Velocity VDOT-SCM-SCI Instruction Manual

Sounder control module

Advertisement

Quick Links

Instruction Manual
VDOT-SCM-SCI Sounder Control Module
Before Installation
Please read these instructions carefully and keep for future reference.
The information in this document is subject to change without notice.
For updates please refer to our website.
Do not use the products outside the rated power supply voltage range
specified in the Specifications. It may cause a fire or damage to
equipment.
Do not disassemble, repair, or modify the products. It may cause a fire or
electric shock.
Make sure to turn the power off before commencing any wiring work.
Otherwise it may cause electric shock or damage to equipment.
Note: Follow the requirements for the installation of the product in
accordance with the Specifications. Otherwise it may cause malfunction.
Note: Do not install the product in any location where oil, dust, iron
powder, chemicals, or hydrogen sulphide may occur or affect the product.
It may cause malfunction.
This package contains the following items:
Main unit ...........................................................................1
O u t e r c o v e r ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 1
Instruction Manual
............................................................1
Tapping screw .....................................................................2
Pan head screw
..................................................................2
EOL Resister (VDOT-RE-10k) ......................................................1
General Description
VDOT-SCM-SCI Sounder Control Module with Short Circuit Isolator is
an output module intended for use in addressable two wire systems,
which provides the control of NAC (Notification Appliance Circuit)
devices. The Notification Appliance Circuit can be wired on Class A and
Class B.
General Operation
Normal standby condition: The module receives polling from a control
panel at the regular interval. Polling LED (green) flashes.
Active condition: When receiving a control signal from the control panel,
the module operates NAC devices, and Output LED (red) illuminates.
CAUTION
!
CAUTION
!
CAUTION
!
Trouble condition: If an overcurrent occurs because SLC (Signaling Line
Circuit) is shorted, SCI LED (yellow) illuminates, and the module
communicates to the control panel the short status. The module also
communicates to the control panel the open/short status of NAC.
SCI (short circuit isolator) Function
The module has a built-in short circuit isolator. SCI circuit prevents
entire loop failure in the event of a short between L+ and L- on the loop.
If a short is detected between L+ and L-, the yellow LED indicator is
illuminated. The line between Lin- and Lout- is disconnected
automatically to isolate the short circuit, and short circuit status is
communicated to the control panel. Upon removal of the short condition,
the module will automatically connect between Lin- and Lout- to restore
the entire loop to the normal operating status.
1
ZETA ALARMS LIMITED
72-78 MORFA ROAD, SWANSEA, SA1 2EN
http://www.velocitydetection.com
Output LED (RED)
Polling LED (GREEN)
SCI LED (YELLOW)
Address Setting Port
Figure 1
Figure 2
GLT-299-7-14 Rev.01
Jan 24, 2022
mm(in)

Advertisement

loading

Summary of Contents for Velocity VDOT-SCM-SCI

  • Page 1 …………………………………………………………2 EOL Resister (VDOT-RE-10k) ………………………………………………1 General Description VDOT-SCM-SCI Sounder Control Module with Short Circuit Isolator is an output module intended for use in addressable two wire systems, which provides the control of NAC (Notification Appliance Circuit) devices. The Notification Appliance Circuit can be wired on Class A and Class B.
  • Page 2 Address Setting Use VDOT-AD2 Programmer for setting the address of the module prior to installation. VDOT-SCM-SCI has an address given at random from factory. Connect the Programmer with the address setting port to change the address to any of 1-254 (dec), with reference to the instruction manual of VDOT-AD2 Programmer.
  • Page 3 Class A Class B Connect Listed synchronization module EVCA-AP-SMD10 for the EOL (10k ohm) is connected between S+ and S- in VDOT-SCM-SCI. synchronization of NAC devices. Refer to Figure 5 for wiring. Connect Listed synchronization module EVCA-AP-SMD10 for the synchronization of NAC devices.
  • Page 4 4) After the module is brought into the active condition, reset the Specifications module. It may be necessary to allow a short time to elapse before the Applied Voltage SLC Rated Range 20 to 38VDC module is reset. I± Rated Range 16 to 30VDC Confirm that the module goes back to the initial status after the SLC Current Consumption Standby 0.8mA...
  • Page 5 Zeta’s factory. 1.3 Notwithstanding anything to the contrary in this warranty terms, Velocity shall not be liable to the customer by reason of any representation or implied warranty, condition or other term or any duty at common law, or under the express terms of this warranty...