Outdoor Unit Installation Drawings

Model
Max. allowable length
**
Min. allowable length
Max. allowable height
Additionl refrigerant
*
required for refrigerant
pipe exceeding
10m in length.
Gas pipe
Liquid pipe
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
The suggested shortest pipe length is 1.5m, in order to avoid
**
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
In sites with poor drainage, use
block bases for outdoor unit.
Adjust foot height until the unit
is leveled. Otherwise, water
leakage or pooling of water may
occur.
3
20/25/35 class
20m
1.5m
15m
20g/m
O.D. 9.5mm
O.D. 6.4mm
unit: mm
Wrap the insulation pipe with
the finishing tape from bottom
to top.
** Set the piping length
from 1.5m to 20m.
Allow space for piping
and electrical servicing.
Where there is a danger of the unit
falling, use foot bolts, or wires.
CAUTION
Stop valve cover
How to remove the stop valve cover.
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.
How to attach the stop valve cover.
Insert the upper part of the
stop valve cover into the
outdoor unit to install.
Tighten the screws.
■English