GE Fuji Electric FVR-C9S-2UX Series Instruction Manual page 30

Three-phase 230 v ac input type
Table of Contents

Advertisement

F 1 0 Restart After Momentary Power Failure
It is possible to select whether or not to restart operation when power supply is resumed after
momentary power failure.
0 Inactive
1 Active
F 1 1 Gain for Frequency Setting Signal
Outputs a frequency which is a proportional ratio of the analog frequency setting.
Selects an analog input signal level when F O 1 is _ _ 1.
0 Maximum frequency is outputted at 10V
1 Maximum frequency is outputted at 5V
When used together with the frequency setting bias,
this frequency setting gain takes priority, and the
bias applied to the frequency after the gain has
been applied.
F 1 2 DC Brake
The current level of DC brake can be set.
Taking the rated current of the drive as 100%, this current level can be set in increments of 1%.
F 1 3 DC Brake (Braking Time)
The DC braking time can be set.
0.0
Inactive
0.1 - 30.0
Braking time can be set within a
range of 0.1 to 30s (in increments of 0.1s)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
FVR-C9S-2UX
While stopped: Stopped condition is maintained even after power supply
has been restored.
While running: After power supply has been restored. LU is lit and an alarm
is outputted.
Operation is restarted in 0.5s after power supply has been restored.
(When drive is stopped, it is maintained in the stopped condition even after
power supply has been restored).
This is valid only if power supply is restored while LU is lit. The length of
time that LU will remain lit after a power failure occurs is as follows.
Drive Model
F12
Time(s)
0.7
Output
frequency
3 Hz
F25
F50
001
0.7
1.4
1.4
100%
Output
voltage
Time
002
003
005
4.0
5.5
9.0
0
1
5V
10V
Analog input
1 DC braking
29