Infinite Restarts - Phase Technology PERFECT PT007 Operation & Installation Manual

Digital phase converter
Hide thumbs Also See for PERFECT PT007:
Table of Contents

Advertisement

Infinite Restarts

WARNING! Risk of electric shock. De-energize the unit by disconnecting all incoming
sources of power, then wait 30 minutes for internal charges to dissipate before servicing
the equipment.
Infinite Restarts will allow the converter to restart an unlimited number of times after fault
conditions. This procedure will require wiring two ON/OFF switches to the converter.
Standard light switches will work. See Figure 24 for wiring diagram. To add a startup delay,
follow the steps below:
Step
1
2
3
Wire dry contact switch between AUX3 and COM (now called SW3)
Wire dry contact switch between AUX4 and COM (now called SW4)
4
5
6
7
Wait several seconds until "Programmed Successfully" is shown on the display, and then
return switches to the OFF position. Turn power to converter OFF, re-install jumper wire
between AUX1 and COM, then reapply power to converter.
Remove jumper wire between AUX1 and COM
Turn power to the PT ON
Toggle SW4 until you see INFINITE RESTARTS on screen
Toggle SW3 to select between YES or NO
Action
Turn power to PT OFF
V4.1
24 |
Page