Functional Description; Technical Data - oventrop Hydrocor WM 120 Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

Hydrocor WM
Technical description
5
Connection for potable water hot R 1 male thread
6
Connection for circulation R 3/4 male thread
7
Thermal insulation
8
Connection for heating water supply G 1 male thread
9
Sensor tube (inner diameter 15 mm)
10
Connection for heating water return G 1 male thread
11
Connection for potable water cold G 1 male thread
12
Anschluss Zirkulation R 3/4" AG
3.2

Functional description

The Hydrocor WM potable water storage tank has an
internal tube heat exchanger. Hot heating water supplied
by a closed hot water heating system flows through the
tube heat exchanger. The heat of the tube heat exchanger
is transferred to the potable water. The internal anode
protects the potable water storage cylinder against
corrosion.
3.3

Technical data

General information
Storage cylinder content
Weight
Heating surface
Performance 80 °C / 45 °C
/ 10 °C
Heat output
max. Betriebstemperatur
Speicher / Wärmetauscher
max. Betriebsdruck
Speicher / Wärmetauscher
Dimensions
Diameter with
thermal insulation
Height with thermal
insulation
Tilting dimension with
thermal insulation
Length of the anode
Diameter of the anode
Connection thread of the
anode
22
Type
120
160
200
118 l
158 l
202 l
53 kg
62 kg
97 kg
1.0 m²
1.2 m²
1.2 m²
31 kW
36 kW
36 kW
2.1
3.2
4
95 °C
10 / 16 bar
10 / 6
bar
610 mm
650 mm
825 mm
1035
1200
mm
mm
1000
1180
1365
mm
mm
mm
390 mm
480 mm
705 mm
26 mm
26 mm
22 mmm
M8
M8
G 3/4
male
thread
139501080-V02.09.2021