 Hz).
3. Within <20 s, place the target on the position for the 2nd teach point (i.e. where 10 V or 20 mA
should be output) and connect the teaching line with +V for 0.1...2 s.
4. LED flashes 2 times:
LED flashes 4 times:
Changing the analog output signal:
The physical quantity (current/voltage) of the analog output is changed.
Procedure:
1. Connect the teaching line (Pin 4) with +V (Pin 1) for >6 s.
2. LED flashes 2 times:
LED flashes 4 times:
Analog output
+V
Analog output
GND
Teach
circuit diagram analog output
Pin 1
Pin 4
Pin 2
Pin 3
teach procedure successful
teach procedure not successful
change successful
change not successful
Switching output
+V
Teach
GND
Switching output
circuit diagram switching output
+
Teach
T
Connection cable K4P
BR
WS
BL
SW
Pin 1
+
Pin 4
Pin 2
T
Teach
Pin 3
npn
pnp