Dimplex FD 9405 / L20 Operating Instructions Manual page 34

Heat pump manager
Table of Contents

Advertisement

Available languages

Available languages

Wärmepumpenmanager
































EN-10
System-specific parameters
Sets the desired return set temperature when dynamic cooling is
selected. d. The return nominal value is adapted linear to the
outside temperature. A characteristic line is used for this purpose,
which is set at two specific operating points. The return nominal
value is determined at the fixed outside temperatures of 15 °C and
35 °C.
Sets the room set temperature for silent cooling.
The actual value is measured by room climate station 1.
Settings to lower the heating characteristic curve of heating circuit
2/3.
Sets the times at which the temperature of heating circuit 2/3 is
lowered.
Sets the temperature to lower the heating characteristic curve of
heating circuit 2/3 by.
For each week day, it is possible to select whether Time1, Time2,
no time or both times are active when the temperature is lowered.
Operations to lower the temperature that exceed a week day are
activated or deactivated at the end of each day accordingly.
Settings to raise the heating characteristic curve of heating circuit
2/3.
Sets the times at which the temperature of heating circuit 2/3 is
raised.
Sets the temperature to raise the heating characteristic curve of
heating circuit 2/3 by.
For each week day, it is possible to select whether Time1, Time2,
no time or both times are active when the temperature is raised.
Operations to raise the temperature that exceed a week day are
activated or deactivated at the end of each day accordingly.
Sets the room set temperature for silent cooling. The actual value
is measured by room climate station 1/2.
Sets the time programs for dynamic cooling.
Sets the times during which dynamic cooling is blocked.
For each week day, it is possible to select whether Time1, Time2,
no time or both times are active for a block. Blocks that exceed a
week day are activated or deactivated at the end of each day
accordingly.
Sets the desired domestic hot water set temperature.
Sets the time program for domestic hot water blocks
Sets the times in which domestic hot water preparation is blocked.
For each week day, it is possible to select whether Time1, Time2,
no time or both times are active for a block. Blocks that exceed a
week day are activated or deactivated at the end of each day
accordingly.
Sets the domestic hot water set temperature which should be
maintained even during a domestic hot water block.
To carry out a thermal disinfection, the domestic hot water is
heated up once to the desired temperature. The heating period is
terminated automatically when the set temperature is reached, at
12:00 p.m. or after 4 hours at the latest.
452114.66.71 FD 9405
L20
Setting range
10 ... 15 °C ... 30
10 ... 15 °C ... 30
15.0 ... 20.0 °C ... 30.0
00:00 ... 23:59
00:00 ... 23:59
0K ... 19
N / T1 / T2 / Y
00:00 ... 23:59
00:00 ... 23:59
0 K ... 19
N / T1 / T2 / Y
15.0 ...20.0 °C ... 30.0
00:00 ... 23:59
00:00 ... 23:59
N / T1 / T2 / Y
30 ... 50 °C ... 85
00:00 ... 23:59
00:00 ... 23:59
N / T1 / T2 / Y
0 ... 10 ...
Hot water set temp.