Sensor Installation; Sensor Wiring - Honeywell Eclipse 90 Quick Start Manual

Uv scanner
Table of Contents

Advertisement

Sensor Installation

■ Incorrect sensor installation may cause the sensor
to generate a false flame signal. This can cause
unburned fuel to collect in the combustion
chamber, resulting in explosions, injuries, and
property damage. Be certain that the flame sensor
detects only the pilot and/or main flame of the
intended burner by testing the control system
under varying operating conditions and firing
rates. Follow the test procedures given in this
manual and the equipment provider's instructions
after installation and at regularly scheduled
maintenance intervals.

Sensor Wiring

Route sensor wiring a sufficient distance from ignition and
other high voltage wiring to avoid electrical interference.
Some areas may have high levels of electromagnetic
fields or ground currents that require the use of special
cables, isolation and grounding methods. Figure 1
illustrates the sensor wiring to appropriate Eclipse
controls. The blue wire supplies power and carries the
flame signal, the yellow wire connects to circuit common.
If sensor wiring is to extend beyond the supplied 10 feet
(305 cm) length, use #14 to #18 AWG wire suitable for at
least 167° F (75° C) and 600 volt insulation.
If each scanner has its own dedicated conduit, unshielded
wiring may be used for wiring runs less than 20 feet (6 m)
and that have at least one foot of separation from ignition
and other high voltage conductors. For wiring runs greater
than 20 feet (6 m) use two-conductor shielded cable (such
as Belden #8719 or #9342, or for extreme temperatures
#83322E). For multiple burner installations, shielded
cables can be run in a common conduit. Use isolated
shielded pairs to avoid the possibility of interference
(cross-talk) between wiring of multiple scanners. The
success of wiring runs of 150 feet (45 m) or more is
dependent upon site conditions; therefore the equipment
layout should be redesigned to allow the control to be
mounted closer to the burner. For these longer wiring
runs, it may be necessary to use a pair of RG62A/U coax
cables (Eclipse #21741) per scanner, with the shielding
insulated and not grounded.
2
CAUTION
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 e-mail: add028883472@gmail.com
Veri-Flame
Scanner
Blue
S1
S2
Yellow
Conduit
Multi-Flame
Scanner
Blue
3
2
Yellow
Conduit
4
Scanner
Blue
9
8
Yellow
Conduit
10
Main
Burner
Scanner
Sight Line
Figure 2. UV Scanner Sighting
Sensor Installation
In most cases, the location for this scanner will be pre-
determined by the burner manufacturer. However, proper
application of this scanner requires knowledge of the
burner, the combustion chamber, and the process.
Opposing burners, flame swirl patterns, and substance in
the line-of-sight may require special mounting techniques.
Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016
โทร: 02-888-3472
Peek-A-Flame
Scanner
Blue
7
8
Yellow
Conduit
2
Bi-Flame
Scanner
J4 3
Blue
2
Yellow
4
Conduit
Scanner
Blue
J5 1
2
Yellow
Conduit
4
Figure 1.
One-Third of
Flame Length

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eclipse 5600-90a

Table of Contents