HEATER CONTROL

9-1. CONTROL SPECIFICATIONS AND FUNCTION SETTING
Table 1 shows how the field-installed heater is controlled. Select the desired pattern in the table below, and set the
Function on the indoor units as shown in Table 1.
Table.1 [Function table]
Select unit numbers 01 to 03 or all units (AL [wired remote controller] / 07 [IR wireless remote controller])
ode
Setting
Heater
Enable heater
1st
control
basic control
Enable heater
1st
comfort mode
2nd
Enable heater
1st
economy mode
2nd
1st: Heater output from CN24-1(yellow) on the indoor unit control board
2nd: Heater output from CN24-2(blue) on the indoor unit control board
*Refer to the Installation anual for function settings
Heater OFF
Inlet air temp. set temp.
Heater ON
Inlet air temp.< set temp. -4.5¡F(2.5¡C)
á
The fan will stop and the heater will turn off when [DEFROST] or [ERROR]
is displayed.
Heater OFF
Inlet air temp. set temp.
Heater ON
Inlet air temp.< set temp. -1.8¡F(1¡C)
á
The fan will stop and the heater will turn off when [DEFROST] is displayed.
Heater OFF
Inlet air temp. set temp.
Heater ON
Inlet air temp.< set temp. -2.7¡F(1.5¡C)
á
The fan will stop and the heater will turn off when [DEFROST] is displayed.
Heater OFF
Inlet air temp. set temp.-1.8¡F(1¡C)
Heater ON
Inlet air temp.< set temp. -3.6¡F(2¡C)
á
The fan will stop and the heater will turn off when [DEFROST] is displayed.
Inlet air temp. set temp.-1.8¡F(1¡C)
Heater ON
Inlet air temp.< set temp. -4.5¡F(2.5¡C)
á
The fan will stop and the heater will turn off when [DEFROST] is displayed.