Precautions on Installation

• Check the strength and level of the installation surface so that the unit does not
cause any operating vibrations or noise after installation.
• Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4
sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all
separately available.)
• It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm)
from the foundation surface.

Outdoor Unit Installation Diagram

Max. allowable piping length
Min. allowable piping length
**
Max. allowable piping height
Additional refrigerant required for refrigerant
*
pipe exceeding 32.8ft (10m) in length.
Gas pipe
Liquid pipe
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
** The suggested shortest pipe length is 10ft (3m), in order to avoid
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
X
Y
18-1/2
12-1/8
09/12 class
inch
inch
(470mm)
(308mm)
23-5/8
13-5/8
15/18/24 class
inch
inch
(600mm)
(346mm)
In sites with poor drainage,
use block bases for the
outdoor unit.
Adjust foot height until the unit
is level. Otherwise, water
leakage or pooling of water
may occur.
Appearance of outdoor units may differ from some models.
English
RX09/12∗
RX15/18∗
65-5/8ft (20m)
10ft (3m)
49-1/4ft (15m)
0.21oz/ft (20g/m)
O.D. 3/8 inch
O.D. 1/2 inch
(9.5mm)
(12.7mm)
O.D. 1/4 inch (6.4mm)
Allow 11-13/16" (300mm)
of work space below the
ceiling surface.
Z
3-13/16
inch
(97mm)
4-15/16
inch
(125mm)
RX24∗
98-1/2ft (30m)
65-5/8ft (20m)
O.D. 5/8 inch
(15.9mm)
Where there is a danger of the unit
falling, use foot bolts, or wires.
Wrap the insulation pipe with
finishing tape from bottom to
top.
CAUTION
Keep the piping length between
10ft (3m) and 65-5/8ft (20m)
(for 09/12 class),
10ft (3m) and 98-1/2ft (30m)
(for 15/18/24 class).
Stop valve cover
How to remove the stop
valve cover
1) Remove the screw on the
stop valve cover.
2) Slide the stop valve cover
downward to remove it.
How to attach the stop
valve cover
1) Insert the upper part of
the stop valve cover into
the outdoor unit.
2) Tighten the screw.
Allow space for piping
and electrical servicing.
4