Velocity VL-ZMB Installation Instructions

Zone monitor

Advertisement

Quick Links

General
The VL-ZMB is a six zone monitor module that is designed to be DIN mounted inside of a Velocity control panel. It's
powered and interfaced to the Velocity MMP via a RJ45 connection. The module has six class B zone monitor's which
can be typically used for conventional devices and/or for special detectors that are not available in addressable form
such as UV detectors, aspiration and beam detectors etc. The module monitors and transmits the status (normal,
open, short, or alarm) of a zone with the detectors to a control panel. Each zone input can be programmed to either
give a supervisory or alarm signal when active.
Installation
ATTENTION: THE PANEL MUST BE POWERED DOWN, AND DISCONNECTED FROM THE BATTERIES BEFORE
INSTALLING OR REMOVING ANY MODULES.
1. Ensure that the installation area is free from any cables or wires that may get caught, and that there is enough
space on the DIN rail to mount the module. Also ensure that the DIN clip underneath the module is in the open
position.
2. Place the module onto the DIN rail, hooking the metal earth clip underneath onto the rail first.
3. Once the earth clip is hooked, push the bottom of the module onto the rail so that the module sits flat.
4. Push the plastic DIN clip (located at the bottom of the module) upwards to lock and secure the module into
position.
5. Once the module is secured to the DIN rail, simply connect the supplied CAT5E cable to the module's RJ45 port.
6. Connect the other end of CAT5E cable to the nearest unoccupied RJ45 port on the termination PCB.
www.velocitydetection.com
VL-ZMB [ZONE MONITOR] Installation Instructions
Doc: GLT-295-7-1
Issue: 003
Date: 29/4/2022

Advertisement

loading

Summary of Contents for Velocity VL-ZMB

  • Page 1 General The VL-ZMB is a six zone monitor module that is designed to be DIN mounted inside of a Velocity control panel. It’s powered and interfaced to the Velocity MMP via a RJ45 connection. The module has six class B zone monitor’s which can be typically used for conventional devices and/or for special detectors that are not available in addressable form such as UV detectors, aspiration and beam detectors etc.
  • Page 2 TRM RJ45 Port Address Designation Each RJ45 port on the Velocity termination has its own unique port address. This port address is important to keep note of as it is displayed on Alarm/Trouble messages and is used when configuring or setting up cause and effects on the panel (See Velocity MMP operation manual GLT-261-7-2).
  • Page 3 Power on Procedure 1. After the above has been completed, turn the panel on (Via AC Only). The panel will follow the same power up sequence described in initial power up section above 2. The panel will now display one of the following messages: Message Meaning Panel has not detected any...
  • Page 4: Current Ratings

    The panel has detected no module changes, so has powered up and started running Check that the module configuration is as expected using the to navigate the through the port     numbers. Press the icon to confirm the changes. The new module is now configured into the panel and is ready for use.
  • Page 5 Flashing when an open circuit condition has been detected. Com. (Green) Pulses to show communication between the module and the motherboard. * When a VL-ZMB circuit is disabled, the Short & Wire Break LED’s will be on steady (Yellow). Specifications Specification...