GP-3500/3600/3700 Series
Installation Guide
Caution
Be sure to read the "Warning/Caution
Information" on the attached sheet
before using the product.
Package Contents
(1) GP Unit (1)
(2) English and Japanese installation
Guides (1 of each) <This Guide>
(3) Warning/Caution Information (1)
(4) Installation Gasket (1, attached to the
GP unit)
(5) Installation Fasteners (Set of 4)
(2 sets of 4 for AGP-3750T only)
(6) RCA-BNC Convertor (1)
(Only for AGP-3550T, AGP-3560T,
AGP-3650T/U, AGP-3750T)
(7) AUX Connector
(1, Attached to the GP unit)
(8) Power Connector (1)
(Attached to the GP unit for DC type)
(9) USB Cable Clamp (2 port) (1 set)
(Holder: 1, Cover: 2)
This unit has been carefully packed, with
special attention to quality. However,
should you find anything damaged or
missing, please contact your local GP
distributor immediately.
About the Manual
For the detailed information on GP3000
series, refer to the following manuals.
• GP3000 Series Hardware Manual
• Maintenance/Troubleshooting
The manuals can be selected from the
help menu of GP-Pro EX or downloaded
from Pro-face Home Page.
URL
http://www.pro-face.com/otasuke/
About Revision
The nameplate on the GP has the
revision number of the GP. In the
example below, the asterisk, which is
placed at the "5" position, shows that the
revision number is "5".
1

Advertisement

Table of Contents
loading

Summary of Contents for Pro-face GP3700 Series

  • Page 1 The manuals can be selected from the GP unit) help menu of GP-Pro EX or downloaded (5) Installation Fasteners (Set of 4) from Pro-face Home Page. (2 sets of 4 for AGP-3750T only) http://www.pro-face.com/otasuke/ (6) RCA-BNC Convertor (1) About Revision...
  • Page 2: Part Names And Functions

    Part Names and Functions Front Left Side Rear AGP-35*0T AGP-3650T AGP-3650T M N O Bottom (With CF Card Cover open) AGP-3650T Name Description Color Indicator Operation Mode Logic execution mode (Drawing) (when logic is enabled) OFFLINE Green In operation Flashing In operation STOP When power is turned on.
  • Page 3 The interface which connects the VM unit manufactured by Digital Electronics Corporation. F VM Unit Interface (This interface is available only in units with embedded color LCD TFT display.) Auxiliary input/output / This interface is External Reset, Alarm Output, Voice Output Interface (AUX) Buzzer Output, and sound output.
  • Page 4: General Specifications

    General Specifications Electrical Specifications DC Model AC Model Input Voltage DC 24V AC 100 to 240 V Rated Voltage DC 19.2 to 28.8 V AC 85 to 265 V Allowable Voltage 1 cycle or less (Voltage drop interval 10 ms (max.) Drop must be 1s or more.) AC 100 V 0.90 A or less...
  • Page 5: Environmental Specifications

    Environmental Specifications Surrounding Air 0 to 50 °C Temperature -20 to +60 °C Storage Temperature 10 to 90 % RH (Wet bulb temperature: 39 °C max. - no Ambient Humidity condensation.) 10 to 90 % RH (Wet bulb temperature: 39 °C max. - no Storage Humidity condensation.) Dust...
  • Page 6: External Interfaces

    External Interfaces • For instructions on how to connect to other devices, always refer to the “GP-Pro EX Device/PLC Connection Manual”. • Always connect the #5 SG (Signal Ground) of the GP unit to the connected device, especially if the connected device is also not isolated. Failure to do so may damage the RS232C/RS422/RS485 circuit.
  • Page 7 COM2 • Always connect close to the GP unit's COM port when terminating with the termina- tion pins (TRMRX/TRMTX). Recommended Cable XM2A-0901 <made by OMRON Corp.> Connector Recommended Jack Screw XM2Z-0073 <made by OMRON Corp.> Recommended Cable Cover XM2S-0913 <made by OMRON Corp.> Fitting fastener #4-40 (UNC) RS422/RS485...
  • Page 8 AUX Input/Output and Sound Output Interface AGP-35*0T: S2L3.5/12/90F <made by Weidmuller> GP Unit Side AGP-3500L/AGP-3500S/ Connector S2L3.5/12/180F <made by Weidmuller> GP-3600/3700 series: Terminal Block B2L3.5/12LH <made by Weidmuller> Pin Arrangement Pin# Signal Name Direction Meaning RESET IN_A Input External Reset Input RESET IN_B Input RUN+...
  • Page 9: Installations

    Unit: mm [in.] Panel Installations thickness r≤3 [0.12] Installation Requirements • For easier maintenance, operation, and improved ventilation, be sure to install the GP at least 100 mm [3.94 in.] away from adjacent structures and other equipment. Unit:mm[in.] Panel thickness AGP-3500T 259.0 201.0...
  • Page 10 Also, the screwdriver’s tip should be flat as indicated in order to access the narrow hole of the connector: Screwdriver Tip Shape Insertion Slots Detachment Turn the tabs on the levers at both ends of the connector, and the connector is Bottom (The figure shows the GP-3500 series.) released from the GP.
  • Page 11 shock. If not enough cover is removed Power Cord Specifications the wire cannot carry a charge. Use copper conductors only. • Do not solder the wire itself. This could AC Power Cord Grounding Wire lead to a bad or poor contact. Double-Insulation 1.25 mm •...
  • Page 12 • Do not solder the cable connection. connected Doing so may damage the unit due to to the GP Power Cord abnormal heat or cause a fire. Insertion holes chassis • The power connector (plug) is CA5- DCCNL-01 made by Pro-face or...
  • Page 13: Power Supply Cautions

    • Be sure to ground the surge absorber (E1) separately from the GP unit (E2). Select a surge absorber that has a maxi- mum circuit voltage greater then that of the peak voltage of the power supply. (6) Attach the Power Connector to the GP and fix it to the GP main unit with right/left tightening screws.
  • Page 14 Holder in the direction of the arrows in Common Grounding (OK) the figure and remove the USB Cover. Tabs Other GP unit Equipment Common Grounding (Not OK) (2) Attach the USB holder to the USB Other Host Interface part of the main unit. GP unit Equipment Hook the lower pick of the USB holder...
  • Page 15: Installation Prerequisites For Standards

    Class I, Division 2”. For the detailed certification's (4) WARNING: Explosion hazard-when information, refer to the Pro-face Home in hazardous locations, turn OFF page. power before replacing or wiring <Cautions> modules.
  • Page 16 AGP3500-T1-D24/AGP3600-T1-D24/ AGP3650-T1-D24/AGP3650-U1-D24/ AGP3750-T1-D24 units are CE marked, EMC compliant products. For the detailed information, be downloaded and refer the Declaration of Conformity from Pro-face Home Page. Digital Electronics Corporation 8-2-52 Nanko-higashi Suminoe-ku, Osaka 559-0031 JAPAN TEL: +81-(0)6-6613-3116 FAX: +81-(0)6-6613-5888 http://www.pro-face.com...