5.13. Field settings table
First
Second
code
code
Setting name
0
Remote control setup
00
Installation related setting
01
Installation related setting
02
Not applicable. Do not change the default value.
03
Status: space heating schedule timer mode
Method 1=1 / Method 2=0
04
Not applicable. Do not change the default value.
1
Automatic storage timing for domestic water heating
00
Status: night time storage
01
Night time storage start time
02
Status: day time storage
03
Day time storage start time
2
Automatic setback function
00
Status: setback operation
01
Setback operation start time
02
Setback operation stop time
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
01
High ambient temperature (Hi_A)
02
Set point at low ambient temperature (Lo_Ti)
03
Set point at high ambient temperature (Hi_Ti)
4
Disinfection function
00
Status: disinfection operation
01
Disinfection operation day selection
02
Disinfection operation start time
5
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
01
Disinfection operation time duration
02
Leaving water setback temperature
03
Room setback temperature
04
Not applicable. Do not change the default value.
6
Option setup
00
Installation related setting
01
Installation related setting
02
Not applicable. Do not change the default value.
03
Not applicable. Do not change the default value.
04
Installation related setting
7
Option setup
00
Not applicable. Do not change the default value.
01
Not applicable. Do not change the default value.
02
Installation related setting
03
Installation related setting
04
Installation related setting
8
Option setup
00
Installation related setting
01
Not applicable. Do not change the default value.
02
Not applicable. Do not change the default value.
03
Status: low noise level
04
Installation related setting
Operation manual
19
Installer setting at variance with default value
Date
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
Value
Date
Value
Default
value
Range
Step
2
2~3
1
0
–5~5
0.5
1
—
—
1 (ON)
0/1
—
1
—
—
1 (ON)
0/1
—
1:00
0:00~23:00
1:00
0 (OFF)
0/1
—
15:00
0:00~23:00
1:00
1 (ON)
0/1
—
23:00
0:00~23:00
1:00
5:00
0:00~23:00
1:00
–10
–20~5
1
15
10~20
1
70
25~80
1
45
25~80
1
1 (ON)
0/1
—
Fri
Mon~Sun
—
23:00
0:00~23:00
1:00
70
60~75
5
10
5~60
5
5
0~10
1
18
17~23
1
0
—
—
0 (OFF)
0/1
—
0 (OFF)
0/1
—
0
—
—
0
—
—
0
0/2
1
0
—
—
0
—
—
0 (A)
0/1
—
0 (OFF)
0/1
—
0 (OFF)
0/1
—
1 (ON)
0/1
—
1
—
—
0
—
—
1
1~3
1
0
0~2
1
HXHD125AV1B + HXHD200AY1B
VRV IV system indoor unit
4P513553-1 – 2017.11
Unit
—
°C
—
—
—
—
hour
—
hour
—
hour
hour
°C
°C
°C
°C
—
—
hour
°C
min
°C
°C
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—