Download Print this page

Velocity VL-SLC Installation Instructions Manual

Signaling line circuit module

Advertisement

Quick Links

General
The plug-in SLC module provides power for and handles communications to the analogue addressable devices. The
SLC continuously monitors the analogue values of all devices and displays this value on the control panel as a
percentage of the alarm threshold value. Up to 254 addresses (500mA max load) can be connected to a single SLC.
The addressable devices use soft addressing using the VDOT-AD2 handheld programming tool which helps minimise
the potential for error and reduce the installation time associated with traditional hard addressing. The AUTO-LEARN
facility provided in the Velocity series control panel saves considerable time and effort when installing a new loop or
when changing device configuration.
It allows the system to learn for itself what devices have been installed on the loop.
Installation
The MMP panel uses the expansion port number to reference modules. It is recommended that any SLC modules are
fitted first to the first expansion ports, so that the loop circuit numbers follow a logical sequence (loop 1 in port 1,
loop 2 in port 2 etc.)
ATTENTION: THE PANEL MUST BE POWERED DOWN, AND DISCONNECTED FROM THE BATTERIES BEFORE INSTALLING
OR REMOVING ANY MODULES.
1. Ensure that the installation area is free from any cables or wires that may get caught, and that there is enough
space on the DIN rail to mount the module. Also ensure that the DIN clip underneath the module is in the open
position.
2. Place the module onto the DIN rail, hooking the metal earth clip underneath onto the rail first.
3. Once the earth clip is hooked, push the bottom of the module onto the rail so that the module sits flat.
4. Push the plastic DIN clip (located at the bottom of the module) upwards to lock and secure the module into
position.
www.velocitydetection.com
VL-SLC [SIGNALING LINE CIRCUIT MODULE] Installation Instructions
Doc: GLT-294-7-2
Issue: 001
Date: 04/03/20

Advertisement

loading

Summary of Contents for Velocity VL-SLC

  • Page 1 The addressable devices use soft addressing using the VDOT-AD2 handheld programming tool which helps minimise the potential for error and reduce the installation time associated with traditional hard addressing. The AUTO-LEARN facility provided in the Velocity series control panel saves considerable time and effort when installing a new loop or when changing device configuration.
  • Page 2 TRM RJ45 Port Address Designation Each RJ45 port on the Velocity termination has its own unique port address. This port address is important to keep note of as it is displayed on Alarm/Trouble messages and is used when configuring or setting up cause and effects on the panel (See Velocity MMP operation manual GLT-261-7-2).
  • Page 3 Power on Procedure 1. After the above has been completed, turn the panel on (Via AC Only). The panel will follow the same power up sequence described in initial power up section above 2. The panel will now display one of the following messages: Message Meaning Panel has not detected any modules fitted...
  • Page 4 The panel has detected no module changes, so has powered up and started running 1. Check that the module configuration is as expected using the to navigate the through the port     numbers. Press the icon to confirm the changes. 2.
  • Page 5 Wiring recommendations The VL-SLC’s are rated for 500mA each, but in a typical UL installation (with no NAC devices powered from the loop, maximum quiescent current will be less than 60mA. Wire Gauge (AWG) Maximum Wiring Run RECOMMENDED CABLE: Twisted pair cable.
  • Page 6 Flashing green when the loop card is transmitting information. Loop RX (Green) Flashing green when the loop card is receiving information. Com. (Green) Pulses to show communication between the module and the motherboard. Specifications Specification VL-SLC Part Number 62-400 Design Standard UL864 10 Edition Approval...
  • Page 7 VDOT-S6 Addressable Sounder Base VDOT-SCI Short Circuit Isolator VDOT-STB-RL Low Power Relay Base VDOT-STB-SCI Short Circuit Isolator Base VDOT-UB4 Standard Detector Mounting 4” Base VDOT-UB4-6 Standard Detector Mounting 6” Base VDOT-ADP Adaptor Plate VDOT-AD2 Handheld Address Programmer www.velocitydetection.com Doc: GLT-294-7-2 Issue: 001 Date: 04/03/20...