Start-up, calibration and operation of the burner
5
From Normal mode, using the keys of the operator panel, it is possible to activate one of the three visualisation/programming modes:
Visualisation modes
Programming modes
Info mode
Visualises the general system information.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the key "i/reset" for 1 - 3s.
Release the key immediately when the display shows "Info".
P
/reset
1..3 s
List of the parameters that can be visualised (in the sequence
in which they are visualised)
Volumetric delivery of fuel in the unit of measurement
167
selected
Operation time with flame
162
Operation time
163
No. of resettable ignitions
164
Total no. of ignitions
166
Identification code of the burner
113
Software version
107
Control box test date
102
Identification code of the control box
103
Identification number of the group of parameters set
104
Version of the group of parameters
105
Reserved
143
End
Operating procedure in Info and Service modes
After access to these levels, the display visualises the number of the parameter
(flashing) on the left, and the corresponding value on the right.
If the value is not visualised, press the key "i/reset" for 1 - 3 s.
To return to the Parameters List, press the key "i/reset" for more than 3 s, or press
simultaneously the keys "+" and "-" (esc).
To move on to the next parameter, press the key "+" or "i/reset" for less than 1 s. At
the end of the list, the display visualises "End".
To move back to the previous parameter, press the key "-".
To return to the Normal/Standard visualisation mode, press the "i/reset" key for
more than 3 s, or press simultaneously keys "+" and "-" (esc). For a moment the
display will show "OPErAte".
Info mode (InFo)
1
Service mode (Ser)
2
Service mode (Ser)
3
m³/h
l
l/h %
Visualises the log of errors and some technical information
regarding the system.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the "i/reset" key for more than 3s.
Release the key immediately when the display shows "SEr".
P
/reset
> 3 s
List of the parameters that can be visualised (in the sequence
in which they are visualised)
Flame intensity (%)
954
Manual setting of output
121
Not defined = automatic operation
Position of the servomotors (expressed in degrees,
922
symbol
)
0 = fuel
1 = air
Number of errors
161
Log of the errors: 701-725.01, Code
701
.
.
.
725
26
GB
Service mode
m³/h
l
l/h %
P
m³/h
l
l/h %
6383